Carrier 50JZ 024-060 High Airflow, Time Delay Profile, When Thermostat is SET on Continuous FAN

Page 3

HIGH VOLTAGE

 

POWER LEADS

POWER

(SEE UNIT WIRING

SUPPLY

LABEL)

 

GND

FIELD-SUPPLIED

FUSED DISCONNECT

a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE

Factory selected gas heat size should correspond to unit label.

b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED

Factory selected air conditioner size should correspond to

capacity of unit installed. Installer should verify air conditioner

size to ensure that airflow delivered falls within proper range

for the size unit installed. This applies to all operational modes.

c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED

CONTROL BOX

 

BLK(DH)

 

YEL(Y)

 

GRN(G)

LOW-VOLTAGE

RED(R)

POWER LEADS

(SEE UNIT

BRN(C)

WIRING LABEL)

 

WHI(W1)

 

GRA(W2)

DHUM

Y

G

R

C

W1

W2

THERMOSTAT (TYPICAL)

Factory selected on 48GP for AC-Air conditioner.

For Gas Heat/Electric Cool Unit–AC must be selected.

d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR

HIGH AIRFLOW

The AC/HP CFM Adjust select is factory set to the High-HI

(NOM for 060) tap. The CFM Adjust selections NOM/LO will

regulate airflow supplied for all operational modes, except

non-heat pump heating modes. HI provides 15 percent airflow

over nominal unit size selected and LO provides 10 percent

airflow below nominal unit size selected. Adjust selection

options are provided to adjust airflow supplied to meet indi-

SPLICE BOX

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

C01027

Fig. 4—50GL High- and Control-Voltage

Connections

HIGH VOLTAGE

 

POWER LEADS

POWER

(SEE UNIT WIRING

SUPPLY

LABEL)

 

GND

FIELD-SUPPLIED

FUSED DISCONNECT

vidual installation needs for such things as noise, comfort, and

humidity removal (See Fig. 8, D as indicated).

e. ON/OFF DELAY—SELECT DESIRED

TIME DELAY PROFILE

Four motor operation delay profiles are provided to customize

and enhance system operation (See Fig. 8, E as indicated).

Selection options are:

(1.) The standard 90 sec off delay (Factory Setting) at 100

 

percent airflow in cooling mode. In heating mode, IGC

 

will control 45 sec on delay with no airflow and 45 sec off

 

delay.

(2.)

A 30 sec cooling delay with no airflow/ 90 sec off delay at

 

100 percent airflow profile is used when it is desirable to

 

allow system coils time to cool-down in conjunction with

 

the airflow in heating mode.

(3.)

A no delay option used for servicing unit or when a

CONTROL BOX

 

BLK(DH)

 

YEL(Y)

 

GRN(G)

LOW-VOLTAGE

RED(R)

POWER LEADS

(SEE UNIT

BRN(C)

WIRING LABEL)

 

WHI(W1)

 

GRA(W2)

 

ORN(0)

DHUM

Y

G

R

C

W1

W2

O

THERMOSTAT (TYPICAL)

 

thermostat is utilized to perform delay functions in cooling

 

mode. In heating mode IGC will control 45 sec on delay

 

with no airflow and 45 sec off delay.

(4.) Not recommended for 48GP

f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED

WHEN THERMOSTAT IS SET ON CONTINUOUS FAN

(1.)

LO speed—Factory setting, 50 percent cooling mode

 

airflow.

(2.)

MED speed—Move connector to MED, 65 percent cooling

 

mode airflow.

(3.)

HI speed—Move connector to HI, 100 percent cooling

 

mode airflow (See Fig. 8, F as indicated).

SPLICE BOX

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

C01028

Fig. 5—50JZ High- and Control-Voltage

Connections

The ICM motor uses the selected taps to modify its operation to a pre-programmed table of airflows.

The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8).

g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE

The low-voltage circuit is fused by a board-mounted 5–amp

automotive fuse placed in series with the transformer SEC2 and

the R circuit. The C circuit of the transformer is referenced to

chassis ground through a printed circuit run at SEC1 connected

to metal standoff marked with ground symbol.

h. BASIC UNIT CONFIGURATION

The following basic configuration of the indoor motor will

provide ARI rated performance of the 48GP. This BASIC

CONFIGURATION should be used when the rated ARI perfor-

mance is required, or if system enhancements such as super

dehumidify are not needed.

