Carrier 50RLP Installation, Aquazone System Control Panel Inputs and Outputs

Page 10

INSTALLATION

Inspection — Inspect the package contents for visual de- fects that may have occurred during shipping. If there is any damage, contact your local representative before proceeding.

Mounting Location — The Aquazone™ system control panel should be located indoors. Be sure the location prevents moisture and rain from coming into contact with the internal hardware. Avoid areas where excessive moisture, corrosive fumes, or vapors are present. The ambient temperature range at the location should be between 32 to 125 F. Do not install the Aquazone system control panel in electrical interference or high radio frequency areas. Select a location which will be safe from water damage and allow sufficient access for service and

wiring. For proper service of the Aquazone system control panel, the following service clearances are recommended:

Height: 54 in.

Width: 42 in.

Depth: 36 in.

Mounting — Mount the Aquazone system control panel to a wall with screws or bolts (not provided). Attach through the mounting holes provided in enclosure. Provide clearance to open key-locked access door. Refer to the mounting sheet in- cluded with the Aquazone system control panel for additional detailed mounting instructions.

Wiring — The Aquazone System Control Panel inputs and outputs are shown in Table 2.

Table 2 — Aquazone System Control Panel Inputs and Outputs

PARAMETER

POWER

INPUT/OUTPUT

TERMINAL

Processor Module

 

 

 

Loop Water Flow

24 vdc

Input

FLOW

System Supply Water Temp.

10 K thermistor

Input

SSWT

System Return Water Temp.

10 K thermistor

Input

SRWT

System Differential Pressure

4-20 mA

Input

SDP

Remote Occupied Mode

24 vdc

Input

RMTOCC

System Shut Down

24 vdc

Input

ALLSYS

Override Input for Zones 1 & 2

24 vdc

Input

OVRIZ1, OVRIZ2

Pump Number 1 & 2 Speeds

4-20 mA

Output

PUMP1, PUMP2

Cooling Tower 1 & 2 Speed/Level

4-20 mA

Output

CTL1, CTL2

Heat Source 1 & 2 Speed/Level

4-20 mA

Output

BLRL1, BLRL2

System Enable for Zone 1 & 2

24 vdc

Output

SYSZ1, SYSZ2

First Optional I/O Module

 

 

 

Override Input for Zone 3 to 10

24 vdc

Input

OVRIZ3 — OVRIZ10

System Enable for Zone 3 to 10

24 vdc

Input

SYSZ3 — SYSZ10

Second Optional I/O Module

 

 

 

Override Input for Zone 11 to 18

24 vdc

Input

OVRIZ11 — OVRIZ18

System Enable for Zone 11 to 18

24 vdc

Input

SYSZ11 — SYSZ18

Pump Control

 

 

 

Occupancy Schedule 1 to 18

Logic

Internal Parameter

Network Global Schedule 65 to 82

Logic

Internal Parameter

Override Input 1 to 18

Logic

Input

OVRIZ1 — OVRIZ18

System Enable Outputs

Logic

Output

SYSZ1 — SYSZ18

Remote Occupied Mode

Logic

Input

RMTOCC

System Differential Pressure

Logic

Input

SDP

System Differential Pressure Set point

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Control Type

Logic

User Configuration

Pump Number 1 & 2 Speeds

Logic

Output

PUMP1, PUMP2

Shut Down Command

Logic

Output

ALLSYS

Heat Rejection Control

 

 

 

System Supply Water Temp.

Logic

Input

SSWT

System Return Water Temp.

Logic

Input

SRWT

System Loop Temperature Set points

Logic

User Configuration

Fluid Cooler/Tower Control

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Cooling Tower 1 & 2 Speed/Level

Logic

Output

CTL1, CTL2

Heat Addition Control

 

 

 

System Supply Water Temp.

Logic

Input

SSWT

System Return Water Temp.

