Installation
SAFETY NOTICE: IF YOUR RESOLUTE ACCLAIM IS NOT PROPERLY INSTALLED, OPERATED AND MAINTAINED, A HOUSE FIRE MAY RESULT. FOR SAFETY, FOLLOW ALL INSTALLATION, OPERATION AND MAINTENANCE DIRECTIONS. CONTACT LOCAL BUILDING OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
Before you begin an installation, review your plans to see that:
•Your stove and chimney connector will be far enough from combustible material to meet all clearance requirements.
•The floor protector is large enough and is constructed properly to meet all requirements.
•You have all necessary permits from local authorities.
Your local building official is the final authority for approving your installation as safe and determining that it meets local and state codes.
The metal label permanently attached to the back of every Vermont Castings stove indicates that it has been tested to current UL and ULC standards, and gives the name of the testing laboratory. Clearance and installation information is also printed on the label. Local authorities generally will accept the label as evidence that, when the stove is installed according to the information on the label and in this manual, the installation meets codes and can be approved.
Codes vary in different areas, however. Before starting the installation, review your plans with the local build- ing authority. Your local dealer can provide any additional information needed.
For any unresolved questions about installation, refer to the National Fire Protection Association’s publication ANSI/NFPA
IMPORTANT: FAILURE TO FOLLOW THESE INSTALLATION INSTRUCTIONS MAY RESULT IN A DANGEROUS SITUATION, INCLUDING A CHIMNEY OR HOUSE FIRE. FOLLOW ALL INSTRUCTIONS EXACTLY AND DO NOT ALLOW MAKESHIFT COMPROMISES TO ENDANGER PROPERTY AND PERSONAL SAFETY.
What Kind of Chimney Tto Use
Your Resolute Acclaim may be connected either to a sound masonry chimney that meets local codes, to a relined masonry chimney that meets local codes, or to an approved prefabricated metal chimney. Whatever kind you use, the chimney and chimney connector must be in good condition and kept clean.
If you use an existing masonry chimney, it must be inspected to ensure safe condition before the stove is installed. Your local professional chimney sweep, building inspector, or fire department official will be able either to make the inspection or to direct you to someone who can.
The chimney should extend at least 3' (900 mm) above the highest point where it passes through a roof, and at least 2' (600 mm) higher than any portion of a building within 10' (3m). (Fig. 2)
| 0 TO 10' |
|
| 2' Min. |
|
| 3' | 0 TO 10' |
| Min. |
|
|
| 2' Min.3' |
|
| Min. |
Reference Point |
| |
|
| AC617 |
Fig. 2 | The |
For proper draft and good performance, any chimney used with a Resolute Acclaim should extend at least 16' (5 m) above the flue collar of the stove.
Masonry Chimneys
An inspection of the chimney must confirm that it has a lining. Do not use an unlined chimney. The chimney also should be examined for cracks, loose mortar, other signs of deterioration, and blockage. Repair any defects before the chimney is used with your stove.
A prefabricated
insulated chimney
A
ST241
Fig. 3 Standard chimney types.
4 | 2000893 |