circulation pump runs when the collector temperature is below a programmable minimum temperature, shown by = symbol. The pump stops as soon as the temperature in the solar loop reaches a safe region programmed by the ? symbol. This feature is also disabled at the factory by entering - 4 oF.

min= Pump runs below this temperature min? Pump stops above this temperature

Start functions - The Circulation pump can be programmed to start on low insolation level. The Start function feature is useful when heat transferred to the collector sensor is

not fast enough for early start; especially when the collectors are flat mounted.

The enabled start function runs the pump at a given solar radiation or programmed temperature difference. The feature is disabled at the factory.

START

Start function screen

ENABL

Enable start function

DISAB

Disable start function

If this feature is selected, following parameters must be adjusted for proper operation:

SENS

Pyranometer port designation (radiation monitoring sensor port)

 

1

Sensor 1

 

2

Sensor 2

 

3

Sensor 3

 

--

Manual input in next step

INS

Radiation threshold in W/m2

CIRC

Pump runtime in seconds

INT

Maximum interval time in second

FLU

Number of flushes

The following example activates the circulation pump at 200 W/m2 and runs it for 15 seconds. If rT condition is met within the time period, the pump stays on.

INS 20

CIRC 15

Alarm functions - User can enable the alarm function of the USDT 2004 in the ALARM screen. Status of sensors and circulation pump can be viewed if alarm function is active.

A

ON

Alarm function enable

A

OFF

Alarm function disable

The status of the system can be monitored in the Stat Mode only if the corresponding feature is active. The following example shows a system condition with a circulation problem:

OT

OFF

Overheating feature disable

OT

OK

No overheating

1SHORT Short circuit in sensor 1 wiring

2SHORT Short circuit in sensor 2 wiring

1 OPEN

Disconnection in sensor 1 wiring

12

Image 12
Contents Usdt Installation and User’s Guide Introduction Control unit has the following functionsInstallation Following sa fety precautions are strongly recommendedPage Page Menmode is for use in advanced applications only. See P.9 Energy collected in kWh GAL Flow rate gallon/hHysteresis Bandwidth Diff ?1Selection DesignationBTU OUTSEN LLPAlarm StartRkty Enabl DisabSens INSNo Circ OK CircMalfunction, but realistic temperature values Incorrect display of temperatures