Carrier 50ZH024-060 instruction manual ÐUnit Base Dimensions, 50ZH060

Page 5

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

 

INCHES [mm]

TOP OF UNIT

0

 

DUCT SIDE OF UNIT

0

 

SIDE OPPOSITE DUCTS

0

 

BOTTOM OF UNIT

0

 

NEC. REQUIRED CLEARANCES.

INCHES [mm]

 

BETWEEN UNITS, POWER ENTRY SIDE

42.00

[1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00

[914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

 

 

GROUNDED SURFACES, POWER ENTRY SIDE

42.00

[1066.8]

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

 

 

INCHES [mm]

CONDENSER. COIL ACCESS SIDE

30.00 [762.0]

POWER ENTRY SIDE

30.00

[762.0]

(EXCEPT FOR NEC REQUIREMENTS)

 

 

UNIT TOP

48.00

[1219.2]

SIDE OPPOSITE DUCTS

30.00

[762.0]

LEGEND

NEC – National Electrical Code

NOTES:

1. Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A removable fence or barricade requires no clearance.

2. Dimensions are in inches. Dimensions in [ ] are in millimeters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C00158

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

CENTER OF GRAVITY IN. (MM)

lb

kg

X

 

 

 

 

 

 

Y

Z

 

 

 

 

 

 

 

 

50ZH060

208/230-1-60, 208/230-3-60, 460-3-60

368

167

14.0 (356)

20.0 (508)

 

16.0 (406)

Fig. 4ÐUnit Base Dimensions, 50ZH060

5

Image 5
Contents Safety Considerations Table of ContentsIntroduction Receiving and Installation50ZH030 50ZH02450ZH048 50ZH03650ZH042 ÐUnit Base Dimensions, 50ZH060 ÐProvide for Condensate Disposal Install Flanges for Ductwork Connections 50ZH060 onlyÐMinimum Airflow for Safe Electric Heater Operation CFM ÐInstall Electrical ConnectionsHIGH-VOLTAGE Connections 024Physical Data START-UP PRE-START-UPÐRefrigerant Charge ÐStart-Up Cooling Section and Make AdjustmentsÐCheck for Refrigerant Leaks ÐIndoor Airflow and Airflow Adjustments Heating Mode ChargeÐUnit Controls For 460-V MotorsHIGH-PRESSURE Relief Valve ÐSequence of OperationUsed ÐElectrical DataÐ50ZHHeat Pump Heating CoolingDefrost MaintenanceÐUnit Top Removal Outdoor-Coil Side ÐAir FilterÐIndoor Blower and Motor ÐOutdoor Coil, Indoor Coil, and Condensate Drain Pan460 Volt Unit ÐOutdoor Fan042 ² 048 ²ÐFilter Pressure Drop in. wg ÐAccessory Electric Heat Pressure Drop In. wgÐWet Coil Pressure Drop ÐHigh Flow Valves ±Typical Heat Pump Operation, Heating Mode±Typical Heat Pump Operation, Cooling Mode ±50ZH Balance Point Chart Symptom Cause Remedy ÐTroubleshootingÐCooling and HeatingPRESSURES-Cooling Mode TEMPERATURE-Cooling ModeTEMPERATURE-Heating Mode PRESSURES-Heating ModeBook Catalog No Form 50ZH-5SI Replaces 50ZH-4SI Tab