Alcove Installations

Vermont Castings Resolute Acclaim

Alcove Installations

Because of their restricted air flow and heat retention characteristics, specific construction requirements and special clearances apply to installations into alcoves. No stove or chimney connector heat shields are used in alcove installa- tions. Bottom heat shield requirements remain the same as for other installations.

ALCOVE INSTALLATION OF THE RESOLUTE ACCLAIM IS NOT PERMITTED IN CANADA.

Construction Requirements

Showing non-combustible ceiling framing and maxi- mum and minimum permitted dimensions

Joist Shield (supplied by chimney manufac- turer)

Metal

Stud

ST504

Fig. 22 Cutaway perspective of alcove installation.

1” air gap top and bottom, on both sides and back wall

Combustible facing may overlap metal studs by only 1”

7/16” Durock© (or equivalent)

R E S O L U T E

Acclaim

ST609

Existings

 

Combustible Framing

24"

 

11"

Metal studs

Min.

support 7/16”

 

Durock© (or

36"

equivalent)

Min.

ceiling

 

 

14¹⁄₄"

 

48" Min.

 

ST505

Fig. 23 Reflected ceiling plan.

 

Fig. 25 Alcove side section.

 

 

Ceiling support

 

 

package

 

 

extends 2”

 

 

below Durock©

 

 

(or equivalent)

 

 

ceiling

 

 

1” air gap,

 

62" Min.

top, bottom,

65"

on both sides

to Alcove

 

and back

 

Ceiling

wall

 

 

NOTE: From

 

 

62” to 65”

 

 

36" Use recommended Max. floor protection

48" Min.

7/16” Durock© (or equivalent) spaced 1” off wood studs on noncombustible spacers

ST502

must be

covered by a

noncombus-

tible material.

ST610

Fig. 26 Front section: 65” minimum clearance to combus- tibles on front face. Combustible facing may overlap metal

Fig. 24 Floor plan. Sheetrock on front face butts to Durock© (or equivalent) alcove lining.

studs by only 1”. It should not extend below the height of the noncombustible ceiling.