Dimplex LA 11PS manual Set-up, Installation, General Information, Condensed Water Pipe

Page 6

6.2

5 Set-up

5.1General Information

The heat pump is suited for outdoor installation. The device should always be installed on a permanently smooth, even and horizontal surface and must be aligned vertically. The entire frame should lie directly on the ground to ensure a good sound- proof seal and to prevent the water-bearing components from be- coming too cold. If this is not the case, additional insulation measures may be necessary. It must be possible to carry out maintenance work without hindrance. This can be ensured by maintaining a clearance of 1.2 m to any fixed walls.

 P

 P

 P

 P

ATTENTION!

Do not restrict or block the area around the air intake or outlet.

5.2Condensed Water Pipe

Condensed water that forms during operation must be drained off frost-free. The heat pump must be mounted on a level plane to guarantee proper drainage. The condensed water pipe must have a minimum diameter of 50 mm and should be fed frost-free into a sewer. Condensate should not be discharged directly into clearing tanks and cesspits because the aggressive vapours could destroy the evaporator.

6 Installation

6.1General Information

The following connections need to be established on the heat pump:

„Flow and return flow of the heating system

„Condensate outflow

„Control line to the heat pump controller

„Power supply

6.2Heating System Connection

The heating system connections on the heat pump have a 1 1/4" external thread.

Route the connection hoses out of the device in a downwards di- rection. Use a spanner to firmly grip the transitions when con- necting the heat pump. After the heat pump has been installed, the ductwork must be sealed so that the connection is gastight.

Before connecting the heating water system to the heat pump, the heating system must be flushed to remove any impurities, residue from sealants, etc., and to prevent any accumulation of deposits in the liquifier. A contaminated liquifier may cause the heat pump to completely break down. For systems in which the heating water flow can be shut off via the radiator or thermostat valves, an overflow valve must be installed in a heating bypass downstream from the heat pump by the customer. This ensures a minimum heating water flow rate through the heat pump and helps to avoid faults.

Once the heating system has been installed, it must be filled, de- aerated and pressure-tested (in the heat pump the air-relief cock is located at or in the water pipes at the condenser).

$LUUHOLHIFRFN

&RQGHQVHU

English

Minimum heating water flow rate

The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing either a manifold without differential pressure or an overflow valve. The procedure for adjusting an overflow valve is described in the Chapter Start-up.

Antifreeze

Manual drainage should be provided for heat pumps which are exposed to frost. The antifreeze function of the heat pump con- troller is active whenever the controller and the heat circulating pump are ready for operation. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained, and if required, blown out, at three locations (see illus- tration). The heating circuit should be operated with a suitable antifreeze if heat pump systems are implemented in buildings where a power failure can not be detected (holiday home).

www.dimplex.de

E-5

Image 6
Contents LA 11PS Table of contents Legal Regulations Directives Please Read ImmediatelyImportant Information Energy-Efficient Use Heat PumpApplication Purpose of the Heat PumpScope of Delivery Operating PrincipleSwitch Box TransportHeat Pump Controller General Information InstallationSet-up Condensed Water PipeElectrical Connection ProcedureStart-up PreparationMaintenance / Cleaning MaintenanceCleaning the Heating System Faults / Trouble- Shooting Cleaning the Air SystemDecommissioning/ Disposal Device Information Type and order code DesignAnhang / Appendix / Annexes IIIMaßbild / Dimension Drawing Schéma cotéDiagramme / Diagrams / Diagrammes HGLQJXQJHQÂ&RQGLWLRQVÂ&RQGLWLRQVStromlaufpläne / Circuit Diagrams / Schémas électriques Steuerung / Control / CommandeLast / Load / Charge Anschlussplan / Circuit Diagram / Schéma électrique MDYHVII Viii Anhang · Appendix · Annexes Bivalente Anlage / Bivalent System / Installation bivalente Anhang · Appendix · Annexes XII