Vermont Castings Resolute Acclaim

5.Secure the extension plate and flue collar with the fasteners removed in the first step. Run the bolts in only finger-tight. Adjust the fit of the extension plate and/or flue collar if necessary. Tighten all four fasteners, but do not overtighten them. Test the action of the griddle; make any needed adjustments by loosening the hardware, repositioning the flue collar and extension plate, retesting the griddle action, and retightening the hardware.

Side trim must have a minimum clearance of 8" (200 mm), measured from the stove's top side edge. In this case, ventilated shielding will not provide protection to allow clearance reduction.

In addition, a fireplace installation must observe the floor protection guidelines discussed previously.

The charts and sample installations on the following pages list the clearances required for various installa- tion configurations of the Resolute Acclaim.

Fireplace Installations

A fireplace installation requires special clearance between the side of the stove and the right and left walls, the side of the stove and the decorative side trim on the fireplace face, and the top of the stove and the mantel.

Ventilated shields (noncombustible) shields installed on noncombustible spacers 1" (25 mm) away from the combustible surface may be used to reduce clear- ances. (Fig. 14) A mantel shield for the Resolute Acclaim must be at least 48" (1220 mm) long, centered over the stove. Side trim shields must extend the full length of the trim. (Fig. 15)

Mantel

Spacer

1" (25mm)

Shield

1/4" (6mm)

ST501

 

A

B

 

 

C

 

C

Fireplace Mantel and Trim Clearances

Measured from the stove top and sides

 

Protected

Unprotected

A. Mantel

30” (760mm)

36” (915mm)

B. Top Trim

28” (710mm)

28” (710mm)

C. Side Trim

8” (200mm)

8” (200mm) ST253b

Fig. 15 Maintain clearances to combustible components of the mantelpiece.

Fig. 14 A custom-formed mantel shield.

An unprotected mantel ("A" ,Fig. 15) must have a minimum clearance of 36" (915 mm), measured from the stove's top plate. With a ventilated shield the clearance may safely be reduced to 30" (760 mm). Maximum depth of the mantel is 9" (230 mm).

Unprotected top trim (B) protruding 1¹⁄₂" (40 mm) or less from the face of the fireplace must be a minimum of 28" (710 mm) from the stove's top surface. This clearance may not be reduced by shielding. If top trim protrudes more than 1¹⁄₂" (40 mm) the mantel clearances of 36" (915 mm) unshielded and 30" (760 mm) shielded must be used.

2000893

11

Page 11
Image 11
Majestic Appliances 2490 installation instructions Fireplace Installations, 6mm