Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall
U.S.: In the United States, the National Fire Protection Association (NFPA) has established guidelines for passing chimney connectors through combustible walls. Many building code inspectors follow these guidelines when approving installations.
The following illustration shows one
Three other methods are also approved by the NFPA. These are:
•Using a section of
•Placing a chimney connector pipe inside a ventilated thimble, which is then separated from combustibles by 6" (150 mm) of fiberglass insulating material.
•Placing a chimney connector pipe inside a section of 9" (230 mm) diameter,
Wall Stud |
Chimney |
Connector |
T |
Floor |
Protection |
ST493a |
Fig. 9 An approved wall |
Canada: In Canada, the Canadian Standards Association has established different guidelines. The illustration below shows one method, in which all combustible material in the wall is cut away to provide the required 18" (460 mm) clearance for the connector. The resulting space must remain empty. A
In Canada, this type of installation must conform to
NOTE: Do not vent your Resolute Acclaim into a
any other use.
DO NOT CONNECT THE RESOLUTE ACCLAIM TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
18” (460mm) clearance | |
all around the pipe |
|
T | T |
| |
| Flush |
| Mounted |
| ST494a |
Fig. 10 An approved wall |
8 | 2000893 |