Carrier 1620, 2420, 2020 installation instructions Points are SHARP! be Very Careful During Cleaning

Page 8

GAPAB

At the time of air purifier cartridge replacement, if a powdery residue is noticed on the tips of the points in the ionization array, proceed to clean them by completing the following steps:

Step 1 Turn heating and cooling system power off.

!WARNING

ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system. There may be more than one (1) disconnect switch.

Step 2 Turn the Infinityt Air Purifier switch to the off position.

Step 3 Remove the Infinityt Air Purifier door.

Step 4 Unplug the power cord and flow sensor cable (if connected) from the enhancement module 9 ( See Fig. 7 and 8)

Step 5 Slide out the enhancement module assembly and safety screen.

!WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.

Step 6 Slide out the Safety Screen and set aside.

NOTE: Best cleaning tools: 5 inch handle paint brush with 2 inch width (or greater) brush point (synthetic or natural bristle) (See Fig. 14) or vacuum cleaner with brush attachment.

Step 7 Gently stroke the ionization pins on the top plane of each bar with enough brush depth to hit front and back tips of the points in the ionization array. Use a gentle back and forth brushing motion to clean any small accumulations from the tips of the points. If desired, use vacuum cleaner with brush attachment to gently vacuum the frame and components of enhancement module.

Step 8 Reinstall the Safety Screen. Step 9 Slide in enhancement module.

Step 10 Reconnect the power cord and flow sensor cable. Step 11 Replace the Infinityt Air Purifier Door

Step 12 Turn the Infinityt Air Purifier switch to the on position.

Step 13 Turn heating and cooling system power on .

30°

POINTS ARE SHARP! BE VERY CAREFUL DURING CLEANING.

Tip of point with residue

Tip of point after cleaning

A06671

Fig. 14 ---Removal of Deposits from Ionization Pins

8

Image 8
Contents Table of Contents Safety ConsiderationsIntroduction HOW IT WorksApplication Considerations Personal Injury HazardInstallation Check Infinityt Air Purifier ComponentsCUT Hazard Identify Mounting LocationUnit Damage Hazard Mount CabinetElectrical Shock and High Voltage Hazard Equipment Damage Hazard WiringPower Cord Installed Fan Coil Chassis Ground Maintenance START-UP and OperationChecking Air Purifier Operation Infinity ControlPoints are SHARP! be Very Careful During Cleaning Removal of Deposits from Ionization PinsTroubleshooting Safety HazardSpecifications and Dimensions DimensionsWarranty For Service or REPAIR, Follow These Steps in OrderCatalog No GAPAB-2SI