Section 1 — Post Installation Start-up and Adjustments

Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators

1.4GENERATOR TESTS UNDER LOAD

To test the generator set with electrical loads applied, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or OPEN) position.

2.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

3.Set the generator's AUTO/OFF/MANUAL switch to OFF.

4.Turn OFF the utility power supply to the transfer switch, using the means provided (such as a utility main line circuit breaker).

Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

5.Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.

6.Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.

7.Let the engine stabilize and warm up for a few minutes.

8.Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.

9.Turn ON electrical loads connected to transfer switch T1 and T2. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.

10.Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.

11.Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.

12.When testing under load is complete, turn OFF electrical loads.

13.Set the generator's main circuit breaker to its OFF (or OPEN) position.

14.Let the engine run at no-load for a few minutes.

15.Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

1.5CHECKING AUTOMATIC

OPERATION

To check the system for proper automatic operation, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or OPEN) position.

2.Check that the AUTO/OFF/MANUAL switch is set to OFF.

3.Turn OFF the utility power supply to the transfer switch, using means provided (such as a utility main line circuit breaker).

4.Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the utility power source side.

5.Turn ON the utility power supply to the transfer switch, using the means provided (such as a utility main line circuit breaker).

6.Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.

7.Turn OFF the utility power supply to the transfer switch.

With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.

With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:

After about six seconds, the switch should transfer loads back to the utility power source.

About one minute after retransfer, the engine should shut down.

1.6ADJUSTING THE REGULATOR

(NATURAL GAS ONLY)

Although the generator has been factory set to provide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.

If experiencing engine problems at high or full load conditions follow these steps. It will require a frequency meter to perform this procedure.

1.Turn off utility power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open position.

2.Allow the generator to start. Before loading the generator, confirm that the No Load Frequency, with the top open and front panel off, is set to 63-63.5 Hz. Transfer load to emergency circuits.

Carrier 5

Image 7
Contents Parts, Adjustment and Maintenance Manual ‹ Read this Manual Thoroughly IntroductionImportant Safety Instructions General Hazards Electrical Hazards Before Initial START-UP Check Transfer Switch OperationElectrical Checks Generator Tests Under Load Adjusting the Regulator Natural GAS onlyChecking Automatic Operation Unit Volts Reconfiguring the Fuel System2 12KW and 15KW, V-TWIN Engines Engine Governor AdjustmentValve Clearance Voltage Regulator AdjustmentValve Clearance Adjustment Problem Cause Correction Troubleshooting GuideBe performed by the nearest Carrier Dealer Service ScheduleElectrical Data Customer Battery Utility SP1 IM1 SP2 IM2 Customer Connection Battery Charge 1VA Electrical Data Electrical Data Electrical Data Electrical Data ATS N2A N1A 51 9 3651 9115 QTY Description Carrier CONTROL, Panel Bottom Pull Main Reset ASSEMBLY, Home StandbyWire SOCKET, 12VDC AccessoryCarrier COVER, 8 Position GTS Load Center Transfer Switch Home Standby 100A 2PLimit Switch Operation not Shown BOX GTS Load CenterCarrier Washer Flat 1/4-M6 Zinc Wire HARNESS,GTS Load Center not Shown for ClarityCOVER, 12 Position GTS Load Center COVER, 10 Position GTS Load CenterCarrier ASSEMBLY, Governor Gear ASSEMBLY, Connecting RODASSEMBLY, Crankshaft GH410 Small Taper CRANKCASE, Subassembly with Plugs GH410Carrier ASSEMBLY,GOVERNOR Lever 12 HP HOUSING, BlowerASSEMBLY, Plastic Carb SWITCH, OIL 8.0 PSI1310 ASSEMBLY,GOVERNOR Gear ASSEMBLY, BreatherASSEMBLY, Head #1 G&S ASSEMBLY, OIL Fill CAP122 138 ASSEMBLY, MIXER/AIRBOX KNOB, AIR CleanerPRE-CLEANER ELEMENT, AIR Cleaner ChromeCarrier ELEMENT, AIR Cleaner CABLE, #6 40 Black BatteryAssembly Brush Holder BASE, AIR CleanerCarrier Rotor 12KW CABLE, #6 48 Black BatteryStator 12KW Stator 13KW / 15KWPIN, Limited Adjustment HousingAssembly Adjuster SCREW, TwinCarrier Air-cooled Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators Catalog no AS-PA0 Form ASPAS07-1PD

ASPAS1CCA012, ASPAS1CCA015 specifications

The Carrier ASPAS1CCA015 and ASPAS1CCA012 are advanced air conditioning units designed to offer superior climate control in residential and light commercial settings. Both models reflect Carrier's commitment to innovation, energy efficiency, and user comfort.

One of the primary features of these units is their inverter technology. This smart technology adjusts the compressor speed in real-time, allowing the system to operate efficiently and maintain a consistent temperature. This results in reduced energy consumption and lower utility bills while providing a more comfortable indoor environment.

The ASPAS1CCA015 and ASPAS1CCA012 also include a state-of-the-art air filtration system. These units are equipped with a high-efficiency particulate air (HEPA) filter that effectively captures dust, allergens, and pollutants. This feature contributes to improved indoor air quality, making them ideal for allergy sufferers and those concerned about indoor air pollution.

In terms of performance, both models deliver impressive cooling and heating capacities. The ASPAS1CCA015 has a cooling capacity of 15,000 BTUs, while the ASPAS1CCA012 offers a cooling capacity of 12,000 BTUs. This range makes them suitable for various room sizes, ensuring effective temperature management whether during scorching summers or chilly winters.

A user-friendly digital thermostat and Wi-Fi connectivity are additional features that enhance the usability of these models. Homeowners can control their air conditioning systems remotely via smartphones or tablets, enabling them to adjust settings for optimum comfort and efficiency even when they are not at home.

The units are designed with quiet operation in mind. They utilize advanced silencing technologies, ensuring that noise levels remain low, allowing for peaceful environments during night-time or in quiet settings. This is particularly beneficial for bedrooms, nurseries, or offices where distraction-free air conditioning is essential.

Moreover, both models are compliant with the latest standards for energy efficiency, earning high SEER (Seasonal Energy Efficiency Ratio) ratings. This not only promotes environmental sustainability but also aligns with governmental incentives aimed at reducing energy consumption.

In summary, the Carrier ASPAS1CCA015 and ASPAS1CCA012 are equipped with cutting-edge technologies and features that make them reliable and efficient air conditioning solutions. With their inverter technology, advanced filtration systems, remote connectivity, and quiet operation, these units represent a combination of comfort, convenience, and environmental responsibility that meets the needs of modern users.