Dimplex LA 11PS manual Device Information, Type and order code Design

Page 10

11

11 Device Information

1Type and order code

2Design

2.1Degree of protection according to EN 60 529 for compact devices and heating components

2.2Installation Location

3

Performance data

 

3.1

Operating temperature limits:

 

 

Heating water flow/return flow

°C / °C

 

Air

°C

3.2Temperature spread of heating water at A7 / W35

3.3

Heat output / COP

at A-7 / W35 1

kW / ---

 

 

at A-7 / W45 1

kW / ---

 

 

at A2 / W35 1

kW / ---

 

 

at A7 / W35 1

kW / ---

 

 

at A7 / W45 1

kW / ---

 

 

at A10 / W35 1

kW / ---

3.4

Sound power level

 

dB(A)

3.5Sound pressure level at a distance of 10 m (air outlet side) dB(A)

3.6Heating water flow with an internal pressure differential of m³/h / Pa

3.7

Air flow rate

 

m³/h

3.8

Refrigerant; total filling weight

 

type / kg

4

Dimensions, connections and weight

 

4.1

Device dimensions

 

H x W x L cm

4.2

Device connections to heating system

Inch

4.3

Weight of the transportable unit(s) incl. packing

kg

5

Electrical connection

 

 

5.1

Nominal voltage; fuse protection

 

V / A

5.2

Nominal power consumption 1

A2 W35

kW

5.3

Starting current with soft starter

 

A

5.4

Nominal current A2 W35 / cos ϕ

 

A / ---

6Complies with the European safety regulations

7Additional model features

7.1Defrosting

Type of defrosting Defrosting tray included

7.2Heating water in device protected against icing 3

7.3Performance levels

7.4Controller internal/external

 

LA 11PS

 

IP 24

 

Outdoors

 

Up to 65 / above 18

 

-25 to +35

9.2

 

 

5.0

 

 

 

7.3 / 2.5

 

7.0 / 2.5

 

 

 

 

 

6.4 / 2.2

 

 

 

9.2 / 3.1

 

8.7 / 3.0

 

 

 

11.5 / 3.8

 

11.2 / 3.5

 

 

 

 

 

10.5 / 3.0

 

 

 

13.1 / 4.1

 

11.8 / 3.9

 

 

 

 

64

 

34

 

 

 

1.1 / 2600

 

2.1 / 9500

 

4000

 

R290 / 1.5

 

157 x 155 x 85

 

G 1'' external

 

258

 

400 / 16

2.98

 

 

2.9

 

 

 

 

30

5.38

 

 

5.23

 

2

Automatic

Hot gas

Yes (heated)

Yes

2

External

English

1.This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temperature and 55 °C heating water flow temperature.

2.See CE declaration of conformity

3.The heat circulating pump and the heat pump controller must always be ready for operation.

www.dimplex.de

E-9

Image 10
Contents LA 11PS Table of contents Legal Regulations Directives Please Read ImmediatelyImportant Information Energy-Efficient Use Heat PumpApplication Purpose of the Heat PumpScope of Delivery Operating PrincipleTransport Switch BoxHeat Pump Controller General Information InstallationSet-up Condensed Water PipeElectrical Connection ProcedureStart-up PreparationMaintenance Maintenance / CleaningCleaning the Heating System Cleaning the Air System Faults / Trouble- ShootingDecommissioning/ Disposal Device Information Type and order code DesignAnhang / Appendix / Annexes IIIMaßbild / Dimension Drawing Schéma cotéDiagramme / Diagrams / Diagrammes HGLQJXQJHQÂ&RQGLWLRQVÂ&RQGLWLRQVStromlaufpläne / Circuit Diagrams / Schémas électriques Steuerung / Control / CommandeLast / Load / Charge Anschlussplan / Circuit Diagram / Schéma électrique MDYHVII Viii Anhang · Appendix · Annexes Bivalente Anlage / Bivalent System / Installation bivalente Anhang · Appendix · Annexes XII