Bryant 698B Defrost Time Selection, FIELD-INITIATED Forced Defrost, Pressure Switch Protection

Page 13

After termination of a defrost cycle, the outdoor fan delays come on for 20 sec. This allows refrigerant system to recover outdoor coil heat and minimize the “steam cloud” effect.

I. DEFROST TIME SELECTION

The defrost interval can be field selected, dependent on local or geographical requirements. It is factory set at 90 minutes but can be changed to either 30, 60, or 120 minutes. To select defrost time, set dip switches located on the left side of the unit board (See Fig. 15). See Table 5 for Defrost Dip Switch Settings.

J. DEFROST

The dual capacity control logic for defrost function is the standard time and temperature initiated, time or temperature terminated.

Defrost only occurs at outdoor temperatures less than 50°F. The control initiates defrost when outdoor coil thermistor is 30°F (±2 °) or less, and selected defrost time (interval) has been accumulated during unit operation. Termination occurs when coil thermistor reaches 80°F (±5 °) or defrost period reaches a maximum of 10 minutes. Defrost will occur at the compressor capacity that is being called for. During defrost, unit operates in high or low capacity, energizes reversing valve O and auxiliary heat W2, and de- energizes outdoor fan. Upon termination, there is a 20-sec delay in outdoor fan being energized.

K. FIELD-INITIATED FORCED DEFROST

By placing a jumper across forced defrost terminals (See Fig. 15) for a minimum of 5 sec and then removing it, a defrost cycle can be initiated. The cycle occurs only if outdoor ambient is less than 50°F, regardless of outdoor coil temperature. The cycle terminates when coil thermistor reaches 80°F (±5 °) or defrost period reaches a maximum of 10 minutes.

L. COMPRESSOR VOLTAGE FAILURE (6 FLASHES)

The control senses the voltage of the compressor run winding. If compressor voltage (Vc) is less than 90v when control board is calling for compressor operation, control shuts compressor off for 15 minutes with outdoor fan running. After 15 minutes (provided there is a call for Y1 or Y2), control attempts to start compressor. During this time, a code of 6 flashes appears at control board. If Vc trip occurs 3 consecutive times during a Y1 request, then low capacity operation is locked out and control responds to Y2 requests until a reset occurs. If 3 consecutive trips occur in a combination of Yl and Y2 or all Y2 requests, then both low and high capacity operation will be locked out. The compressor voltage failure (6 flashes) can be caused by:

compressor internal overload trip (refer to Table 7 for correct winding)

no 208/230 volt power supply to outdoor unit

failed compressor contactor(s)

failure of start relay to pick-up properly.

improper wiring.

M. PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high- and low-pressure switches. If the control senses the opening of the high or low pressure switch, it will respond as follows:

1.De-energize the compressor hi or low speed contactor,

2.Keep the outdoor fan operating for 15 minutes,

3.Display the appropriate error code on the status light (see Table 4).

4.After a 15 minute delay, if Yl or Y2 inputs are on and the LPS or HPS is reset, energize appropriate compressor contactor, either low or high.

5.If LPS or HPS has not closed after 15 minute delay, outdoor fan is turned off. If the open switch closes anytime after the 15-minute delay, then resume operation on call for Y1 and/or Y2.

N.MAJOR COMPONENTS

TWO-SPEED CONTROL

The two-speed control board controls the following functions:

Low- and high-compressor contactor operation

Outdoor fan motor operation

Crankcase heater operation

Compressor protection

Pressure switch monitoring

Time delays

Time/temperature defrost

Defrost interval selection

Electric heat operation during defrost mode

FIELD CONNECTIONS

The two-speed dual capacity control received 24v low-voltage control system inputs through the screw connections on the left side of the control board.

TWO-SPEED DUAL CAPACITY COMPRESSOR

The two-speed dual capacity compressor contains motor windings that provide 3500 RPM operation. Refer to Table 7 for correct winding resistance.

COMPRESSOR INTERNAL RELIEF

The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when differen- tial between suction and discharge pressures exceeds 525 psi. The compressor is also protected by an internal overload attached to motor windings.

COMPRESSOR CONTROL CONTACTORS

Low and High capacity contactor coils are 24 volts. The electronic control board controls the operation of the low speed (C-L) and the high speed (C-H) contactors.

