Outback Power Systems GTFX, GVFX manual List of AUX Functions, Adjustable AUX Output Functions

Page 21

LIST OF AUX FUNCTIONS

Cool Fan activates the standard TurboFan which cools the FX.

Divert DC and Divert AC allows the AUX to divert excess renewable energy to a DC or AC load, respectively. This allows control of energy sources such as wind turbines or hydro-generators. When using Divert AC, the AUX output will shut off if the inverter is overloaded.

AC Drop is activated when an AC power source disconnects from an FX. An indicator, such as an alarm, connected to the AUX warns a user that AC power is no longer available.

Vent Fan provides 0.7 amps to run a 12 VDC fan for removing hydrogen from the battery compartment. Vent Fan can operate automatically when the VENTFAN ON voltage set point is exceeded or it can operate intermittently by adjusting the VENTFAN OFF PERIOD.

In Fault mode, the AUX can send an alarm signal via radio, pager, or telephone device when the FX enters into an error condition. Fault mode can also be used to log error conditions by triggering an event recording device.

GenAlert, through a 12VDC relay, will tell the system to start a two-wire type generator when the battery voltage falls below a certain set point. GenAlert can be adjusted according to the shortfallbattery voltage, the amount of time spent at this voltage, the recharged voltage and amount of time at this voltage before GenAlert is de-energized.

Load Shed energizes the AUX the reduce the load demand on the batteries and the inverter function, thus acting as a load management system.

Setting the AUX to Remote allows a message sent through the serial port on the MATE to switch the AUX on and off.

Note: Using Advanced Generator Start (AGS) overrides any programmed AUX function.

Adjustable AUX OUTPUT FUNCTIONS

There are four AUX functions whose settings can be adjusted by the user:

Diversion

Vent Fan

GenAlert

Load Shed

ADV/FX/AUX

-------------P00

 

aux output

Remote

From the Remote aux output function screen, press

function

 

the <DOWN> soft key

 

 

DOWN INC

DEC PORT

 

20

Image 21
Contents Grid-Interactive About Outback Power Systems Warranty SummaryDisclaimer Contact InformationTable of Contents Condition Voltage Range VAC Frequency Hz Seconds Allowed Important Safety Instructions Grid-INTERACTIVE FX Series Inverter/Charger Programming Stacking ConcernsStacking Options Components and Connections LED Color LED Action LED Indicates Mate Screens Classic Stacking Stacking OptionsStacking and Assigning FX Status Master141 Programming the FXsADV Down INC DEC Classic Slave MasterPower Save Levels AC on Turn the AC input breakers on Auxiliary AUX Functions ADV/PASSWORD P00 List of AUX Functions Adjustable AUX Output FunctionsP00 ADV/FX/AUX Battery Charging Instructions MaintenanceBattery Charging Setpoints GenAlert Off Set Point On Set Point FX Default Values subject to change with FX upgradesOutBack Power Systems Two Year Limited Warranty WarrantyProduct Registration Extended Warranty Application U.S. and Canada onlyGTFX, Gvfx and PS1 Products Year Limited Warranty CaliforniaRevision.2007-06-01 Installer Year Warranty Registration CaliforniaSystem Owner Product