Bard WH361, WH-301 installation instructions Checking Temperature Sensor Outside Unit Circuit

Page 23

CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT

1.Disconnect temperature sensor from board and from outdoor coil.

2.Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.

3.Check resistance reading to chart of resistance use sensor ambient temperature. (Tolerance of part is

± 10%.)

4.If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.

5.If sensor is out of tolerance, shorted, open or reads very low ohms then it should be replaced.

TEMPERATURE "F" VS. RESISTANCE "R" OF TEMPERATURE SENSOR

F

R

F

R

F

R

F

R

 

 

 

 

 

 

 

 

-25.0

196871

13.0

56985

53.0

19374

89.0

7507

-24.0

190099

14.0

55284

52.0

18867

90.0

7334

-23.0

183585

15.0

53640

53.0

18375

91.0

7165

-22.0

177318

16.0

52051

54.0

17989

92.0

7000

-21.0

171289

17.0

50514

55.0

17434

93.0

6840

-20.0

165487

18.0

49028

56.0

16984

94.0

6683

-19.0

159904

19.0

47590

57.0

16547

95.0

6531

-18.0

154529

20.0

46200

58.0

16122

96.0

6383

-17.0

149355

21.0

44855

59.0

15710

97.0

6239

-16.0

144374

22.0

43554

60.0

15310

98.0

6098

-15.0

139576

23.0

42295

61.0

14921

99.0

5961

-14.0

134956

24.0

41077

62.0

14544

100.0

5827

-13.0

130506

25.0

39898

63.0

14177

101.0

5697

-12.0

126219

26.0

38757

64.0

13820

102.0

5570

-11.0

122089

27.0

37652

65.0

13474

103.0

5446

-10.0

118108

28.0

36583

66.0

13137

104.0

5326

-9.0

114272

29.0

35548

67.0

12810

105.0

5208

-8.0

110575

30.0

34545

68.0

12492

106.0

5094

-7.0

107010

31.0

33574

69.0

12183

107.0

4982

-6.0

103574

32.0

32634

70.0

11883

108.0

4873

-5.0

100260

33.0

31723

71.0

11591

109.0

4767

-4.0

97064

34.0

30840

72.0

11307

110.0

4663

-3.0

93981

35.0

29986

73.0

11031

111.0

4562

-2.0

91008

36.0

29157

74.0

10762

112.0

4464

-1.0

88139

37.0

28355

75.0

10501

113.0

4367

0.0

85371

38.0

27577

76.0

10247

114.0

4274

1.0

82699

39.0

26823

77.0

10000

115.0

4182

2.0

80121

40.0

26092

78.0

9760

116.0

4093

3.0

77632

41.0

25383

79.0

9526

117.0

4006

4.0

75230

42.0

24696

80.0

9299

118.0

3921

5.0

72910

43.0

24030

81.0

9077

119.0

3838

6.0

70670

44.0

23384

82.0

8862

120.0

3757

7.0

68507

45.0

22758

83.0

8653

121.0

3678

8.0

66418

46.0

22150

84.0

8449

122.0

3601

9.0

64399

47.0

21561

85.0

8250

123.0

3526

10.0

62449

48.0

20989

86.0

8057

124.0

3452

11.0

60565

49.0

20435

87.0

7869

 

 

12.0

58745

50.0

19896

88.0

7686

 

 

 

 

 

 

 

 

 

 

Manual

2100-193O

Page

23 of 26

Image 23
Contents Models WH301, WH361 Wall Mounted Installation Packaged Heat Pump InstructionsContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Wall Mount General InformationHeat Pump Wall Mount Model Nomenclature Shipping DamageBTU Electric Heat TableFront View Side View Back View CKT a CKT B Electrical SpecificationsCondensate Drain Fresh AIR Damper AssemblyFilters Fresh AIR IntakeTOP Outlet only Installation InstructionsWall Mounting Information Mounting the UnitMounting Instructions Electric Heat Clearance Manual WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Operating Voltage Range Wiring Main PowerWiring LOW Voltage Wiring LOW Voltage ConnectionsLOW Voltage Wiring Thermostat Wire Size Optional Outdoor Thermostat Applications Compressor Cutoff Thermostat WiringElectric Heat HOLD-OFF See Figures 13 Electric Heat HOLD-OFF Wiring 4 & 10KW 1 PH 6 & 9KW 3 PHWall Thermostat Thermostat Predominate FeaturesCrankcase Heaters Important Installer NoteService Hints Start UPDefrost Control Board Pressure Service PortsDefrost Cycle Troubleshooting TroubleshootingSolid State Heat Pump Control Troubleshooting Procedure Temperature F VS. Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitRefrigerant Charge FAN Blade Setting DimensionsRemoval of FAN Shroud Heating Pressure PSI Outdoor Temperature F Cooling Pressure PSI Outdoor Temperature FWH301-A WH301-B WH301-C WH361-A WH361-B WH361-C Optional Accessories