Carrier 50RLP Start-Up, Water Flow Switch Troubleshooting, Recommended Cables, Problem Solution

Page 14

Table 5 — Water Flow Switch Troubleshooting

PROBLEM

SOLUTION

No display or output from the flow sensor

Check for 24 VAC across pins 1 and 3. These are small pins and caution should

 

be used when measuring the voltage in the harness so as not to damage the connector.

 

Check flow switch pin connections for damage.

Flow sensor indicates zero flow

Check for air in the chilled water system.

when flow is present

Check for 24 vac across pins 1 and 3. These are small pins and caution should be used

 

 

when measuring the voltage in the harness so as not to damage the connector.

 

Check for fouling on the sensor switch, which could inhibit the dissipation of heat from the probe.

 

Consider replacing the flow switch. The switch might be out of calibration,

 

the internal heater may have been damaged by extreme temperatures, pressure

 

or vibration, or mechanical damage to the tip of the device may have occurred.

Flow Sensor indicates flow

Check for 24 vac across pins 1 and 3. These are small pins and caution should

when no flow is present

be used when measuring the voltage in the harness so as not to damage the connector.

 

Low voltage can lead to less heat generated by the internal heater.

 

Consider replacing the flow switch. The switch might be out of calibration, the internal

 

heater may have been damaged by extreme temperatures, pressure or vibration, or

 

mechanical damage to the tip of the device may have occurred.

Connect to CCN Communication Bus — The Aquazone™ system control panel primary controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins and likewise positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3-pin plug. See Fig. 9.

At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.

NOTE: Carrier device default is 9600 baud.

COMMUNICATION BUS WIRE SPECIFICATIONS — The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded three-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network. See Table 6 for recommended cable.

Table 6 — Recommended Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required.

The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communi- cation bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).

START-UP

LID Power Up Display — When power is applied to the Aquazone System Control panel, the red LED on the top front of the processor module will flash at a rapid pace (about twice a second) for the first 20 seconds. This rapid flash will then be replaced by a slower pace of about once per second.

The green LED below the red LED will start flashing. This LED indicates input/output communications for accessory input output modules and the LID display.

The first six red LEDs on the controller will light.

The yellow LED will flash when the controller is broadcast- ing CCN messages to a laptop or other computer.

The LID display will show the controller identification, time and date as shown below.

Aquazone System hh:mm mm-dd-yy

Log On to the LID Display — To Log On to the LID display of the Aquazone System Control panel, perform the following procedure:

1.Press 3 and then SET . The LID display will show: Controller Password

2.Press ENTER . The LID display will show: Log in to Controller

Enter Password

NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the display will only show the word “pass- word.” Press the EXPN/EDIT key to toggle to the Status mode.

3.Key in the password and press ENTER . NOTE: The default password is 1111.

4.The LID display will show: Log in to Controller Logged In

14

Image 14
Contents General ContentsSafety Considerations Components Aquazone System Control Panel HardwareTypical Stand-Alone Wshp System Premierlink Aquazone SystemAquazone System Control Panel Control Relay or Staging Card TP Wires To Comfort Controller PremierLink Control Module PremierLink Controller Applications with Complete C Control Ordering Thermostat Type Functions Number Field-Supplied Hardware For CCN ApplicaAquazone Thermostats 50QE900-220WSAquazone System Control Panel Inputs and Outputs InstallationParameter Power INPUT/OUTPUT Terminal PremierLink Controller Inputs and Outputs Typical Aquazone System Control Panel GPM Loop Water Flow Switch LED DisplaySize Schedule 40 Pipe START-UP Water Flow Switch TroubleshootingProblem Solution Recommended CablesConnection to CCN Bus Check System Parameters To check system OCCPC01Operative Keys Log Off from Controller To log off from the AquaLID Function Keys Numeric KeysTypical LID Device Quick Access Chart Algo Stat Hist Srvc Alrm SET SchdSequence of Operation Hardware Points 33 to 64 HWP33-64 ConfigurationHardware Points 1 to 32 HWP01-32 Description Value NameOutput Displayed Total Number of StagesTotal Number of Stages Stage Activated Stage DeactivatedSoftware Points 65 to 96 SWP65-96 System Pressure SETPT02 Global DictionaryLoop Supply Water SETPT01 Global Dictionary AquamascLoop Supply Water Set Point Screen Heating Control 1 HEAT1 Pump 1 Speed PUMP1Cooling Tower 1 COOLT1 Occupancy Schedule OCCPC01 Copyright 2003 Carrier Corporation

50RLP specifications

The Carrier 50RLP is a well-regarded air conditioning unit that combines efficiency, durability, and innovative technology to provide optimal cooling solutions for both residential and commercial applications. This model is part of Carrier's extensive lineup designed to meet various climate control needs.

One of the standout features of the Carrier 50RLP is its high energy efficiency rating. Equipped with a scroll compressor, the system operates efficiently, reducing energy consumption significantly. This not only lowers utility bills for the user but also contributes to a smaller carbon footprint, making it an environmentally friendly choice. The unit adheres to stringent energy standards, often exceeding the minimum requirements, which is especially advantageous in regions with strict energy codes.

The Carrier 50RLP also boasts advanced refrigerant technology. Utilizing R-410A refrigerant, the unit is designed to minimize ozone depletion potential. R-410A is known for its effectiveness in heat exchange as well as its stability, thus ensuring reliable performance over the unit's lifespan. Additionally, the option for variable refrigerant flow technology in some variants of the 50RLP allows for precise temperature control, making it adaptable to varying cooling needs.

Durability is another hallmark of the Carrier 50RLP. The unit features a robust construction with weatherproof materials that withstand harsh environmental conditions. This resilience is crucial for outdoor installations and contributes to a longer lifespan. Carrier also incorporates innovative sound reduction technologies, allowing the unit to operate quietly, making it suitable for both residential and commercial settings where noise levels are a concern.

Furthermore, the Carrier 50RLP is equipped with advanced controls. The inclusion of smart thermostat capabilities enables users to manage and schedule cooling efficiently, optimizing energy usage based on occupancy or time of day. These controls can often be integrated with home automation systems, enhancing user convenience.

In summary, the Carrier 50RLP air conditioning unit brings together high efficiency, innovative refrigerant technology, robust durability, and advanced smart controls. Its design not only meets the cooling demands of various spaces but also promotes energy savings and environmental sustainability. Ideal for both residential and commercial applications, the Carrier 50RLP stands out as a reliable choice for maintaining comfortable indoor environments. Whether for new installations or replacements, this model is a testament to Carrier's commitment to quality and innovation in HVAC technology.