Bryant 764A installation instructions Cooling Troubleshooting Chart, Symptom Cause Remedy

Page 19

COOLING TROUBLESHOOTING CHART

SYMPTOM

CAUSE

REMEDY

Compressor and con-

Power failure

Call power company.

denser fan will not

 

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

start.

Defective thermostat, contactor, transformer,

Replace component.

 

 

or control relay

 

 

Insufficient line voltage

Determine cause and correct.

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

 

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not

Faulty wiring or loose connections in

Check wiring and repair or replace.

start but condenser

compressor circuit

 

fan runs.

 

 

Compressor motor burned out, seized, or

Determine cause. Replace compressor.

 

internal overload open

 

 

Defective run/start capacitor, overload, or

Determine cause and replace.

 

start relay

 

 

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Compressor cycles

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and recharge

(other than normally

 

to capacities shown on nameplate.

satisfying thermostat).

 

 

Defective compressor

Replace and determine cause.

 

 

Insufficient line voltage

Determine cause and correct.

 

Blocked condenser

Determine cause and correct.

 

Defective run/start capacitor, overload,

Determine cause and replace.

 

or start relay

 

 

Defective thermostat

Replace thermostat.

 

Faulty condenser-fan motor or capacitor

Replace.

 

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates

Dirty air ®lter

Replace ®lter.

continuously.

 

 

Unit undersized for load

Decrease load or increase unit size.

 

 

Thermostat set too low

Reset thermostat.

 

Low refrigerant charge

Locate leak, repair, and recharge.

 

Leaking valves in compressor

Replace compressor.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head

Dirty air ®lter

Replace ®lter.

pressure.

Dirty condenser coil

Clean coil.

 

 

Refrigerant overcharged

Recover excess refrigerant.

 

Air in system

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair and recharge.

 

Compressor valves leaking

Replace compressor.

 

Restriction in liquid tube

Remove restriction.

Excessive suction

High heat load

Check for source and eliminate.

pressure.

 

 

Compressor valves leaking

Replace compressor.

 

 

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure too

Dirty air ®lter

Replace ®lter.

low.

Low refrigerant charge

Check for leaks, repair, and recharge.

 

 

Metering device or low side restricted

Remove source of restriction.

 

Insufficient evaporator air¯ow

Increase air quantity. Check ®lter, and replace if

 

 

necessary.

 

Temperature too low in conditioned area

Reset thermostat.

 

Outdoor ambient below 40 F

Install low-ambient kit.

 

Field-installed ®lter-drier restricted

Replace.

 

 

 

Ð19Ð

Image 19
Contents Installation Important Ð Read Before InstallingContents Safety ConsiderationsÐ2Ð Base Unit Dimensions Ð 564A/764A024-036Ð3Ð Base Unit Dimensions Ð 564A/764A042,048Ð4Ð Base Unit Dimensions Ð 564A/764A060II. RIG and Place Unit Ground-Level InstallationLocate the Unit ClearanceField-Duct Connections Physical DataÐ6Ð Ð7Ð Shipping Location of Duct Flanges Size 060 OnlyElectrical Connections Do not USE Aluminum WireÐ8Ð Unit Electrical Connection Entry Holes Control Box WiringFLA MCA Mocp LRA Electrical DataPRE-START-UP Accessory InstallationII. Cooling Section START-UP and Adjustments START-UP Heating Section START-UP and AdjustmentsIII. Indoor Airflow and Airflow Adjustments AIR Filter Care and MaintenanceII. Evaporator FAN and Motor Condenser Coil, Evaporator Coil, and Condensate Drain Pan Service CleaningRepairing Refrigerant Leaks Unit Top RemovalVI. Metering Device Servicing IV. Electrical Controls and WiringIX. Replacement Parts Indoor AirflowCooling Charging Chart Ð 564A/764A024 Cooling Charging Chart Ð 564A/764A048 Symptom Cause Remedy Cooling Troubleshooting ChartPage Page Packaged Service Training Page III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information

764A specifications

The Bryant 764A is a high-performance air conditioning and heating system that exemplifies efficiency and reliability for residential and commercial use. Designed to deliver optimal comfort in various climates, the 764A is known for its impressive energy efficiency ratings and advanced technologies.

One of the standout features of the Bryant 764A is its variable speed compressor. This innovative component allows the system to adjust its output according to the specific cooling or heating demands of the environment. By operating at different speeds, the compressor can maintain a consistent indoor temperature while using less energy compared to traditional single-stage systems. This not only enhances comfort but also contributes to significant energy savings over time.

The Bryant 764A is equipped with a smart thermostat that offers precise control over indoor climates. This thermostat can be programmed to adjust temperatures based on user preferences and schedules, further improving energy efficiency. Users can also control the system remotely via a smartphone app, ensuring comfort is just a tap away.

In terms of its construction, the Bryant 764A is built with durability in mind. The unit features a robust cabinet designed to withstand harsh weather conditions, which extends the lifespan of the system. Additionally, its sound-dampening technology minimizes operational noise, creating a more peaceful indoor environment.

The 764A incorporates advanced filtration systems to improve indoor air quality. With allergen filtration capabilities, it effectively reduces dust, pollen, and other airborne particles, making it an excellent choice for allergy sufferers. This focus on air quality aligns with Bryant's commitment to creating healthier living spaces.

Moreover, the Bryant 764A is designed with environmentally friendly refrigerants, aligning with modern standards for reducing greenhouse gas emissions. This commitment to sustainability is becoming increasingly important for consumers looking to reduce their environmental footprint.

Overall, the Bryant 764A stands out as a comprehensive solution for heating and cooling needs. With its variable speed technology, smart thermostat, durable construction, and focus on air quality, it offers both efficiency and comfort, making it a wise investment for any property owner looking to enhance their indoor environment.