Omega Vehicle Security DRA-RTM-8 General Description, Mounting Instructions, Replacing Fuses

Page 4

1. GENERAL DESCRIPTION

The DRA-RTM-8 is a multiplexer for 16 analog inputs - eight of which, marked

1-8, are direct inputs for Pt-100 sensors, while the remaining (9-16), are for 4- 20mA current loops.

The DRA-RTM-8 output format is a 4-20mA current loop, with a 28mA limitation.

Each Pt-100 input has its own signal conditioner, allowing each input to be calibrated separately. Each signal conditioner includes six DIP switches for coarse calibration and two potentiometers for fine tuning.

2. MOUNTING INSTRUCTIONS

The DRA-RTM-8 is designed for standard DIN rail mounting.

Place the unit on the upper part of the mounting rail with the fastening tab facing down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit to the rail. Once the tab is loosened, ensure that the unit is fastened securely in place.

3. REPLACING FUSES

To replace a blown fuse, disassemble the unit as follows:

a. Take off both terminal strips by removing the four screws at the edges.

Note: This does not require disconnecting the cables connected to the strips.

b. Remove the front panel using a suitable flat screwdriver. Press down gently on the plastic springloaded tabs located in the slots on either side of the unit.

c. Disconnect the flat connectors which connects the front panel printed circuit. d. Replace the blown fuse.

WARNING: Never install a fuse rated more than 800mA

4. ASSEMBLY

The DRA-RTM-8 unit includes two printed circuit cards designated as P.N 7020 and P.N 7021. The two printed circuit cards should occupy the slots in the enclosure according to fig 1.

2

Image 4
Contents User’s Guide Omega.comTM Contents Assembly General DescriptionMounting Instructions Replacing FusesConnecting Transmitters to the Multiplexer TWO Wire TransmitterFour Wire Transmitter Current InputsEnable Connecting the DRA-RTM-8 to a PLCControl Address Address Polarity see figCalibration Procedure True High SettingCalibration Calibration Tables Zero Coarse Calibration Tables Span Coarse Calibration TablesMultidrop Configuration Analog Inputs RTD InputWARRANTY/DISCLAIMER Temperature