Carrier 50ZH024-060 instruction manual ±Typical Heat Pump Operation, Cooling Mode

Page 20

OUTDOOR COIL

ACCUMULATOR

COMPRESSOR

 

A

Check Valves

AClosed

BOpen

CClosed

DOpen

LEGEND

LCS Loss of Charge Switch

Acutrol Metering Device

Check Valve (Arrow indicates direction of flow)

INDOOR COIL

B

LCS

STRAINER

D

STRAINER

C

COOLING CYCLE

1.Hot gas from compressor flows through the 4-way valve and is directed to the heating liquid line check valve. It is then con- densed and subcooled through converging circuits. Refrigerant leaves the outdoor coil by way of the strainer and the check valve in the cooling liquid line.

2.The refrigerant then feeds the indoor coil through the Acutrol metering device on each circuit.

3.Each circuit evaporates the refrigerant and the circuits are com- bined in the indoor coil header with some of the circuits flowing through the check valve.

4.The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.

C95044

Fig. 24±Typical Heat Pump Operation, Cooling Mode

20

Image 20
Contents Table of Contents Safety ConsiderationsReceiving and Installation Introduction50ZH024 50ZH03050ZH048 50ZH03650ZH042 ÐUnit Base Dimensions, 50ZH060 Install Flanges for Ductwork Connections 50ZH060 only ÐProvide for Condensate DisposalÐInstall Electrical Connections ÐMinimum Airflow for Safe Electric Heater Operation CFMHIGH-VOLTAGE Connections 024Physical Data PRE-START-UP START-UPÐRefrigerant Charge ÐStart-Up Cooling Section and Make AdjustmentsÐCheck for Refrigerant Leaks Heating Mode Charge ÐIndoor Airflow and Airflow AdjustmentsFor 460-V Motors ÐUnit ControlsHIGH-PRESSURE Relief Valve ÐSequence of OperationÐElectrical DataÐ50ZH UsedCooling Heat Pump HeatingMaintenance DefrostÐAir Filter ÐUnit Top Removal Outdoor-Coil SideÐIndoor Blower and Motor ÐOutdoor Coil, Indoor Coil, and Condensate Drain PanÐOutdoor Fan 460 Volt Unit042 ² 048 ²ÐFilter Pressure Drop in. wg ÐAccessory Electric Heat Pressure Drop In. wgÐWet Coil Pressure Drop ±Typical Heat Pump Operation, Heating Mode ÐHigh Flow Valves±Typical Heat Pump Operation, Cooling Mode ±50ZH Balance Point Chart ÐTroubleshootingÐCooling and Heating Symptom Cause RemedyTEMPERATURE-Cooling Mode PRESSURES-Cooling ModeTEMPERATURE-Heating Mode PRESSURES-Heating ModeBook Catalog No Form 50ZH-5SI Replaces 50ZH-4SI Tab