Carrier 50ZH024-060 ±Typical Heat Pump Operation, Heating Mode, ÐHigh Flow Valves

Page 19

OUTDOOR COIL

ACCUMULATOR

COMPRESSOR

 

A

Check Valves

AOpen

BClosed

COpen

DClosed

LEGEND

LCS Loss of Charge Switch

Acutrol Metering Device

Check Valve (Arrow indicates direction of flow)

INDOOR COIL

B

LCS

STRAINER

D

STRAINER

C

HEATING CYCLE

1.Hot gas from compressor flows through the 4-way valve and is directed to the cooling liquid line check valve. It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line.

2.The refrigerant then feeds the outdoor coil through the Acutrol metering device on each circuit.

3.Each circuit evaporates the refrigerant and the circuits are com- bined in the outdoor header with some of the circuits flowing through the check valve.

4.The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.

C95045

Fig. 23±Typical Heat Pump Operation, Heating Mode

Check valves are also located in the liquid lines near the strainers.

The Strainers are the larger of the two components.

Step 12ÐHigh Flow Valves

Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.

19

Image 19
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation50ZH030 50ZH02450ZH042 50ZH03650ZH048 ÐUnit Base Dimensions, 50ZH060 ÐProvide for Condensate Disposal Install Flanges for Ductwork Connections 50ZH060 only024 ÐInstall Electrical ConnectionsÐMinimum Airflow for Safe Electric Heater Operation CFM HIGH-VOLTAGE ConnectionsPhysical Data START-UP PRE-START-UPÐCheck for Refrigerant Leaks ÐStart-Up Cooling Section and Make AdjustmentsÐRefrigerant Charge ÐIndoor Airflow and Airflow Adjustments Heating Mode ChargeÐSequence of Operation For 460-V MotorsÐUnit Controls HIGH-PRESSURE Relief ValveUsed ÐElectrical DataÐ50ZHHeat Pump Heating CoolingDefrost MaintenanceÐOutdoor Coil, Indoor Coil, and Condensate Drain Pan ÐAir FilterÐUnit Top Removal Outdoor-Coil Side ÐIndoor Blower and Motor048 ² ÐOutdoor Fan460 Volt Unit 042 ²ÐWet Coil Pressure Drop ÐAccessory Electric Heat Pressure Drop In. wgÐFilter Pressure Drop in. wg ÐHigh Flow Valves ±Typical Heat Pump Operation, Heating Mode±Typical Heat Pump Operation, Cooling Mode ±50ZH Balance Point Chart Symptom Cause Remedy ÐTroubleshootingÐCooling and HeatingPRESSURES-Heating Mode TEMPERATURE-Cooling ModePRESSURES-Cooling Mode TEMPERATURE-Heating ModeBook Catalog No Form 50ZH-5SI Replaces 50ZH-4SI Tab