Carrier ZONEKIT2ZCAR ÐTroubleshooting, LED Codes Error Description Action Required

Page 10

I

Red LEDÐDisplays ON when fan is energized.

 

J

Red LEDÐDisplays ON when first-stage cooling is

energized.

 

K

Red LEDÐDisplays ON when second-stage cooling is

energized.

L

Red LEDÐDisplays ON when reversing valve is ener-

gized.

Red LEDÐDisplays ON when first-stage heat is M energized.

N

Red LEDÐDisplays ON when second-stage heat

is energized.

J2 (Not Shown)ÐCut for 50 hz operation. Lo- O cated under plastic housing approximately 1 in.

above comprotec override.

Table 2ÐTroubleshooting

 

 

 

 

 

 

LED CODES

ERROR DESCRIPTION

ACTION REQUIRED

 

Green flashes 1 time every sec and no

Normal operation.

None.

 

other LEDs are flashing.

 

 

 

 

 

 

Wait until duct temperature cools below

 

Green flashes 1 time and Red flashes 1

Duct temperature sensor. First-stage heat

exceeded temperature trip. (Heat leaving

 

air temperature trip limits set at LAT limits

 

time

limit exceeded; heat will be locked out.

 

POT on central control circuit board; range

 

 

 

 

 

 

is 110° to 175°F.)

 

Green flashes 1 time and Red flashes 2

Duct temperature sensor. Second-stage

Wait until duct temperature cools below

 

exceeded temperature trip. Range is 105°

 

times

heat limit exceeded.

 

to 155°F.

 

 

 

 

Green flashes 1 time and Red flashes 3

Duct temperature sensor. First-stage cool

Wait until duct temperature raises above

 

times

limit exceeded; cool will be locked out.

exceeded temperature trip (45°F).

 

Green flashes 1 time and Red flashes 4

Duct temperature sensor. Second-stage

Wait until duct temperature raises above

 

times

cool limit exceeded.

exceeded temperature trip (50°F).

 

Green flashes 1 time and Red flashes 5

HP temperature sensor. First-stage heat

Wait until HP temperature cools below ex-

 

times

limit exceeded; heat will be locked out.

ceeded temperature trip. Fixed at 110°F.

 

Green flashes 2 times and Red flashes 1

HP temperature sensor error. Second-

Wait until HP temperature cools below ex-

 

time

stage heat limit exceeded.

ceeded temperature trip. Fixed at 105°F.

 

Green flashes 2 times and Red flashes 2

HP temperature sensor. First-stage cool

Wait until duct temperature raises above

 

times

limit exceeded; cool will be locked out.

exceeded temperature trip (45°F).

 

Green flashes 2 times and Red flashes 3

HP temperature sensor. Second-stage cool

Wait until duct temperature raises above

 

times

limit exceeded.

exceeded temperature trip (50°F).

 

Green flashes 2 times and Red flashes 4

 

1. Verify that duct temperature sensor or

 

1. Duct temperature sensor.

10k ohm resistor is attached to control cen-

 

times

2. Temperature sensor is shorted.

ter at duct temperature connectors.

 

 

 

2. Replace duct temperature sensor.

 

Green flashes 2 times and Red flashes 5

 

1. Verify that duct temperature sensor or

 

1. Duct temperature sensor.

10k ohm resistor is attached to control cen-

 

times

2. Temperature sensor is open.

ter at duct temperature connectors.

 

 

 

2. Replace duct temperature sensor.

 

Green flashes 3 times and Red flashes 1

 

1. Verify that HP temperature sensor or

 

1. HP temperature sensor.

10k ohm resistor is attached to control cen-

 

time

2. Temperature sensor is shorted.

ter at HP temperature connectors.

 

 

 

2. Replace HP temperature sensor.

 

Green flashes 3 times and Red flashes 2

 

1. Verify that HP temperature sensor or

 

1. HP temperature sensor.

10k ohm resistor is attached to control cen-

 

times

2. Temperature sensor is open.

ter at HP temperature connectors.

 

 

 

2. Replace HP temperature sensor.

 

 

 

1. Check for short circuits on damper wire

 

Green flashes 3 times and Red flashes 3

 

connections at the dampers and control

 

Damper fuse blown.

center.

 

times

2. Replace damper fuse.

 

 

 

 

 

3. Check damper operation, may need to

 

 

 

be replaced.

 

Green flashes 3 times and Red flashes 4

Fatal control center circuit board failure.

Replace control center.

 

times

 

 

 

 

 

 

 

10

Image 10
Contents → ÐWeatherMaker Two-Zone SystemA97292 Shown Without Cover ÐInstall WeatherMaker Two-Zone ÐWiringÐInstall Zone Dampers ÐRectangular Metal Ductwork ÐAvailable Heating and Cooling Stages Versus System Type Sequence of OperationIt is highly recommended that you use this control option. Zone Center Connections ÐElectronic Non-Programmable Thermostat Wiring Diagrams ÐElectronic Programmable Thermostat Wiring Diagrams Care and MaintenanceTroubleshooting ÐSystem Diagram, Jumpers, and SwitchesÐTroubleshooting LED Codes Error Description Action Required→ ÐWiring Diagram Reference → ÐTemperature/Ohm/Voltage RelationshipWiring Diagrams Conditioner With Single-Speed Air Conditioner → ÐSingle-Stage Furnace With Single-Speed Air Conditioner→ ÐTypical Fan Coil → ÐFK4C Fan Coil With Single-Speed Air→ ÐSingle-Stage Furnace With 2-Speed Air Conditioner → ÐSingle-Stage Furnace With Single-Speed Heat Pump → ÐSingle-Stage Furnace With 2-Speed Heat Pump → ÐTypical Fan Coil With Single-Speed Heat Pump→ ÐFK4C Fan Coil With Single-Speed Heat Pump → ÐTypical Fan Coil With 2-Speed Heat Pump → Wiring Diagram Notes→ ÐFK4C Fan Coil With 2-Speed Heat Pump