TROUBLESHOOTING
This section contains information to assist you in troubleshooting problems and errors associated with the WeatherMaker
Step 1ÐSystem Diagram, Jumpers, and Switches
→NOTE: For correct control board operation, it must have either a sensor attached or a 10k resistor in place at the duct and HP inputs.
1 |
|
|
| FncÐGas/electric thermostat is installed in | |
|
|
| |||
|
|
| each zone. | ||
|
|
| Must be in this position to function prop- | ||
|
|
|
| ||
|
|
|
| erly. | |
Tstat | |||||
| |||||
|
|
|
| HPÐDO NOT USE. | |
|
|
|
| ||
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
|
2 |
|
|
|
| FncÐAir conditioning equipment installed |
|
|
|
| ||
|
|
|
| is a cooling only unit. | |
Equipmt |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| HPÐAir conditioning equipment installed |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| is a heat pump. |
3 |
|
|
|
| W/O FANÐWhen demand for heating ex- |
|
|
|
| ||
|
|
|
| ||
|
|
|
| ||
|
|
|
| ists, fan is controlled by gas/electric fur- | |
Fnc Ht |
|
|
|
| nace. |
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| W/FANÐWhen demand for heating exists, |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| fan comes on immediately (heat pump |
|
|
|
|
| only). |
|
|
|
|
| |
|
|
|
|
| |
4 |
|
|
|
| DTO OffÐWhen |
|
|
|
| ||
|
|
|
| approach a trip limit, HVAC equipment | |
|
|
|
|
| will turn off. Dampers do not open until |
|
|
|
|
| |
DTO |
|
|
|
| equipment is locked out by control. |
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
| DTO OnÐWhen |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
| approach a trip limit, closed dampers open |
A |
|
|
|
| to maintain proper air temperatures. |
|
|
|
| ||
|
|
|
| ||
Damper FuseÐProtects damper from electrical dam- | |||||
age (3 Amp). |
High Heating Temperature Trip Limit Setting Ð B When DTO is On, temperature is sensed by duct temperature sensor. When the duct temperature reaches this temperature setting, the duct temperature
optimizer is enabled.
If the LAT is exceeded then heating will turn off.
NOTE: HP temperature sensor is recommended for all heat pump applications.
| NORMAL GAS/ | EQUIPMENT |
NORMAL HEAT | ELECTRICAL | SHUTOFF |
PUMP SETTING | SETTING | TEMPERATURE |
155°F | 155°F | 175°F |
147°F | 147°F | 164°F |
138°F | 138°F | 153°F |
130°F | 130°F | 143°F |
122°F | 122°F | 132°F |
113°F | 113°F | 121°F |
105°F | 105°F | 110°F |
Emergency Heat SwitchÐThis switch should remain C in the OFF position for both furnace and heat pump operation. It should be switched to the ON position only upon heat pump compressor failure to provide
emergency heat.
ON |
|
|
| OFF |
|
|
| ||
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Comprotec OverrideÐMomentarily short D pins together for temporary equipment time
delay override.
J6 jumperÐConnects Rc and Rh inter- E nally.
F | Emergency heat LEDÐWill turn on when |
emergency heat is on. |
G
H Green LEDÐFlashes once every second for normal operation, alternates with red LED for diagnostic errors.
9