(1.) HEAT-Factory selected to match heat input size.

3

Image 3
Contents Installation, Start-Up, and Operating Instructions Standard Connection Special Procedures for 208-V OperationEasy SELECT-48GP Control Voltage ConnectionsTime Delay Profile When Thermostat is SET on Continuous FANHigh Airflow Accessory Installation AIR Conditioner48GP Sequence of Operation Select Options Easy SELECT-48JZHumidifier Wiring-48JZ 48JZ Sequence of Operation TionEasy SELECT-50GL & 50JZ Page 50GL & 50JZ Sequence of Operation Humidifier Wiring for 50GL & 50JZFAN Operation ICM Fiop START-UPAutomatic CHANGE-OVER Cooling ModeGAS Heat Mode Heat Pump HeatingICM Fiop Physical Data-Unit 48GP LOSS-OF-CHARGE/LOW-PRESSURE Switch 48GP with ICM Fiop Electrical DataSize 48GP ICM Fiop Electric Schematic-Unit 48GP Indoor Blower ICM Fiop Physical Data-Unit 48JZOutdoor Coil Indoor Coil48JZ with ICM Fiop Electrical Data ICM Fiop Electric Schematic-Unit 48JZ ICM Fiop Physical Data-Unit 50GL Heat Power Supply Size 50GL 50GL with ICM Fiop Electrical DataRange Motor ICM Fiop Electrical Schematic-50GL ICM Fiop Physical Data-Unit 50JZ Compressor Quantity TypeRefrigerant 50JZ with ICM Fiop Electrical Data Range Motor Heat Power Supply Size 50JZICM Fiop Electrical Schematic-50JZ CFM Adjust LO PIN NOM PIN HI PIN Unit PIN Select Size 48GP & 48JZ ICM Air Flow vs. Temperature Rise Chart 48GP & 48JZ Gas Heating ICM Airflow Small Cabinet48GP & 48JZ Gas Heating ICM Airflow Large Cabinet Minimum Airflow for Reliable Electric Heater Operation CFM Filter Pressure Drop Table in. wg Electric Heat Pressure Drop Table in. wgElectric Heat Pressure Drop Table in. wg Large Cabinet ICM Fiop WET Coil Pressure Drop in. wgCause Remedy Troubleshooting ChartPreliminary Information START-UP ChecklistBook Catalog No Form 48-21SI 10-01 Replaces 48-20SI Tab

48JZ (N) 024-060, 50JZ 024-060, 48GP (N) 024-060, 50GL 024-060 specifications

The Carrier 50GL 024-060, 48GP (N) 024-060, 50JZ 024-060, and 48JZ (N) 024-060 units are part of Carrier’s advanced HVAC solutions, offering efficient cooling and heating systems designed for both residential and light commercial applications. These models are known for their reliability, energy efficiency, and innovative technology, making them a popular choice for users looking to enhance comfort while reducing operational costs.

One of the main features of the Carrier 50GL series is its use of high-efficiency compressors. These compressors are engineered to operate quietly and effectively, providing optimal performance even during peak load conditions. Additionally, they are equipped with smart features that allow for precise temperature control and improved energy savings, often exceeding standard performance metrics.

The 48GP (N) units are particularly notable for their compact design, making them ideal for installations where space is a limitation. Despite their smaller footprint, they boast significant cooling and heating capacities, ensuring consistent comfort. The use of advanced variable-speed technology in these units helps to maintain consistent indoor temperatures while minimizing energy consumption.

The 50JZ and 48JZ (N) models incorporate advanced inverter technology, allowing for variable refrigerant flow. This technology adjusts the system's output according to the demand, resulting in lower energy usage and increased comfort levels. Additionally, these units feature enhanced filtration systems that improve indoor air quality by capturing airborne pollutants, allergens, and other contaminants.

Another key characteristic of these Carrier units is their durability. Built with high-quality materials, they are designed to withstand harsh environmental conditions, ensuring longevity and reduced maintenance requirements. Furthermore, the installation process is simplified, thanks to user-friendly design features that promote easy serviceability and accessibility.

Overall, the Carrier 50GL 024-060, 48GP (N) 024-060, 50JZ 024-060, and 48JZ (N) 024-060 HVAC units stand out in the industry for their advanced features, energy efficiency, and robust performance. They offer a comprehensive solution for anyone seeking reliable temperature control and improved indoor air quality in a variety of settings.