Carrier 48GP (N) 024-060, 50GL 024-060, 48JZ (N) 024-060 ICM Fiop START-UP, FAN Operation

Page 10

value. If circuit R to G is open (0–v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over cooling.

e.ELECTRIC HEATING MODE

(1.) Thermostat closes circuit R to W/W1, or W2—The unit delivers the selected electric heat airflow. There are no on or off delays.

f.HEAT PUMP HEATING MODE (50JZ only)

(1.) Thermostat closes circuits R to G and R to Y/Y2—The unit delivers selected heat pump heating airflow.

g.HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT (50JZ only)

(1.) Thermostat closes circuits R to G, R to Y/Y2 and R to W/W1 or W2 (and R to O in the case of defrost).

In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.

h.HEATING MODE—SUPER COMFORT HEAT OPERA- TION

NOTE: The indoor control used, such as a Thermidistat™, must be capable of providing Super Comfort Heat operation mode and control must be configured as outlined in its installation instruc- tions. The system must be installed with appropriate outdoor temperature sensor. Consult indoor control literature to determine if control is capable and for configuration instructions. Consult indoor control instructions and sensor instructions for sensor installation details.

If the outdoor temperature is in the range of 12° to 40° F, the Thermidistat™ closes circuit R to Y/Y2 and opens circuit R to G. If circuit R to G is closed (24-v.), the motor will deliver airflow at the full heating requested value. If circuit R to G is open (0-v.) for maximum heating comfort, the motor delivers reduced airflow to maximize the temperature and minimize the draft effect of the heated air leaving the unit.

ICM FIOP START-UP

ICM General Start Up

CHECKING AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with Puron® (R-410A) refrigerant, and is tested and factory sealed.

NOTE: Adjustment of the refrigerant charge is not required UNLESS the unit is suspected of not having the proper R-410A charge.

The charging label and the tables shown refer to system tempera- tures and pressures. The temperatures and pressures are calculated at rated airflow. When charging unit, set to rated airflow. A refrigerant charging chart label is attached to the outside of the compressor access door. The chart includes the required suction line temperature at given suction line pressures and outdoor ambients. An accurate superheat, thermocouple- or thermistor-type thermometer, and gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not

use mercury or small dial-type thermometers because they are not adequate for this type of measurement

IMPORTANT: When evaluating the refrigerant charge, an indi- cated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insuf-

ficient airflow across either one or both coils.

Step 1—48GP Start-Up (ICM FIOP)

CHECKING COOLING CONTROL OPERATION-Start and check the unit for proper cooling control operation as follows:

(1.) Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position. Note fan delay time setting selected on the Easy Select™ board. (See Easy Select Section.)

(2.) Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room tem- perature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evapo- rator fan will continue to run for the time setting selected on Easy Select™ board. (See Easy Select Section.)

(3.) When using an auto-changeover room thermostat, place both SYSTEM and FAN switches in AUTO position. Observe that unit operates in heating mode when tempera- ture control is set to “call for heating” (above room temperature) and operates in cooling mode when tempera- ture control is set to “call for cooling” (below room temperature).

AIRFLOW AND TEMPERATURE RISE-The heating section for each size unit is designed and approved for heating operation within the temperature rise range stamped on the unit rating plate. Table 15 shows the approved temperature rise range for each heating input, and the air delivery (CFM) at various temperature rise ranges.

The heating operation airflow must produce a temperature rise that falls with in the approved range.

Refer to Indoor Airflow and Airflow Tables on the following pages to adjust heating airflow when required.

CHECK HEATING CONTROL-Start and check the unit for proper heating control operation as follows. (see furnace lighting instructions located inside burner or blower access panel.):

(1.) Place room thermostat SYSTEM switch in the HEAT position and the FAN switch in the AUTO position.

(2.) Set the heating temperature control of the thermostat above room temperature.

(3.) The induced-draft motor will start.

(4.) After a call for heating, the main burner should light with in 5 sec. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the lockout control, break the 24-v. power to W.

(5.) The indoor fan will turn on 45 sec after the flame has been established. The indoor fan will turn off according to time delay selected on the Easy Select™ board (See Easy Select Section) after the thermostat has been satisfied.

Step 2—48JZ Start-Up (ICM FIOP)

Also refer to the Thermidistat™ instructions for start up and check out of the system.

(1.) FAN OPERATION—

The fan button on Thermidistat™ switches fan icon between AUTO and ON. While ON is displayed, output will be on, turning fan on. Allow up to 10 sec. after button is pressed for fan to turn on and off. the fan will continue to run for the time setting selected on the Easy Select™ board after AUTO icon is displayed.

