Bryant 583B, 683B III. 702B START-UP ICM FIOP, IV. 602B START-UP ICM FIOP, Thermostat

Page 11

remains on for 4 minutes. Observe that compressor, outdoor fan and indoor blower motors start after the call for Cooling. At the end of 4 minutes, the cooling cycle stops and the MODE reverts back to OFF. The Indoor Blower continues to run for the time selected on the Easy Select™ board after OFF icon is displayed.

(3.) HEAT PUMP HEATINGÐ

Press MODE button on the Thermidistat™ until HEAT icon is displayed. Heat pump heating begins within 10 sec. and remains on for 4 minutes. Observe that the compres- sor, outdoor fan and indoor blower come on. At the end of the 4 minutes, heating cycle stops and the MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™ Board after the OFF icon is displayed. Heating maybe turned off anytime during the 4 minute cycle by pressing MODE button until OFF is displayed.

(4.) GAS HEAT MODEÐ

Press MODE button until E-HEAT(Emergency Heat or Back-Up Heat) icon is displayed. Gas heating begins within 10 sec. and remains on for 4 minutes. The induced draft motor should start immediately. The burners should light within 5 sec. of E-HEATcall. The indoor blower will turn on 45 sec. after the flame has been established. Gas heating stops at the end of 4 minutes and MODE reverts back to OFF. The indoor blower continues to run for the time selected on the Easy Select™ Board after the OFF icon is displayed.

NOTE: If the burners do not light, this lighting sequence is repeated for 15 minutes from the initial call for E-HEAT.If after 15 minutes the burners do not light, there will be a lockout. To reset the burner lockout control, break the 24-v. power to ªWº.

(5.) AUTOMATIC CHANGE-OVERÐ

To test AUTO CHANGE-OVERfunction between COOL and HEAT:

Enable the AUTO CHANGE-OVERmode during Thermi- distat™ set-up. Refer to the Thermidistat™ literature for details. Observe that the unit operates in cooling when in COOL MODE (when setting is below room temperature) and HEAT MODE (when setting is above room tempera- ture).

AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges.

The heating operation airflow must produce a temperature rise that falls with in the approved range.

Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required.

III.702B: START-UP (ICM FIOP)

CHECKING COOLING CONTROL OPERATION±Start and check the unit for proper cooling control operation as follows:

(1.) Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.

(2.) Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the selected off delay.

Ð11Ð

(3.) When using an auto-changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in heating mode when tempera- ture control is set to ``call for heating'' (above room temperature) and operates in cooling mode when tempera- ture control is set to ``call for cooling'' (below room temperature).

NOTE: Once the compressor has started and then has stopped, it will not start again until 5 minutes have elapsed. (The cooling cycle remains ``on'' until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ``breaks'' the circuit between ther- mostat terminal R to terminals Y and G.) These open circuits de-energize contactor coil C and ICM board. The condenser and compressor motors stop. After the time delay setting selected on the Easy Select™ board (See Easy Select Section) , the blower motor stops. The unit is in a ``standby'' condition, waiting for the next ``call for cooling'' from the room thermostat.

IV. 602B: START-UP (ICM FIOP)

CHECKING COOLING AND HEATING CONTROL OPERA- TION± Start and check the unit for proper control operation as follows:

(1.) Place room thermostat SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down according to time delay selected on the Easy Select™ board (See Easy Select Section) when FAN MODE switch is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (through unit wire G) across the 24-v. secondary of transformer (TRAN).

Thermidistat™ or Thermostat and Humidistat:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat ter- minal R to terminals Y, O, DH, and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and ICM board (though unit wire G) across the 24-v. secondary of transformer (TRANS).

(3.) Place system switch or MODE control in HEAT position. Set control above room temperature. Observe that com- pressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down according to time delay selected on the Easy Select™ board (See Easy Select Section) when control setting is satisfied.

(4.) When using an automatic changeover room thermostat, place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to ªcall for Coolingº (below room temperature), and unit operates in Heating mode when temperature control is set to ªcall for Heatingº (above room temperature).

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains ``on'' until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ``breaks'' the circuit between thermostat terminal R to terminals Y and G. These open circuits de-energize contactor coil C and ICM board. The con- denser and compressor motors stop. After the time delay setting selected on the Easy Select™ board (See Easy Select Section) , the

