Bard WH-301, WH361 Filters, Fresh AIR Intake, Condensate Drain, Fresh AIR Damper Assembly

Page 8

Refer to Table 12 for maximum static pressure available for duct design.

Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.

A 1/4 inch clearance to combustible material for the first three (3) feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3, 4, 7 & 8 for further details.

Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.

CAUTION

Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.

Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2 through RG-5 or RFG-2 through RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.

NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.

FILTERS

A 1-inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1-inch washable filter and a 2-inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the two inch filter by loosening two screws in each bracket assembly and sliding the brackets apart to the required width and retightening the four screws.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the service panel.

If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.

All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.

The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.

FIGURE 2

FRESH AIR DAMPER ASSEMBLY

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.

Manual 2100-193O Page 8 of 26

Image 8
Contents Wall Mounted Installation Packaged Heat Pump Instructions Models WH301, WH361Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersWall Mount General Information Heat Pump Wall Mount Model NomenclatureShipping Damage GeneralElectric Heat Table BTUFront View Side View Back View Electrical Specifications CKT a CKT BFresh AIR Damper Assembly FiltersFresh AIR Intake Condensate DrainInstallation Instructions Wall Mounting InformationMounting the Unit TOP Outlet onlyMounting Instructions Electric Heat Clearance Manual WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Wiring Main Power Wiring LOW Voltage WiringLOW Voltage Connections Operating Voltage RangeLOW Voltage Wiring Thermostat Wire Size Compressor Cutoff Thermostat Wiring Optional Outdoor Thermostat ApplicationsElectric Heat HOLD-OFF Wiring 4 & 10KW 1 PH 6 & 9KW 3 PH Electric Heat HOLD-OFF See Figures 13Thermostat Predominate Features Wall ThermostatImportant Installer Note Service HintsStart UP Crankcase HeatersDefrost Control Board Pressure Service PortsDefrost Cycle Troubleshooting TroubleshootingSolid State Heat Pump Control Troubleshooting Procedure Checking Temperature Sensor Outside Unit Circuit Temperature F VS. Resistance R of Temperature SensorRefrigerant Charge FAN Blade Setting DimensionsRemoval of FAN Shroud Cooling Pressure PSI Outdoor Temperature F Heating Pressure PSI Outdoor Temperature FOptional Accessories WH301-A WH301-B WH301-C WH361-A WH361-B WH361-C