Carrier 50ZH024-060 Heating Mode Charge, ÐIndoor Airflow and Airflow Adjustments

Page 11

C01022

Fig. 15AÐTypical Unit Electrical Diagram (208/230±1±60)

charts to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.

Example: (See Fig. 16)

Outdoor Temperature Ð85°F

Suction PressureÐ74 psig

Suction Temperature should beÐ60°F

NoteÐSuction Temperature may vary +/- 5°F.

HEATING MODE CHARGE

Do not attempt to adjust charge by cooling methods while in heat pump heating mode. Recover refrigerant and weigh in according to unit data plate refrigerant data.

Step 4ÐIndoor Airflow and Airflow Adjustments

NOTE: For cooling operation, the recommended airflow is 350 to 450 cfm per each 12,000 Btuh of rated cooling capacity.

Table 4 shows dry coil air delivery for horizontal discharge units. Tables 5-7 show pressure drops.

11

Image 11
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation50ZH030 50ZH02450ZH048 50ZH03650ZH042 ÐUnit Base Dimensions, 50ZH060 ÐProvide for Condensate Disposal Install Flanges for Ductwork Connections 50ZH060 only024 ÐInstall Electrical ConnectionsÐMinimum Airflow for Safe Electric Heater Operation CFM HIGH-VOLTAGE ConnectionsPhysical Data START-UP PRE-START-UPÐRefrigerant Charge ÐStart-Up Cooling Section and Make AdjustmentsÐCheck for Refrigerant Leaks ÐIndoor Airflow and Airflow Adjustments Heating Mode ChargeÐSequence of Operation For 460-V MotorsÐUnit Controls HIGH-PRESSURE Relief ValveUsed ÐElectrical DataÐ50ZHHeat Pump Heating CoolingDefrost MaintenanceÐOutdoor Coil, Indoor Coil, and Condensate Drain Pan ÐAir FilterÐUnit Top Removal Outdoor-Coil Side ÐIndoor Blower and Motor048 ² ÐOutdoor Fan460 Volt Unit 042 ²ÐFilter Pressure Drop in. wg ÐAccessory Electric Heat Pressure Drop In. wgÐWet Coil Pressure Drop ÐHigh Flow Valves ±Typical Heat Pump Operation, Heating Mode±Typical Heat Pump Operation, Cooling Mode ±50ZH Balance Point Chart Symptom Cause Remedy ÐTroubleshootingÐCooling and HeatingPRESSURES-Heating Mode TEMPERATURE-Cooling ModePRESSURES-Cooling Mode TEMPERATURE-Heating ModeBook Catalog No Form 50ZH-5SI Replaces 50ZH-4SI Tab