Outback Power Systems GVFX, GTFX manual P00

Page 22

ADV/FX/AUX-------------

P00

aux output

Remote

function

 

DOWN INC DEC

PORT

ADV/FX/AUX---------------

P00

genalert

11.5vdc

on setpoint

 

DOWN INC DEC

PORT

ADV/FX/AUX---------------

P00

loadshed

11.0 vdc

off setpoint

 

DOWN INC DEC

PORT

ADV/FX/AUX---------------

P00

ventfan

13.0 vdc

on setpoint

 

DOWN INC DEC

PORT

From the Remote aux output function screen, press the <DOWN> soft key. This will bring up the first of several screen used to adjust which ever mode you have chosen for the AUX function.

The genalert on setpoint functions are not available for grid-interactive FXs. Press the <DOWN> soft key three times to view the loadshed off setpointscreen.

The loadshed off setpointis the battery voltage which triggers the AUX to reduce the inverter and battery loads. When the battery voltage drops below this value for three seconds, the AUX powers a DC coil relay to disconnect an AC load. Once triggered, loadshed remains on for at least three minutes. The loadshed off setpointis adjustable from10 VDC-14 VDC in 0.1 VDC increments using the <INC> and <DEC> soft keys. Press the <DOWN> soft key to bring up the ventfan on setpoint.

When the AUX is set to ventfan, a fan ventilates a battery enclosure. The ventfan on setpoint establishes the battery voltage which energizes the AUX and thus the fan for a one minute period. The voltage setting has a range of 10.0 VDC-16.0 VDC in 0.1 VDC increments using the <INC> and <DEC>

soft keys. Recharging causes batteries to emit mostly hydrogen gas; higher recharging voltages emit more gas. Press the <DOWN> soft key to view the ventfan off periodscreen.

21

Image 22
Contents Grid-Interactive Disclaimer Warranty SummaryAbout Outback Power Systems Contact InformationTable of Contents Condition Voltage Range VAC Frequency Hz Seconds Allowed Important Safety Instructions Stacking Concerns Grid-INTERACTIVE FX Series Inverter/Charger ProgrammingStacking Options Components and Connections LED Color LED Action LED Indicates Mate Screens Stacking and Assigning FX Status Stacking OptionsClassic Stacking MasterProgramming the FXs 141ADV Down INC DEC Master Classic SlavePower Save Levels AC on Turn the AC input breakers on Auxiliary AUX Functions ADV/PASSWORD P00 Adjustable AUX Output Functions List of AUX FunctionsP00 ADV/FX/AUX Maintenance Battery Charging InstructionsBattery Charging Setpoints FX Default Values subject to change with FX upgrades GenAlert Off Set Point On Set PointWarranty OutBack Power Systems Two Year Limited WarrantyExtended Warranty Application U.S. and Canada only Product RegistrationYear Limited Warranty California GTFX, Gvfx and PS1 ProductsRevision.2007-06-01 System Owner Year Warranty Registration CaliforniaInstaller Product