Carrier 40RU manual Electrical Data, Standard Motors, Electrical Data, Alternate Motors

Page 20

Table 4 – Electrical Data, Standard Motors

 

 

 

 

 

VOLTAGE

FAN MOTOR

 

UNIT

---V---PH

Hz{

Hp (kW)

 

FLA

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

40RUA*25

208/230---

3---

60

187---

253

5.0 (3.73)

 

14.7/13.6

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

5.0 (3.73)

 

6.8

40RUQ*25

 

40RUS*25

575

3---

60

518

632

5.0 (3.73)

 

5.1

 

 

 

 

 

 

 

 

 

 

 

40RUA*28

208/230---

3---

60

187---

253

7.5 (5.59)

 

21.4/19.4

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

7.5 (5.59)

 

9.7

40RUS*28

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

7.5 (5.59)

 

7.8

 

 

 

 

 

 

 

 

 

 

 

40RUA30

208/230---

3---

60

187---

253

10.0 (7.46)

 

28.0/25.2

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

10.0 (7.46)

 

12.6

40RUS30

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

10.0 (7.46)

 

10.3

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

Minimum

MOCP

Circuit Amps

 

 

 

18.4/17.0

30/25

 

 

8.5

15

 

 

6.4

15

 

 

26.9/24.3

45/40

12.120

9.8

15

 

 

35.0/31.5

60/50

15.825

12.920

40RU

See Legend and Notes below.

Table 5 – Electrical Data, Alternate Motors

 

 

 

 

 

VOLTAGE

FAN MOTOR

 

UNIT

V---PH

Hz{

 

 

 

Hp (kW)

 

FLA

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

40RUA*25

208/230---

3---

60

187---

253

7.5 (5.59)

 

21.4/19.4

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

7.5 (5.59)

 

9.7

40RUQ*25

 

40RUS*25

575

3---

60

518

632

7.5 (5.59)

 

7.8

 

 

 

 

 

 

 

 

 

 

 

40RUA*28

208/230---

3---

60

187---

253

10.0 (7.46)

 

28.0/25.2

40RUA*30

 

 

 

 

 

 

 

 

 

460

3---

60

414

506

10.0 (7.46)

 

12.6

40RUS*28

 

 

 

 

 

 

 

 

 

 

575

3---

60

518

632

10.0 (7.46)

 

10.3

40RUS*30

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

Minimum

MOCP

Circuit Amps

 

 

 

26.9/24.3

45/40

12.120

9.8

15

 

 

35.0/31.5

60/50

15.825

12.920

See Legend and Notes below.

Legend and Notes for Tables 4 and 5

LEGEND:

FLA

---

Full Load Amps

MOCP

---

Maximum Overcurrent Protection

{Motors are designed for satisfactory operation within 10% of normal voltage shown. Voltages should not exceed the limits shown in the Voltage Limits column.

NOTES:

1.Minimum circuit amps (MCA) and MOCP values are calcu- lated in accordance with The NEC. Article 440.

2.Motor FLA values are established in accordance with Under- writers’ Laboratories (UL). Standard 1995.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula in the example (see column to the right) to determine the percentage of volt- age imbalance.

4.Installation with Accessory Electric Heaters

Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430--- 28 (1) or (2) (depends on length of conduit between heater enclosure and 40RU power entry location). Install wires in field--- installed conduit.

Example: Supply voltage is 230-3-60

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

 

average voltage

 

AB = 393 v

BC = 403 v

AC = 396 v

Average Voltage =

(393 + 403 + 396)

=

1192

 

 

3

3

 

 

=397

Determine maximum deviation from average voltage. (AB) 397 – 393 = 4 v

(BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

6

 

397

 

 

 

= 1.5%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

20

Image 20
Contents Installation, Start---Up Service Instructions PRE-INSTALLATION 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units 40RUQ Physical Data, English Heat Pump Units Unit 40RUQ40RUA Physical Data, SI Heat Pump Units Operating charge kgFins/m 591 138Chilled Water Coil 40RUS Physical Data, English Chilled Water UnitsUnit 40RUS Operating Weight kg Base Unit 40RUS Physical Data, SI Chilled Water UnitsFace Area sq m Upper Face Area sq m Lower Rows...Fins/m Max Working Pressure kPag at 125 CUnit Unit Weight 40RUA*2540RUQ*25 40RUS*25Dimensions Sizes 28 40RUA*28 1050 40RUA*30 1062 40RUS*28 1035 40RUS*30 1042U a a 2 5 a 1 a 6 0 a 0 a Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsUnit Coil Type TXV Distributor STD Feeder Tubes PER DistributorFitting Requirement 40RUA*28 Typical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Voltage Maximum 40RUHolding VA 25, 28Typical Fan Discharge Connections for Multiple Fan Units Label, TXV Adjustment 40RUA and 40RUQ onlyLubricant Data Manufacturer LubricantFan Rotation Fan Pulley Alignment Align as followsRemove Filter Retainer Clip Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishMotor Drive FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIUnit External Static Pressure kPa 000 542 577 1042 646 716 785 849 907 2830 10.77 11.94 13.08 1087 14.15 15.12 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure Drop40RU Catalog No 40RU---07SI START-UP Checklist 40RUA, 40RUQCheck Voltage Imbalance Comp A1 Comp B1