Carrier ZONEKIT2ZCAR → ÐTemperature/Ohm/Voltage Relationship, → ÐWiring Diagram Reference

Page 11

Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the WeatherMaker Two-Zone System. This table will evaluate both the Duct/HP temperature sensor operation. Use a digital multimeter to perform the following:

To verify a sensor is good, disconnect both leads from the I/O board and measure the resistance through the sensor. Match ohm reading to table and compare temperature reading on table to ambient temperature surrounding sensor (Accuracy should be ± 5-10 percent). Example: if 10.92k

ohms are measured, this equals approximately 73°F.

To verify if I/O board is normal, reattach sensor to I/O board, set meter to 5vdc, and measure voltage across terminal connections. Match voltage reading to temperature reading in chart. The ambient temperature surrounding sensor should be ± 5-10 percent. Example: 2.61vdc is

approximately 73°F.

Table 3ÐTemperature/Ohm/Voltage Relationship

TEMP °F

OHMS

VOLTS

TEMP °F

OHMS

VOLTS

TEMP °F

OHMS

VOLTS

TEMP °F

OHMS

VOLTS

30

34,367

3.873

73

10,921

2.610

117

4042

1.439

160

1693

0.724

32

32,654

3.828

75

10,449

2.555

118

3889

1.400

162

1637

0.703

34

31,030

3.781

77

10,000

2.500

120

3743

1.362

163

1582

0.683

36

29,498

3.734

79

9571

2.445

122

3603

1.324

165

1530

0.663

37

28,052

3.686

81

9164

2.391

124

3469

1.288

167

1480

0.645

39

26,686

3.637

82

8776

2.337

126

3340

1.252

169

1431

0.626

41

25,396

3.587

84

8407

2.284

127

3217

1.217

171

1385

0.608

43

24,171

3.537

86

8056

2.231

129

3099

1.183

172

1340

0.591

45

23,013

3.485

88

7720

2.178

131

2986

1.150

174

1297

0.574

46

21,918

3.433

90

7401

2.127

133

2878

1.117

176

1255

0.558

48

20,883

3.381

91

7096

2.075

135

2774

1.086

178

1215

0.542

50

19,903

3.328

93

6806

2.025

136

2675

1.055

180

1177

0.527

52

18,972

3.274

95

6530

1.975

138

2579

1.025

181

1140

0.512

54

18,090

3.220

97

6266

1.926

140

2488

0.996

183

1104

0.497

55

17,255

3.165

99

6014

1.878

142

2400

0.968

185

1010

0.483

57

16,464

3.111

100

5774

1.830

144

2315

0.940

187

1037

0.470

59

15,714

3.056

102

5546

1.784

145

2235

0.913

189

1005

0.457

61

15,000

3.000

104

5327

1.738

147

2157

0.887

190

974

0.444

63

14,323

2.944

106

5117

1.692

149

2083

0.862

Ð

Ð

Ð

64

13,681

2.889

108

4918

1.648

151

2011

0.837

Ð

Ð

Ð

66

13,071

2.833

109

4727

1.605

153

1943

0.813

Ð

Ð

Ð

68

12,493

2.777

111

4544

1.562

154

1876

0.790

Ð

Ð

Ð

70

11,942

2.721

113

4370

1.521

156

1813

0.767

Ð

Ð

Ð

72

11,418

2.666

115

4203

1.480

158

1752

0.745

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

 

 

WIRING DIAGRAMS

Table 4ÐWiring Diagram Reference

OUTDOOR

SINGLE-SPEED

TWO-SPEED

SINGLE-SPEED

TWO-SPEED

UNIT

AIR CONDITIONER

AIR CONDITIONER

HEAT PUMP

HEAT PUMP

Single-Stage Furnace

Fig. 15

Fig. 19

Fig. 23

Fig. 27

Two-Stage Furnace

Fig. 16

Fig. 20

Fig. 24

Fig. 28

Typical Fan Coil

Fig. 17

Fig. 21

Fig. 25

Fig. 29

FK4C Fan Coil

Fig. 18

Fig. 22

Fig. 26

Fig. 30

 

 

 

 

 

11

Image 11
Contents → ÐWeatherMaker Two-Zone SystemA97292 Shown Without Cover ÐInstall Zone Dampers ÐWiringÐInstall WeatherMaker Two-Zone ÐRectangular Metal Ductwork Sequence of Operation ÐAvailable Heating and Cooling Stages Versus System TypeIt is highly recommended that you use this control option. Zone Center Connections ÐElectronic Non-Programmable Thermostat Wiring Diagrams Care and Maintenance ÐElectronic Programmable Thermostat Wiring DiagramsÐSystem Diagram, Jumpers, and Switches TroubleshootingLED Codes Error Description Action Required ÐTroubleshootingWiring Diagrams → ÐTemperature/Ohm/Voltage Relationship→ ÐWiring Diagram Reference With Single-Speed Air → ÐSingle-Stage Furnace With Single-Speed Air Conditioner→ ÐTypical Fan Coil → ÐFK4C Fan Coil Conditioner With Single-Speed Air Conditioner→ ÐSingle-Stage Furnace With 2-Speed Air Conditioner → ÐSingle-Stage Furnace With Single-Speed Heat Pump → ÐFK4C Fan Coil With Single-Speed Heat Pump → ÐTypical Fan Coil With Single-Speed Heat Pump→ ÐSingle-Stage Furnace With 2-Speed Heat Pump → ÐFK4C Fan Coil With 2-Speed Heat Pump → Wiring Diagram Notes→ ÐTypical Fan Coil With 2-Speed Heat Pump