O. TEMPERATURE THERMISTORS

Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor ambient and coil temperature. Refer to Fig. 16 for resistance values versus temperature.

If the outdoor ambient thermistor or coil thermistor should fail, a fault code appears at electronic control. The crankcase heater is turned on during all off cycles.

IMPORTANT: OUTDOOR AIR THERMISTOR PLACEMENT Mount outdoor air thermistor underneath unit base pan lip on control box side of unit as shown in Fig. 17. Attach to base pan with adhesive tape or other field expedient means.

IMPORTANT: If outdoor air thermistor is nor properly placed underneath base pan, unit may have nuisance thermistor out of range faults.

TABLE 6—FACTORY DEFAULTS

FAILED COMPONENT

FUNCTION

DEFAULT

Ambient Thermistor

Defrost Initiation

Defrost is initiated based on coil

temperature and time.

 

 

Outdoor Coil Thermistor

Defrost Initiation and Termination

Defrost occurs at each time interval, but

terminate after 5 minutes

 

 

 

 

 

—13—

Image 13
Contents Installation Recommendations Safety ConsiderationsII. Install on a SOLID, Level Mounting PAD Installation Check Equipment and JOB Site Unpack UnitInspect Equipment III. Clearance RequirementsFAN Coils VI. Check Indoor Expansion Device Furnace CoilsVII. Make Piping Connections Install Adapter TubeOutdoor Unit Connected to FACTORY- Approved Indoor Unit Required LIQUID-LINE Temperature F Accessory UsageRefrigerant Tubing and Filter Drier Sweat ConnectionFinal Tubing Check MinutesVIII. Make Electrical Connections Connect Ground and Power Wires Route Ground and Power WiresConnect Control Wiring Final Wiring CheckTypical 24V Circuit Connections Volt Factory Wiring XII. Check Charge Unit Charge Wiring Diagram NotesHeating Check Charge Procedure Cooling only ProcedureXIII. System Functions and Sequence of OP- Eration Cooling OperationFactory Defaults ONE Minute Speed Change Time DelayDefrost DIP Switch Settings Heating OperationTemperature Thermistors Pressure Switch ProtectionDefrost Time Selection DefrostXIV. Final Checks Care and MaintenanceTWO-SPEED Compressor Winding Resistance AT 70F ± → -Wiring Diagram-024, 036 Wiring Diagram-060
Related manuals
Manual 44 pages 15.83 Kb

698B specifications

The Bryant 698B is an advanced residential air conditioning unit known for its efficiency and reliability in delivering optimal indoor climate control. Designed for comfort and energy savings, the Bryant 698B is a notable choice for homeowners seeking high-performance cooling solutions.

One of its standout features is its impressive Seasonal Energy Efficiency Ratio (SEER) rating, which ranges from 16 to 18, depending on the specific model. This high efficiency helps to reduce energy consumption while providing consistent cooling performance, allowing homeowners to enjoy a comfortable environment without incurring high electricity bills. The unit's efficient operation is recognized by various energy efficiency certifications, helping promote a more sustainable lifestyle.

The Bryant 698B is equipped with a variable-speed compressor, which adjusts its operating speed based on the cooling needs of the home. This technology allows the system to run at lower speeds for longer periods, ensuring a more consistent temperature throughout the space and reducing wear and tear on the system. This also minimizes noise levels, making the Bryant 698B one of the quieter units available today.

In terms of build quality, the Bryant 698B features a durable steel cabinet designed to withstand harsh weather conditions. The unit is treated with a baked-on powder finish that provides corrosion resistance, ensuring its longevity even in challenging environments. Additionally, the coil is designed for easy maintenance, allowing for optimal airflow and ensuring the system runs efficiently.

Smart technology integration is another highlight of the Bryant 698B. The unit can be connected to a smart thermostat, offering homeowners remote access to control their HVAC system from their smartphones. This capability allows for more precise temperature adjustments and scheduling, contributing to enhanced energy savings and increased comfort.

The Bryant 698B also offers various customizable options, including different cooling capacities and compatibility with additional heating systems like heat pumps or gas furnaces. This versatility makes it suitable for a wide range of residential applications.

In summary, the Bryant 698B air conditioning unit stands out due to its energy efficiency, variable-speed compressor, durable construction, smart technology features, and customization options, making it an ideal choice for homeowners looking for a robust and efficient cooling solution.