Bryant 702B installation instructions installation, start-up, and operating instructions, 583B

Page 1

installation, start-up,

583B

and operating instructions

683B

 

602B

ICM FIOP INSTALLATION INSTRUCTIONS

702B

NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS

 

SAFETY CONSIDERATIONS

1

INTRODUCTION

2

RECEIVING AND INSTALLATION

2

ICM FIOP PRE-START-UP

2

Electrical Connections

2

Control Voltage Connections

2

Standard Connection

2

Easy Select™— 583B

2

583B Sequence of Operation

4

Easy Select™— 683B

5

683B Sequence of Operation

7

Easy Select™— 702B & 602B

7

702B & 602B Sequence Of Operation

9

ICM FIOP START-UP

10

583B Start-Up (ICM FIOP)

10

683B Start-Up (ICM FIOP)

10

702B: Start-Up (ICM FIOP)

11

602B: Start-Up (ICM FIOP)

11

ELECTRICAL DATA & SCHEMATICS—ICM FIOP

12

Physical Data & Electrical Schematics

12

Tables For System Set-Up

12

CARE AND MAINTENANCE

12

TROUBLESHOOTING

13

START-UP CHECKLIST

13

NOTE TO INSTALLER — READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY before installing this unit. Also, make sure the Owner’s Manual and Service Instructions are left with the unit after installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

—1—

Cancels: II 583B-24-2

II 583B-24-3

 

11-01

C99087

Fig. 1—Puron® Unit (583B Shown)

WARNING: Improper installation, adjustment, alter- ation, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences, which could cause serious injury or death or damage your property. Consult a qualified installer or service agency for infor- mation or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product.

Recognize safety information. This is the safety-alert symbol . When you see this symbol on the product or in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words — DANGER, WARNING, CAU- TION, and NOTE. Danger identifies the most serious hazards, which will result in severe personal injury or death. Warning indicates a condition that could cause serious personal injury or death. Caution is used to identify unsafe practices, which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

The power supply (volts, phase, and hertz) must correspond to that specified on unit rating plate.

The electrical supply provided by the utility must be sufficient to handle load imposed by this unit. Electrical supply must match the voltage requirements listed on unit rating plate.

This installation must conform with local building codes and with NEC (National Electrical Code). Refer to provincial and local plumbing or waste water codes and other applicable local codes. Approved for outdoor installation on wood flooring or on class A, B or C roof covering materials.

Image 1 Bryant 702B installation instructions installation, start-up, and operating instructions, 583B, 683B, 602B
Contents ICM FIOP INSTALLATION INSTRUCTIONS installation, start-upTABLE OF CONTENTS SAFETY CONSIDERATIONSC. Easy SelectÐ583B RECEIVING AND INSTALLATIONINTRODUCTION ICM FIOP PRE-START-UP I. ELECTRICAL CONNECTIONSFor Gas Heat/Electric Cool Unit±AC must be selected CONFIGURATION should be used when the rated ARI perforFig. 4Ð702B High- and Control-Voltage Connections Fig. 5Ð602B High- and Control-Voltage ConnectionsFig. 7ÐHumidistat Wiring for De-Humidify Mode-583B Fig. 6ÐHumidifier Wiring-583BD. 583B Sequence of Operation Fig. 8ÐDetail of SPP Printed-Circuit Board E. Easy SelectÐ683BFig. 9ÐHumidifier Wiring-683B HUM G HUMIDIFIER WIRINGFig. 10ÐThermidistat Wiring for De-Humidify Mode-683B THERMIDISTATF. 683B Sequence of Operation EASY SELECT CONFIGURATION TAPS FOR 702B & 602BFig. 11ÐDetail of SPP Printed-Circuit Board The type of system will be factory selected see below for details 1. LO speedÐFactory setting, 50 percent cooling mode airflow Ð8Ð1. AC-Air conditioner Factory Selected for 702B 3. SYSTEM TYPE-Factory selected AC 702B or HP-EFF 602BFig. 13ÐHumidistat Wiring for De-Humidify Mode-for 702B & 602B Fig. 12ÐHumidifier Wiring for 702B & 602BH. 702B & 602B Sequence Of Operation ICM General Start Up ICM FIOP START-UPI. 583B START-UP ICM FIOP II. 683B START-UP ICM FIOPIV. 602B START-UP ICM FIOP III. 702B START-UP ICM FIOP2. Thermostat Thermidistat or Thermostat and HumidistatI. PHYSICAL DATA & ELECTRICAL SCHEMATICS ELECTRICAL DATA & SCHEMATICSÐICM FIOPCARE AND MAINTENANCE TABLE 1ÐICM FIOP PHYSICAL DATAÐUNIT 583BTABLE 2ÐICM FIOP PHYSICAL DATAÐUNIT 583B CONTINUED TROUBLESHOOTING START-UP CHECKLISTTABLE 3Ð583B WITH ICM FIOP ELECTRICAL DATA Ð14Ð Fig. 14ÐICM FIOP Electric SchematicÐUnit 583BÐ15Ð TABLE 4ÐICM FIOP PHYSICAL DATAÐUNIT 683BTABLE 6Ð683B WITH ICM FIOP ELECTRICAL DATA TABLE 5ÐICM FIOP PHYSICAL DATAÐUNIT 683B CONTINUEDÐ16Ð Ð17Ð Fig. 15ÐICM FIOP Electric SchematicÐUnit 683BÐ18Ð TABLE 7ÐICM FIOP PHYSICAL DATAÐUNIT 702BÐ19Ð TABLE 8Ð702B WITH ICM FIOP ELECTRICAL DATAÐ20Ð Fig. 16ÐICM FIOP Electrical SchematicÐ702BÐ21Ð TABLE 9ÐICM FIOP PHYSICAL DATAÐUNIT 602BÐ22Ð TABLE 10Ð602B WITH ICM FIOP ELECTRICAL DATAÐ23Ð Fig. 17ÐICM FIOP Electrical SchematicÐ602BDRY COIL ICM AIRFLOW SMALL CABINET TABLE 11±583B & 683B COOLING AND HEAT PUMP HEATING-683B ONLYTABLE 12Ð583B & 683B COOLING AND HEAT PUMP HEATING-683B ONLY DRY COIL ICM AIRFLOW LARGE CABINETTABLE 15Ð583B & 683B ICM AIR FLOW VS. TEMPERATURE RISE CHART TABLE 14Ð583B & 683B GAS HEATING ICM AIRFLOW LARGE CABINETTABLE 16Ð702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW SMALL CABINETLARGE CABINET TABLE 17Ð702B/602B COOLING & HEATING DRY COIL ICM AIRFLOWTABLE 18ÐMINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION CFM TABLE 19ÐELECTRIC HEAT PRESSURE DROP TABLE IN. WG SMALL CABINETTABLE 22ÐFILTER PRESSURE DROP TABLE IN. WG TABLE 21ÐICM FIOP WET COIL PRESSURE DROP IN. WGTABLE 23ÐELECTRIC HEATER MULTIPLICATION FACTORS Ð27ÐTABLE 24ÐTROUBLESHOOTING CHART THERMIDISTAT CONTROL SETTINGSQUICK REFERENCE GUIDE SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURESIV. EASY SELECT SETTINGS START-UP CHECKLIST Remove and Store in Job FileEASY SELECT I. Preliminary InformationPrinted in U.S.A Ð30Ðii583b243 Catalog No
Related manuals
Manual 30 pages 21.04 Kb Manual 28 pages 39.19 Kb

602B, 683B, 702B, 583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.