Bard WH361 Cooling Pressure PSI Outdoor Temperature F, Heating Pressure PSI Outdoor Temperature F

Page 25

TABLE 13

COOLING PRESSURE (PSI) – OUTDOOR TEMPERATURE °F

AIR TEMPERATURE ENTERING OUTDOOR COIL °F

 

Return Air

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg DB

Low Side

76

78

80

81

83

84

85

87

88

 

62 deg WB

High Side

235

249

263

277

291

305

319

333

347

 

 

 

 

 

 

 

 

 

 

 

 

WH301

80 deg DB

Low Side

81

83

85

87

88

90

91

93

94

67 deg WB

High Side

241

255

269

284

298

312

327

341

356

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg DB

Low Side

88

90

92

93

95

97

98

100

101

 

72 deg WB

High Side

250

264

279

294

308

323

338

353

368

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg DB

Low Side

69

71

73

75

76

78

80

82

83

 

62 deg WB

High Side

210

226

242

257

273

290

306

323

339

 

 

 

 

 

 

 

 

 

 

 

 

WH361

80 deg DB

Low Side

73

76

78

80

82

84

85

87

89

67 deg WB

High Side

216

232

248

264

281

297

314

331

348

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg DB

Low Side

79

81

84

86

88

90

92

94

95

 

72 deg WB

High Side

223

240

256

273

290

308

325

342

360

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 14

HEATING PRESSURE (PSI) – OUTDOOR TEMPERATURE °F

AIR TEMPERATURE ENTERING OUTDOOR COIL °F

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

0

5

10

15

20

25

30

35

40

45

50

55

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WH301

70o

Low Side

21

25

28

32

36

39

43

47

51

55

59

63

67

High Side

143

148

153

159

165

172

180

188

197

207

217

228

239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WH361

70o

Low Side

22

25

28

31

34

38

42

46

50

55

60

65

70

High Side

145

152

159

167

177

186

197

208

220

233

246

260

275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 psig

High side pressure ± 5 psig

Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled “Refrigerant Charge” on Page 24 in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

Manual

2100-193O

Page

25 of 26

Image 25
Contents Models WH301, WH361 Wall Mounted Installation Packaged Heat Pump InstructionsContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsHeat Pump Wall Mount Model Nomenclature Wall Mount General InformationShipping Damage GeneralBTU Electric Heat TableFront View Side View Back View CKT a CKT B Electrical SpecificationsFilters Fresh AIR Damper AssemblyFresh AIR Intake Condensate DrainWall Mounting Information Installation InstructionsMounting the Unit TOP Outlet onlyMounting Instructions Electric Heat Clearance Manual WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Wiring LOW Voltage Wiring Wiring Main PowerLOW Voltage Connections Operating Voltage RangeLOW Voltage Wiring Thermostat Wire Size Optional Outdoor Thermostat Applications Compressor Cutoff Thermostat WiringElectric Heat HOLD-OFF See Figures 13 Electric Heat HOLD-OFF Wiring 4 & 10KW 1 PH 6 & 9KW 3 PHWall Thermostat Thermostat Predominate FeaturesService Hints Important Installer NoteStart UP Crankcase HeatersDefrost Cycle Pressure Service PortsDefrost Control Board Solid State Heat Pump Control Troubleshooting Procedure TroubleshootingTroubleshooting Temperature F VS. Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitRemoval of FAN Shroud FAN Blade Setting DimensionsRefrigerant Charge Heating Pressure PSI Outdoor Temperature F Cooling Pressure PSI Outdoor Temperature FWH301-A WH301-B WH301-C WH361-A WH361-B WH361-C Optional Accessories