Bard WH421, WH602 Phase Monitor, Service Hints, Sequence of Operation, Pressure Service Ports

Page 17

PHASE MONITOR

All units with three phase compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct, the green LED will light. If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.

2.Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch. Turn thermostat off, then on to reset the high pressure switch.

3.The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.

4.Check all power fuses or circuit breakers to be sure they are the correct rating.

5.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.

HEATING A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing "Auto" changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On "Auto" option a circuit is completed from R-W1 and R-Y on each heating "on" cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle

now in operation. The second option has no "Auto" changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in "Heat" position, the "B" terminal being constantly energized from R. A Thermostat demand for heat completes r-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure curve to the unit by model number.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the solid state heat pump control.

When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32° F or below. This coil temperature is sensed by the coil sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30° F or below, the coil sends a signal to the control logic of the heat pump control and the defrost timer will start.

After 60 (90 or 30) minutes at 30° F or below, the heat pump control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil sensor will send a signal to the heat pump control which will return the system to heating operations automatically.

If some abnormal or temporary conditions such as a high wind caused the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operating automatically after 10 minutes.

There is a cycle SPEEDUP jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or another 1/4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost. Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.

Manual 2100-399 Page 15

Image 17
Contents Models Installation Instructions Wall Mounted Package Heat PumpsContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsElectric Heat Table Wall Mount General InformationHeat Pump Wall Mount Model Nomenclature Unit Dimensions Single Circuit Dual Circuit Electrical SpecificationsGeneral Shipping DamageDuct Work FiltersCondensate Drain Blower Damper AssemblyFresh AIR Intake Typical Installations Installation InstructionsWall Mounting Information Mounting the UnitElectric Heat Clearance Mounting InstructionsWALL-MOUNTING Instructions Common WALL-MOUNTING Installations Unit 24V Terminal Board Wiring Main PowerWiring LOW Voltage Wiring Thermostat Wire Size Thermostat WiringCompressor Cutoff and Outdoor Thermostat Wiring Heat AnticipationThermostat Subbase Predominant Features Thermostat Indicator LampsEmergency Heat Position Compressor Malfunction LightHigh Pressure Switch Important Installer NoteThree Phase Scroll Compressor Start UP Information Start UPService Hints Phase MonitorPressure Service Ports Sequence of OperationDefrost Control Board Troubleshooting TroubleshootingSolid State Heat Pump Control Troubleshooting Procedure Temperature F VS. Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitRefrigerant Charge FAN Blade Setting DimensionsRemoval of FAN Shroud Maximum ESP of Operation Electric Heat only Cooling Pressure ALL Temperatures FModel WH421 WH483 WH602 Speed KW High Speed Low Speed Return Air ModelPressure Heating Pressures ALL Temperatures FOptional Accessories
Related manuals
Manual 29 pages 26.38 Kb Manual 8 pages 45.17 Kb

WH421, WH483, WH602 specifications

Bard WH602, WH421, and WH482 are distinguished models in Bard's line of high-performance wall-mounted heaters. Each unit is designed to offer reliable heating solutions for various commercial and industrial applications. These models are renowned for their energy efficiency, robust construction, and ease of use, making them ideal for a variety of environments, including warehouses, manufacturing facilities, and other large spaces.

The WH602 model boasts impressive heating capabilities, featuring a powerful fan-forced heater equipped with a 60000 BTU rating. This allows it to effectively heat large areas quickly and efficiently. One of its main features is the high-efficiency, stainless steel heat exchanger that promotes better heat transfer, enhancing the overall performance and longevity of the heater. The WH602 is designed with energy-saving technology, allowing it to operate with minimal electricity consumption while maximizing output.

The WH421 model offers a more compact solution without sacrificing power. With a heating capacity of 42000 BTU, it is suitable for medium-sized spaces. Like the WH602, the WH421 utilizes a stainless steel heat exchanger, ensuring durability and efficient heating. This model is equipped with a quiet, high-performance fan that distributes heat uniformly throughout the space, maintaining comfortable conditions without the distraction of excessive noise. Its compact design also allows for easy installation in tighter spaces.

The WH482 is a versatile model that falls between the two in terms of performance and application. Rated at 48000 BTU, it combines the benefits of both the WH602 and WH421, making it suitable for various heating demands. The WH482 features advanced control options, allowing users to set specific heating schedules and temperatures for improved comfort and energy efficiency. Additionally, it has built-in safety features like over-temperature protection and a thermal cutoff switch, ensuring safe operation in commercial environments.

All three models share key characteristics, including a robust construction built to withstand harsh conditions, user-friendly controls, and compliance with industry safety standards. Their wall-mounted design saves valuable floor space while providing powerful heating performance. Overall, Bard WH602, WH421, and WH482 represent a commitment to quality, performance, and customer satisfaction, making them top choices for businesses seeking efficient heating solutions.