SYSTEM DESIGN SUMMARY

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55_F (12.8_C).

3.Maximum outdoor operating air temperature is 125_F (51.7_C).

4.For reliable operation, unit should be level in all horizontal planes.

5.For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor.

6.If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4 mm).

7.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

8.Do not apply capillary tube indoor coils to these units.

9.Factory-supplied filter drier must be installed.

116B

Copyright 2012 Bryant Heating & Cooling Systems. S 7310 W. Morris St. S Indianapolis, IN 46231

Edition Date: 09/12

Catalog No: PDS116B---04

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Replaces: PDS116B--- 03

22

Image 22
Contents Industry Leading Features / Benefits Product DataModel Number Nomenclature Standard FeaturesPhysical Data Refrigerant Piping Length Limitations Vertical Separation ft mVapor Line Sizing and Cooling Capacity Loss Long Line ApplicationsCharging Formula Part Number Program GAS Electric Heat Cool Accessory ThermostatsAccessories KIT Number DescriptionAccessory Usage Guideline Support Feet Time-Delay RelaySound Hood Thermostatic Expansion Valve TXVMAX MIN LRA RLA FLA Electrical DataCharging Subcooling TXV-TYPE Expansion Device AmpsDimensions English Dimensions SI Wall 609.6 Service 457.2 ClearancesTested Ahri Combination Ratings Http//cactaxcredits.info/bryant-ratings/hpratingssrch.php525 105 115 125Capacity MBtuh† Total System Sens‡ 6001125 8751000 10501575 12251400 16002000 17502250 Outdoor Section With CNPV*6124A**+TDR Indoor Section SST Condenser Entering AIR Temperatures F C Condenser only Ratings116BNA036****A 116BNA049****A Guide Specifications General ProductsSystem Design Summary Catalog No PDS116B---04