Omega Vehicle Security manual DRA-DCC-8 Calibration

Page 11

The channel LEDs are connected in series with the output current so that they will light only as an indication of a closed current loop.

Note: After every power on, the unit is reset and the initialized default output currents are according to the SW6 setting (see para #5.2).

In the parallel control mode, internal pull-up resistors on each of the input terminals keep them in logical 1 state. The unit will recognize input voltage up to 0.5V as logical 0 and voltages from 4V to 60V as logical 1.

11. DRA-DCC-8 CALIBRATION

Generally there is no need to calibrate the DRA-DCC-8 unit. However if calibration is required, the following steps should be carried out: Two potentiometer trimmers, one for "Zero" and the other for "Span" are located on printed card 7040. The trimmer close to the card edge is the "Zero". Use the following switch setup for switching all the outputs between 4 and 20mA

MODE

S1

S2

S3

S4

S5

S6

S7

ALL CH. = 4mA

OFF

OFF

X

X

X

ON

OFF

ALL CH. = 20mA

OFF

ON

X

X

X

ON

OFF

Note: Set the unit to sink mode (fig.2).

Step 1:

Select one channel (for example ch.#1) for the initial tuning. Set the DIPswitch array to "all 4mA".

Apply supply voltage to the unit. The initial state of all the output currents is 4 mA. Use SW2 to switch all the outputs between 4 and 20mA. Iteratively set the "Zero" and the "Span" trimmers for 4.00mA and 20.00mA.

Step 2:

Monitor all the 8 channels in 4mA state, and calibrate the Zero trimmer so that their average readings is 4.000mA.

Then repeat for 20mA state, and calibrate the Span trimmer so that their average readings is 20.000mA. This procedure should be repeated until calibration is satisfactory.

9

Image 11
Contents User’s Guide Omega.comTM Contents Replacing Fuses AssemblyMounting Instructions Supply Voltage 0-20 or 4-20mA Output Current ModeSwitch Settings Parallel Control ModePLC Interface Parallel Control ModeSerial Control Mode RS422 Termination Serial Control ModeE Enable Terminal Serial Control Switch SettingsWithout Echo Back Format Command FormatsThree types of command formats are available Baud Rate SelectStatus Report Format Self Test ModesSelf Test #2 Same Level Multidrop ConfigurationPutting the Unit Into Operation Self Test #1 Communication Ports TestDRA-DCC-8 Calibration Relative Humidity Housing WARRANTY/DISCLAIMER Temperature