Bryant 698B VII. Make Piping Connections, Outdoor Unit Connected to FACTORY- Approved Indoor Unit

Page 4

B

INLET

D A

COIL

E

BULB

INSULATION

TAPE

C

A01418

Fig. 6—TXV Kit Contents

of the Long-Line Guideline section in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant. If required by Long-Line Application Guideline, install LSV kit Part No. KHALS0401LLS specifically designed for Puron® Heat Pumps. LSV should be installed between filter drier and indoor coil as close as possible to filter drier. Follow the Installation Instructions included with accessory kit.

IMPORTANT: Flow arrow must point toward outdoor unit.

VII. MAKE PIPING CONNECTIONS

WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.

CAUTION: Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.

CAUTION: To prevent compressor damage DO NOT bury more than 36 in. of refrigerant tubing. If ANY tubing is buried, provide 6-in. vertical rise at service valve.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50 ft For tubing requirements beyond 50 ft, substantial capacity and performance losses can occur. Follow the recommendations in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant to minimize losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and

—4—

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT

LIQUID

VAPOR

VAPOR (LONG-LINE)

SIZE

Connection

Tube

Connection

Tube

Connection

Tube

 

Diameter

Diameter

Diameter

Diameter

Diameter

Diameter

024

3/8

3/8

5/8

5/8

5/8

3/4

036

3/8

3/8

3/4

3/4

3/4

7/8

048

3/8

3/8

7/8

7/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

7/8

1-1/8

Notes:

1.Tube diameters are for lengths up to 50 equivalent ft and/or 20 ft vertical differential.

2.Do not increase or decrease tubing sizes.

3.If required by local codes, Pressure Guard™ kit is available. See Product Data Sheet for part numbers.

moisture in the system. Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Al- ways keep ends of tubing sealed during installation.

A. OUTDOOR UNIT CONNECTED TO FACTORY- APPROVED INDOOR UNIT

These outdoor units are carefully evaluated and listed with specific indoor coils for proper system performance.

IMPORTANT: Do not apply indoor coils which are not factory approved to these units.

IMPORTANT: For 036 size units matched with the FV/FK005 or FV/FK006 and the 698BNX048 matched with the FV/FK006, a piston change is required. Refer to the KHAPX0201BPA Instal- lation Instructions for details.

B.INSTALL ADAPTER TUBE

1.Remove plastic retainer holding outdoor piston in liquid service valve.

2.Check to be sure outdoor piston is properly installed in liquid service valve.

3.Locate plastic bag taped to unit containing adapter tube.

4.Remove Teflon washer from bag and install on open end of liquid service valve. (See Fig. 8.)

5.Remove adapter tube from bag and connect threaded nut to liquid service valve. Tighten nut finger tight and then with wrench an additional 1/2 turn (15 ft-lb). DO NOT OVER TIGHTEN!

Image 4
Contents Safety Considerations Installation RecommendationsInstallation Check Equipment and JOB Site Unpack Unit II. Install on a SOLID, Level Mounting PADInspect Equipment III. Clearance RequirementsVI. Check Indoor Expansion Device Furnace Coils FAN CoilsVII. Make Piping Connections Install Adapter TubeOutdoor Unit Connected to FACTORY- Approved Indoor Unit Accessory Usage Required LIQUID-LINE Temperature FRefrigerant Tubing and Filter Drier Sweat ConnectionFinal Tubing Check MinutesVIII. Make Electrical Connections Route Ground and Power Wires Connect Ground and Power WiresConnect Control Wiring Final Wiring CheckTypical 24V Circuit Connections Volt Factory Wiring Wiring Diagram Notes XII. Check Charge Unit ChargeCooling only Procedure Heating Check Charge ProcedureXIII. System Functions and Sequence of OP- Eration Cooling OperationONE Minute Speed Change Time Delay Factory DefaultsDefrost DIP Switch Settings Heating OperationPressure Switch Protection Temperature ThermistorsDefrost Time Selection DefrostXIV. Final Checks Care and MaintenanceTWO-SPEED Compressor Winding Resistance AT 70F ± → -Wiring Diagram-024, 036 Wiring Diagram-060
Related manuals
Manual 44 pages 15.83 Kb

698B specifications

The Bryant 698B is an advanced residential air conditioning unit known for its efficiency and reliability in delivering optimal indoor climate control. Designed for comfort and energy savings, the Bryant 698B is a notable choice for homeowners seeking high-performance cooling solutions.

One of its standout features is its impressive Seasonal Energy Efficiency Ratio (SEER) rating, which ranges from 16 to 18, depending on the specific model. This high efficiency helps to reduce energy consumption while providing consistent cooling performance, allowing homeowners to enjoy a comfortable environment without incurring high electricity bills. The unit's efficient operation is recognized by various energy efficiency certifications, helping promote a more sustainable lifestyle.

The Bryant 698B is equipped with a variable-speed compressor, which adjusts its operating speed based on the cooling needs of the home. This technology allows the system to run at lower speeds for longer periods, ensuring a more consistent temperature throughout the space and reducing wear and tear on the system. This also minimizes noise levels, making the Bryant 698B one of the quieter units available today.

In terms of build quality, the Bryant 698B features a durable steel cabinet designed to withstand harsh weather conditions. The unit is treated with a baked-on powder finish that provides corrosion resistance, ensuring its longevity even in challenging environments. Additionally, the coil is designed for easy maintenance, allowing for optimal airflow and ensuring the system runs efficiently.

Smart technology integration is another highlight of the Bryant 698B. The unit can be connected to a smart thermostat, offering homeowners remote access to control their HVAC system from their smartphones. This capability allows for more precise temperature adjustments and scheduling, contributing to enhanced energy savings and increased comfort.

The Bryant 698B also offers various customizable options, including different cooling capacities and compatibility with additional heating systems like heat pumps or gas furnaces. This versatility makes it suitable for a wide range of residential applications.

In summary, the Bryant 698B air conditioning unit stands out due to its energy efficiency, variable-speed compressor, durable construction, smart technology features, and customization options, making it an ideal choice for homeowners looking for a robust and efficient cooling solution.