Step 5ÐInstall Barometric Bypass Damper
NOTE: The barometric bypass damper is a critical part of the WeatherMaker
The bypass should be installed according to local codes and SMACNA standards. Be sure the bypass is properly supported.
For proper installation, refer to the Installation Instructions pack- aged with the barometric bypass.
Failure to properly install the bypass damper can cause permanent damage to the HVAC equipment. For
→Step 6ÐInstall Leaving Air Temperature Duct Sensor
Locate duct temperature sensor in main supply trunk after heating and cooling coil and before the bypass damper and before the first branch. The duct sensor must be radiant shielded to prevent heat from affecting the correct air temperature.
1.Drill
2.Insert sensor in hole and use as template to mark 2 mounting holes.
3.Drill two
4.Use 2 No. 6 sheet metal screws to mount duct temperature sensor to unit.
5.Connect sensor to
→Step 7ÐInstall Heat Pump (HP) Temperature Sensor
The HP temperature sensor is required in all heat pump/fan coil installations. It is not used in dual fuel (heat pump/furnace installation.) It measures the indoor coil temperature. The sensor is to be installed downstream of the indoor coil, but before the electric heaters. It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet. Anchor firmly in place with cable ties so that it cannot interfere with the blower wheel. To activate the HP temperature sensor, remove factory supplied resistor from HP terminal block and replace with sensor leads. When activated, the HP temperature sensor has built in LAT set points of 50°F and 45°F in the cooling mode, and 105°F and 110°F in the heating mode. This is
SEQUENCE OF OPERATION
Step 1ÐSequence of Events for a Normal Heating or Cooling Cycle
The thermostats will determine if active heating or cooling is required. If so, the WeatherMaker
· Make sure all zone dampers are fully open.
·Energize HVAC equipment fan.
·Energize heating or cooling equipment. The equipment may be a compressor, furnace, strip heater, etc.
·Set zone damper to the open or closed position based upon individual zone demand.
·Energize additional stages of heating or cooling if the thermostat demand warrants.
·Turn off heating or cooling equipment when all zones are satisfied.
·Open all zone dampers when equipment is turned off (after 90 sec delay).
This is the basic sequence of operation for the WeatherMaker
Step 2ÐSelection of a System Mode
The first step in any heating or cooling cycle requires Weather- Maker
Step 3ÐPre-Positioning Dampers and Starting System Fan
In order to minimize noise and enhance system operation, Weath- erMaker
The other reason for opening the dampers is to provide unrestricted ductwork to other equipment which is not directly controlled by WeatherMaker
Only the zone 1 thermostat controls continuous fan operation. When the zone 1 thermostat has the fan selector switch in the AUTO position, the fan will operate only when the heating and cooling equipment is operating. When the zone 1 thermostat has the fan selector switch in the ON position, the fan will operate continuously. Zone 2 will not control this.
Step 4Ð HVAC Equipment Connections
The WeatherMaker
Table 1ÐAvailable Heating and Cooling Stages Versus System Type
TYPE OF HVAC | COOLING STAGE 1 | COOLING STAGE 2 | REVERSING VALVE | HEAT STAGE 1 | HEAT STAGE 2 | REVERSING VALVE | |
EQUIPMENT USED | O | O | |||||
Y1 | Ð | Energized | Y1/W1 | W2 | |||
Pump | |||||||
|
|
|
|
|
| ||
Y1 | Y2 | Energized | Y1/W1 | W2 | |||
Cooling Only, any | Y1 | Y2 | Ð | W1 | W2 | Ð | |
Heater Type | |||||||
|
|
|
|
|
|
4