10

Image 10
Contents Installation, Start-Up, and Operating Instructions Control Voltage Connections Special Procedures for 208-V OperationEasy SELECT-48GP Standard ConnectionWhen Thermostat is SET on Continuous FAN Time Delay ProfileHigh Airflow AIR Conditioner Accessory Installation48GP Sequence of Operation Easy SELECT-48JZ Select OptionsHumidifier Wiring-48JZ Tion 48JZ Sequence of OperationEasy SELECT-50GL & 50JZ Page Humidifier Wiring for 50GL & 50JZ 50GL & 50JZ Sequence of OperationICM Fiop START-UP FAN OperationHeat Pump Heating Cooling ModeGAS Heat Mode Automatic CHANGE-OVERICM Fiop Physical Data-Unit 48GP 48GP with ICM Fiop Electrical Data LOSS-OF-CHARGE/LOW-PRESSURE SwitchSize 48GP ICM Fiop Electric Schematic-Unit 48GP Indoor Coil ICM Fiop Physical Data-Unit 48JZOutdoor Coil Indoor Blower48JZ with ICM Fiop Electrical Data ICM Fiop Electric Schematic-Unit 48JZ ICM Fiop Physical Data-Unit 50GL 50GL with ICM Fiop Electrical Data Heat Power Supply Size 50GLRange Motor ICM Fiop Electrical Schematic-50GL Compressor Quantity Type ICM Fiop Physical Data-Unit 50JZRefrigerant Range Motor Heat Power Supply Size 50JZ 50JZ with ICM Fiop Electrical DataICM Fiop Electrical Schematic-50JZ CFM Adjust LO PIN NOM PIN HI PIN Unit PIN Select Size 48GP & 48JZ Gas Heating ICM Airflow Small Cabinet 48GP & 48JZ ICM Air Flow vs. Temperature Rise Chart48GP & 48JZ Gas Heating ICM Airflow Large Cabinet Minimum Airflow for Reliable Electric Heater Operation CFM ICM Fiop WET Coil Pressure Drop in. wg Electric Heat Pressure Drop Table in. wgElectric Heat Pressure Drop Table in. wg Large Cabinet Filter Pressure Drop Table in. wgTroubleshooting Chart Cause RemedySTART-UP Checklist Preliminary InformationBook Catalog No Form 48-21SI 10-01 Replaces 48-20SI Tab

48JZ (N) 024-060, 50JZ 024-060, 48GP (N) 024-060, 50GL 024-060 specifications

The Carrier 50GL 024-060, 48GP (N) 024-060, 50JZ 024-060, and 48JZ (N) 024-060 units are part of Carrier’s advanced HVAC solutions, offering efficient cooling and heating systems designed for both residential and light commercial applications. These models are known for their reliability, energy efficiency, and innovative technology, making them a popular choice for users looking to enhance comfort while reducing operational costs.

One of the main features of the Carrier 50GL series is its use of high-efficiency compressors. These compressors are engineered to operate quietly and effectively, providing optimal performance even during peak load conditions. Additionally, they are equipped with smart features that allow for precise temperature control and improved energy savings, often exceeding standard performance metrics.

The 48GP (N) units are particularly notable for their compact design, making them ideal for installations where space is a limitation. Despite their smaller footprint, they boast significant cooling and heating capacities, ensuring consistent comfort. The use of advanced variable-speed technology in these units helps to maintain consistent indoor temperatures while minimizing energy consumption.

The 50JZ and 48JZ (N) models incorporate advanced inverter technology, allowing for variable refrigerant flow. This technology adjusts the system's output according to the demand, resulting in lower energy usage and increased comfort levels. Additionally, these units feature enhanced filtration systems that improve indoor air quality by capturing airborne pollutants, allergens, and other contaminants.

Another key characteristic of these Carrier units is their durability. Built with high-quality materials, they are designed to withstand harsh environmental conditions, ensuring longevity and reduced maintenance requirements. Furthermore, the installation process is simplified, thanks to user-friendly design features that promote easy serviceability and accessibility.

Overall, the Carrier 50GL 024-060, 48GP (N) 024-060, 50JZ 024-060, and 48JZ (N) 024-060 HVAC units stand out in the industry for their advanced features, energy efficiency, and robust performance. They offer a comprehensive solution for anyone seeking reliable temperature control and improved indoor air quality in a variety of settings.