Image 11
Contents SAFETY CONSIDERATIONS installation, start-upICM FIOP INSTALLATION INSTRUCTIONS TABLE OF CONTENTSICM FIOP PRE-START-UP I. ELECTRICAL CONNECTIONS RECEIVING AND INSTALLATIONC. Easy SelectÐ583B INTRODUCTIONFig. 5Ð602B High- and Control-Voltage Connections CONFIGURATION should be used when the rated ARI perforFor Gas Heat/Electric Cool Unit±AC must be selected Fig. 4Ð702B High- and Control-Voltage ConnectionsD. 583B Sequence of Operation Fig. 6ÐHumidifier Wiring-583BFig. 7ÐHumidistat Wiring for De-Humidify Mode-583B Fig. 8ÐDetail of SPP Printed-Circuit Board E. Easy SelectÐ683BTHERMIDISTAT HUM G HUMIDIFIER WIRINGFig. 9ÐHumidifier Wiring-683B Fig. 10ÐThermidistat Wiring for De-Humidify Mode-683BFig. 11ÐDetail of SPP Printed-Circuit Board EASY SELECT CONFIGURATION TAPS FOR 702B & 602BF. 683B Sequence of Operation 3. SYSTEM TYPE-Factory selected AC 702B or HP-EFF 602B 1. LO speedÐFactory setting, 50 percent cooling mode airflow Ð8ÐThe type of system will be factory selected see below for details 1. AC-Air conditioner Factory Selected for 702BH. 702B & 602B Sequence Of Operation Fig. 12ÐHumidifier Wiring for 702B & 602BFig. 13ÐHumidistat Wiring for De-Humidify Mode-for 702B & 602B II. 683B START-UP ICM FIOP ICM FIOP START-UPICM General Start Up I. 583B START-UP ICM FIOPThermidistat or Thermostat and Humidistat III. 702B START-UP ICM FIOPIV. 602B START-UP ICM FIOP 2. ThermostatTABLE 1ÐICM FIOP PHYSICAL DATAÐUNIT 583B ELECTRICAL DATA & SCHEMATICSÐICM FIOPI. PHYSICAL DATA & ELECTRICAL SCHEMATICS CARE AND MAINTENANCETABLE 3Ð583B WITH ICM FIOP ELECTRICAL DATA TROUBLESHOOTING START-UP CHECKLISTTABLE 2ÐICM FIOP PHYSICAL DATAÐUNIT 583B CONTINUED Ð14Ð Fig. 14ÐICM FIOP Electric SchematicÐUnit 583BÐ15Ð TABLE 4ÐICM FIOP PHYSICAL DATAÐUNIT 683BÐ16Ð TABLE 5ÐICM FIOP PHYSICAL DATAÐUNIT 683B CONTINUEDTABLE 6Ð683B WITH ICM FIOP ELECTRICAL DATA Ð17Ð Fig. 15ÐICM FIOP Electric SchematicÐUnit 683BÐ18Ð TABLE 7ÐICM FIOP PHYSICAL DATAÐUNIT 702BÐ19Ð TABLE 8Ð702B WITH ICM FIOP ELECTRICAL DATAÐ20Ð Fig. 16ÐICM FIOP Electrical SchematicÐ702BÐ21Ð TABLE 9ÐICM FIOP PHYSICAL DATAÐUNIT 602BÐ22Ð TABLE 10Ð602B WITH ICM FIOP ELECTRICAL DATAÐ23Ð Fig. 17ÐICM FIOP Electrical SchematicÐ602BDRY COIL ICM AIRFLOW LARGE CABINET TABLE 11±583B & 683B COOLING AND HEAT PUMP HEATING-683B ONLYDRY COIL ICM AIRFLOW SMALL CABINET TABLE 12Ð583B & 683B COOLING AND HEAT PUMP HEATING-683B ONLYSMALL CABINET TABLE 14Ð583B & 683B GAS HEATING ICM AIRFLOW LARGE CABINETTABLE 15Ð583B & 683B ICM AIR FLOW VS. TEMPERATURE RISE CHART TABLE 16Ð702B/602B COOLING & HEATING DRY COIL ICM AIRFLOWTABLE 19ÐELECTRIC HEAT PRESSURE DROP TABLE IN. WG SMALL CABINET TABLE 17Ð702B/602B COOLING & HEATING DRY COIL ICM AIRFLOWLARGE CABINET TABLE 18ÐMINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION CFMÐ27Ð TABLE 21ÐICM FIOP WET COIL PRESSURE DROP IN. WGTABLE 22ÐFILTER PRESSURE DROP TABLE IN. WG TABLE 23ÐELECTRIC HEATER MULTIPLICATION FACTORSSET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES THERMIDISTAT CONTROL SETTINGSTABLE 24ÐTROUBLESHOOTING CHART QUICK REFERENCE GUIDEI. Preliminary Information START-UP CHECKLIST Remove and Store in Job FileIV. EASY SELECT SETTINGS EASY SELECTCatalog No Ð30ÐPrinted in U.S.A ii583b243
Related manuals
Manual 30 pages 21.04 Kb Manual 28 pages 39.19 Kb

602B, 683B, 702B, 583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.