Logic

Input

SRWT

System Loop Temperature Set points

Logic

User Configuration

Boiler Control Type

Logic

User Configuration

Loop Water Flow

Logic

Input

FLOW

Boiler 1 & 2 Speed/Level

Logic

Output

BLRL1, BLRL2

10

Image 10
Contents Safety Considerations ContentsGeneral Components Aquazone System Control Panel HardwareTypical Stand-Alone Wshp System Premierlink Aquazone SystemAquazone System Control Panel Control Relay or Staging Card TP Wires To Comfort Controller PremierLink Control Module PremierLink Controller Applications with Complete C Control Ordering Thermostat Type Functions Number Field-Supplied Hardware For CCN ApplicaAquazone Thermostats 50QE900-220WSParameter Power INPUT/OUTPUT Terminal InstallationAquazone System Control Panel Inputs and Outputs PremierLink Controller Inputs and Outputs Typical Aquazone System Control Panel Size Schedule 40 Pipe Loop Water Flow Switch LED DisplayGPM START-UP Water Flow Switch TroubleshootingProblem Solution Recommended CablesConnection to CCN Bus Check System Parameters To check system OCCPC01Operative Keys Log Off from Controller To log off from the AquaLID Function Keys Numeric KeysTypical LID Device Quick Access Chart Algo Stat Hist Srvc Alrm SET SchdSequence of Operation Hardware Points 33 to 64 HWP33-64 ConfigurationHardware Points 1 to 32 HWP01-32 Description Value NameOutput Displayed Total Number of StagesTotal Number of Stages Stage Activated Stage DeactivatedSoftware Points 65 to 96 SWP65-96 System Pressure SETPT02 Global DictionaryLoop Supply Water SETPT01 Global Dictionary AquamascLoop Supply Water Set Point Screen Cooling Tower 1 COOLT1 Pump 1 Speed PUMP1Heating Control 1 HEAT1 Occupancy Schedule OCCPC01 Copyright 2003 Carrier Corporation

50RLP specifications

The Carrier 50RLP is a well-regarded air conditioning unit that combines efficiency, durability, and innovative technology to provide optimal cooling solutions for both residential and commercial applications. This model is part of Carrier's extensive lineup designed to meet various climate control needs.

One of the standout features of the Carrier 50RLP is its high energy efficiency rating. Equipped with a scroll compressor, the system operates efficiently, reducing energy consumption significantly. This not only lowers utility bills for the user but also contributes to a smaller carbon footprint, making it an environmentally friendly choice. The unit adheres to stringent energy standards, often exceeding the minimum requirements, which is especially advantageous in regions with strict energy codes.

The Carrier 50RLP also boasts advanced refrigerant technology. Utilizing R-410A refrigerant, the unit is designed to minimize ozone depletion potential. R-410A is known for its effectiveness in heat exchange as well as its stability, thus ensuring reliable performance over the unit's lifespan. Additionally, the option for variable refrigerant flow technology in some variants of the 50RLP allows for precise temperature control, making it adaptable to varying cooling needs.

Durability is another hallmark of the Carrier 50RLP. The unit features a robust construction with weatherproof materials that withstand harsh environmental conditions. This resilience is crucial for outdoor installations and contributes to a longer lifespan. Carrier also incorporates innovative sound reduction technologies, allowing the unit to operate quietly, making it suitable for both residential and commercial settings where noise levels are a concern.

Furthermore, the Carrier 50RLP is equipped with advanced controls. The inclusion of smart thermostat capabilities enables users to manage and schedule cooling efficiently, optimizing energy usage based on occupancy or time of day. These controls can often be integrated with home automation systems, enhancing user convenience.

In summary, the Carrier 50RLP air conditioning unit brings together high efficiency, innovative refrigerant technology, robust durability, and advanced smart controls. Its design not only meets the cooling demands of various spaces but also promotes energy savings and environmental sustainability. Ideal for both residential and commercial applications, the Carrier 50RLP stands out as a reliable choice for maintaining comfortable indoor environments. Whether for new installations or replacements, this model is a testament to Carrier's commitment to quality and innovation in HVAC technology.