REFRIGERANT PIPING LENGTH LIMITATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puronr Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
|
| Liquid |
| AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor |
| |||||||
Size | Liquid Line | Line |
|
|
| Vertical Separation ft (m) |
|
|
|
| ||
Connection | Diam. |
|
|
|
|
|
|
|
|
|
| |
|
| |||||||||||
|
| w/ TXV |
| |||||||||
18000 |
| 1/4 | 150 | 150 | 125 | 100 | 100 | 75 |
| |||
AC with | 3/8 | 5/16 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 225* |
| 150 |
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
| 3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 250* |
| 250* | |
|
|
| ||||||||||
24000 |
| 1/4 | 75 | 75 | 75 | 50 | 50 |
| ||||
AC with | 3/8 | 5/16 | 250* | 250* | 250* | 250* | 250* | 225* | 175 | 125 |
| 100 |
Puron |
| 3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 250* |
| 250* |
|
|
| ||||||||||
30000 |
| 1/4 | 30 |
| ||||||||
AC with | 3/8 | 5/16 | 175 | 225* | 200 | 175 | 125 | 100 | 75 |
| ||
Puron |
| 3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 250* |
| 250* |
|
|
| ||||||||||
36000 |
| 5/16 | 175 | 150 | 150 | 100 | 100 | 100 | 75 |
| ||
AC with | 3/8 |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
3//8 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 250* |
| 250* | ||
Puron |
|
| ||||||||||
42000 |
| 5/16 | 125 | 100 | 100 | 75 | 75 | 50 |
| |||
AC with | 3/8 |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 250* | 250* |
| 150 | ||
Puron |
|
| ||||||||||
48000 |
|
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 230 | 160 |
| |
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
49000 |
|
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* | 250* | 250* | 250* | 250* | 250* | 230 | 160 |
| |
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
60000 |
|
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* | 250* | 250* | 225* | 190 | 150 | 110 |
| ||
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
61000 |
|
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* | 250* | 250* | 225* | 190 | 150 | 110 |
| ||
Puron |
|
|
|
|
|
|
|
|
|
|
|
|
* Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
---
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
|
| Liquid |
| AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor | |||||||
Size | Liquid Line | Line |
|
|
|
| Vertical Separation ft (m) |
|
|
| |
Connection | Diam. |
|
|
|
|
|
|
|
|
| |
| 25 |
| |||||||||
|
| w/ TXV | (7.6) |
| |||||||
18000 |
| 1/4 | 175 |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
AC with | 3/8 | 5/16 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
| 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
|
|
| |||||||||
24000 |
| 1/4 | 100 |
| 125 | 175 | 200 | 225* | 250* | 250* | 250* |
AC with | 3/8 | 5/16 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
| 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
|
|
| |||||||||
30000 |
| 1/4 | 30 |
| |||||||
AC with | 3/8 | 5/16 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
|
|
|
|
|
|
|
|
|
|
|
| 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* | |
|
|
| |||||||||
36000 | 3/8 | 5/16 | 225* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
AC with |
|
|
|
|
|
|
|
|
|
| |
3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* | ||
Puron |
|
| |||||||||
42000 |
| 5/16 | 175 |
| 200 | 250* | 250* | 250* | 250* | 250* | 250* |
AC with | 3/8 |
|
|
|
|
|
|
|
|
|
|
3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* | ||
Puron |
|
| |||||||||
48000 | 3/8 | 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
AC with |
| ||||||||||
Puron |
|
|
|
|
|
|
|
|
|
|
|
49000 |
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
|
|
|
|
|
|
|
|
|
|
|
60000 |
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
|
|
|
|
|
|
|
|
|
|
|
61000 |
|
|
|
|
|
|
|
|
|
|
|
AC with | 3/8 | 3/8 | 250* |
| 250* | 250* | 250* | 250* | 250* | 250* | 250* |
Puron |
|
|
|
|
|
|
|
|
|
|
|
* Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
---
116B