FAN BLADE SETTING DIMENSIONS

Shown in the drawing in Figure 11 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 11

FAN BLADE SETTING

TABLE 6

FAN BLADE DIMENSIONS

Model

Dimension A

 

 

WH421

 

WH483

1.75

WH602

 

 

 

MIS-1190

REMOVAL OF FAN SHROUD

1.Disconnect all power to unit.

2.Remove the screws holding both grilles – one on each side of unit – and remove grilles.

3.Remove screws holding fan shroud to condenser and bottom – (9) screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in the Table 7.

TABLE 7

SUCTION LINE TEMPERATURES

 

Rated

95°F O.D.

82°F O.D.

Model

Airflow

Temperature

Temperature

WH421

1400

52 -- 54

62 -- 64

WH483

1550

53 -- 55

62 -- 64

WH602

1700

52 -- 54

61 -- 63

 

 

 

 

The suction line temperatures in Table 7 are based upon 80ºF dry bulb/67 degrees F wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 8

RECOMMENDED OPERATING RANGES

 

Rated

Rated

Recommended

Model

CFM *

ESP *

Air Flow Range

WH421

1400

.30

1600 -- 1150

 

 

 

 

WH483

1550

.20

1750 -- 1285

 

 

 

 

WH602

1700

.30

1950 -- 1375

 

 

 

 

*Rated CFM and ESP on high speed tap.

TABLE 9

INDOOR BLOWER PERFORMANCE

CFM @ 230V

 

 

WH421, WH483

 

 

WH602

 

 

 

 

 

 

 

 

 

 

E.S.P.

Low 230V

High 230V

Low 230V

High 230V

 

 

 

 

 

 

 

 

In H2O

Dry Coil

Wet Coil

Dry Coil

Wet Coil

Dry Coil

Wet Coil

Dry Coil

Wet Coil

.0

1650

1600

1885

1800

1600

1450

2200

2000

.1

1550

1500

1770

1665

1525

1375

2100

1900

.2

1450

1400

1635

1540

 

 

2000

1800

.3

1350

1300

1500

1400

 

 

1875

1700

.4

1300

1175

1370

1285

 

 

1775

1600

.5

-----

-----

1250

1150

 

 

1650

1475

Manual 2100-399 Page 19

Image 21
Contents Models Installation Instructions Wall Mounted Package Heat PumpsContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsWall Mount General Information Heat Pump Wall Mount Model NomenclatureElectric Heat Table Unit Dimensions Single Circuit Dual Circuit Electrical SpecificationsGeneral Shipping DamageDuct Work FiltersBlower Damper Assembly Fresh AIR IntakeCondensate Drain Typical Installations Installation InstructionsWall Mounting Information Mounting the UnitElectric Heat Clearance Mounting InstructionsWALL-MOUNTING Instructions Common WALL-MOUNTING Installations Wiring Main Power Wiring LOW Voltage WiringUnit 24V Terminal Board Thermostat Wire Size Thermostat WiringCompressor Cutoff and Outdoor Thermostat Wiring Heat AnticipationThermostat Subbase Predominant Features Thermostat Indicator LampsEmergency Heat Position Compressor Malfunction LightHigh Pressure Switch Important Installer NoteThree Phase Scroll Compressor Start UP Information Start UPService Hints Phase MonitorPressure Service Ports Sequence of OperationDefrost Control Board Troubleshooting Solid State Heat Pump Control Troubleshooting ProcedureTroubleshooting Temperature F VS. Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitFAN Blade Setting Dimensions Removal of FAN ShroudRefrigerant Charge Maximum ESP of Operation Electric Heat only Cooling Pressure ALL Temperatures FModel WH421 WH483 WH602 Speed KW High Speed Low Speed Return Air ModelHeating Pressures ALL Temperatures F Optional AccessoriesPressure
Related manuals
Manual 29 pages 26.38 Kb Manual 8 pages 45.17 Kb

WH421, WH483, WH602 specifications

Bard WH602, WH421, and WH482 are distinguished models in Bard's line of high-performance wall-mounted heaters. Each unit is designed to offer reliable heating solutions for various commercial and industrial applications. These models are renowned for their energy efficiency, robust construction, and ease of use, making them ideal for a variety of environments, including warehouses, manufacturing facilities, and other large spaces.

The WH602 model boasts impressive heating capabilities, featuring a powerful fan-forced heater equipped with a 60000 BTU rating. This allows it to effectively heat large areas quickly and efficiently. One of its main features is the high-efficiency, stainless steel heat exchanger that promotes better heat transfer, enhancing the overall performance and longevity of the heater. The WH602 is designed with energy-saving technology, allowing it to operate with minimal electricity consumption while maximizing output.

The WH421 model offers a more compact solution without sacrificing power. With a heating capacity of 42000 BTU, it is suitable for medium-sized spaces. Like the WH602, the WH421 utilizes a stainless steel heat exchanger, ensuring durability and efficient heating. This model is equipped with a quiet, high-performance fan that distributes heat uniformly throughout the space, maintaining comfortable conditions without the distraction of excessive noise. Its compact design also allows for easy installation in tighter spaces.

The WH482 is a versatile model that falls between the two in terms of performance and application. Rated at 48000 BTU, it combines the benefits of both the WH602 and WH421, making it suitable for various heating demands. The WH482 features advanced control options, allowing users to set specific heating schedules and temperatures for improved comfort and energy efficiency. Additionally, it has built-in safety features like over-temperature protection and a thermal cutoff switch, ensuring safe operation in commercial environments.

All three models share key characteristics, including a robust construction built to withstand harsh conditions, user-friendly controls, and compliance with industry safety standards. Their wall-mounted design saves valuable floor space while providing powerful heating performance. Overall, Bard WH602, WH421, and WH482 represent a commitment to quality, performance, and customer satisfaction, making them top choices for businesses seeking efficient heating solutions.