Bryant 116B Electrical Data, Charging Subcooling TXV-TYPE Expansion Device, Max Min Lra Rla Fla

Page 8

116B

ELECTRICAL DATA

 

 

OPER VOLTS*

COMPR

FAN

 

MIN WIRE

MIN WIRE

MAX

MAX

MAX FUSE**

UNIT SIZE

V/PH

MCA

LENGTH

LENGTH

 

 

 

 

 

SIZE{

SIZE{

or CKT BRK

 

 

 

 

 

ft. (m)}

ft. (m)}

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

AMPS

 

 

 

60° C

75° C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018---B

 

 

 

48.0

9.0

0.50

11.8

14

14

67 (20.4)

64 (19.5)

20

024---A

 

 

 

58.3

13.5

0.75

17.7

14

14

46 (14.0)

43 (13..1)

25

030---A

 

 

 

64.0

12.8

0.75

16.8

14

14

44 (13.4)

41 (12.5)

25

036---A

 

 

 

77.0

14.1

0.50

18.1

12

12

57 (17.4)

54 (16.5)

30

042---A

208/230/1---60 253

197

112.0

17.9

1.20

23.6

10

10

85 (25.9)

81 (24.7)

40

048---B

 

 

 

109.0

19.9

1.20

26.1

10

10

70 (21.3)

67 (20.4)

40

049---A

 

 

 

117.0

21.8

1.20

26.1

10

10

70 (21.3)

67 (20.4)

40

060---A

 

 

 

135.0

21.4

1.20

28.0

8

10

91 (27.7)

56 (17.1)

40

061---A

 

 

 

134.0

25.0

1.20

32.5

8

10

94 (28.7)

58 (17.7)

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 334---80. If other than uncoated (no---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Complies with 2007 requirements of ASHRAE Standards 90.1

A-WEIGHTED SOUND POWER LEVEL (dBA)

Unit Size ---

Standard

 

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

 

Voltage, Series

Rating (dBA)

125

250

500

1000

2000

4000

8000

0018---B

76

52.5

59.0

65.5

70.5

64.5

59.0

54.5

0024---A

76

57.5

64.0

69.0

71.0

69.0

64.5

60.0

0030---A

76

55.0

63.5

68.0

69.5

67.0

63.5

58.5

0036---A

76

50.5

59.5

64.5

70.5

62.0

59.5

54.5

0042---A

78

52.5

62.0

66.0

73.5

68.0

62.0

55.5

0048---B

78

57.5

61.5

66.0

70.5

65.5

59.5

53.5

0049---A

78

51.5

62.0

67.5

73.5

69.0

64.5

62.0

0060---A

78

55.0

62.5

67.5

70.5

65.0

61.0

53.5

0061---A

78

56.5

63.0

65.5

69.0

67.0

61.5

56.0

NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

A-WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD

Unit Size ---

Standard

 

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

 

Voltage, Series

Rating (dBA)

125

250

500

1000

2000

4000

8000

0018---B

74

55.5

59.0

65.0

68.5

63.5

58.0

52.0

0024---A

75

58.0

64.0

69.0

70.5

68.5

64.5

59.5

0030---A

75

55.5

63.0

68.0

69.0

67.0

63.0

58.5

0036---A

74

51.5

58.5

62.0

65.0

61.0

58.0

52.0

0042---A

76

53.0

62.0

65.5

72.0

65.0

61.0

54.0

0048---B

76

58.5

61.5

66.0

69.0

64.0

58.5

51.0

0049---A

76

53.0

61.5

67.5

72.0

68.0

61.5

59.0

0060---A

75

56.5

62.5

66.5

68.0

63.0

59.5

51.5

0061---A

75

57.0

63.0

65.5

67.0

65.5

59.0

52.5

NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---VOLTAGE, SERIES

REQUIRED SUBCOOLING _F (_C)

018---B

10 (5.6)

024---A

10 (5.6)

030---A

10 (5.6)

036---A

10 (5.6)

042---A

9 (5.0)

048---B

10 (5.6)

049---A

8 (4.4)

060---A

9 (5.0)

061---A

9 (5.0)

8

Image 8
Contents Industry Leading Features / Benefits Product DataPhysical Data Standard FeaturesModel Number Nomenclature Refrigerant Piping Length Limitations Vertical Separation ft mCharging Formula Long Line ApplicationsVapor Line Sizing and Cooling Capacity Loss Accessory Thermostats AccessoriesPart Number Program GAS Electric Heat Cool KIT Number DescriptionAccessory Usage Guideline Time-Delay Relay Sound HoodSupport Feet Thermostatic Expansion Valve TXVElectrical Data Charging Subcooling TXV-TYPE Expansion DeviceMAX MIN LRA RLA FLA AmpsDimensions English Dimensions SI Wall 609.6 Service 457.2 ClearancesTested Ahri Combination Ratings Http//cactaxcredits.info/bryant-ratings/hpratingssrch.php105 115 125 Capacity MBtuh† Total System Sens‡525 600875 10001125 10501225 14001575 16002250 17502000 Outdoor Section With CNPV*6124A**+TDR Indoor Section SST Condenser Entering AIR Temperatures F C Condenser only Ratings116BNA036****A 116BNA049****A Guide Specifications General ProductsSystem Design Summary Catalog No PDS116B---04