Carrier 40RU manual Refrigerant and Chilled Water Piping Access Holes

Page 13

Unit Isolation - Where extremely quiet operation is essential, install isolators between floor and base of unit, or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.

Refrigerant and Chilled Water Piping Access - The 40RU Series units come with standard knockouts for refrigerant and chilled water piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 40RUA*25, 28, and 30 units. 40RUQ*25 units, as well as 40RUS*25, 28, and 30 units require additional holes which must be field-fabricated to accommodate the piping. See Fig. 8 for the positions and dimensions of the additional access holes required for 40RUQ and 40RUS units. Recommended access hole use is also listed for all units. Note that Fig. 8 shows the access holes on the control-box side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.

IMPORTANT: Do not bury refrigerant piping underground.

Refrigerant Piping - See Tables 1A–1F for refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.

The 40RU direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-410A. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 40RU refrigerant piping. See Fig. 8, which also lists recommended knockouts and access holes to use for each 40RU unit size. Recommended fittings are listed in Table 3.

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 9.

NOTE: Be sure to remove the styrofoam shipping pad from the TXV. Verify that it has been removed. See Fig. 5.

IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.

The 40RU Series evaporator coils have a face-split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. See Fig. 10.

External TXV equalizer connections are provided and factory-brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig.11.

40RU

8

7

6

5

4

3

2

1

A

B

C

D

C10727

 

USE HOLE

FIELD--FABRICATED HOLE DIAMATERS

FIELD--FABRICATED HOLE POSITION DIMENSIONS

UNIT

 

in. (mm)

 

 

in. (mm)

 

NUMBERS

 

 

 

 

 

 

 

 

 

No. 5

No. 6

No. 7

No. 8

A

B

C

D

 

 

 

 

 

 

 

 

 

 

 

 

40RUA*25, 28, 30

1,2, 3, 4

 

 

 

 

 

 

 

 

 

 

40RUS*25

4, 5, 6, 7

13/4 (44.5)

13/4 (44.5)

13/4 (44.5)

3.0 (76.2)

6.0 (152.5)

10.5 (266.7)

40RUQ*25

3{, 5, 6, 7

11/8 (28.6)

11/8 (28.6)

13/4 (44.5)

3.25 (82.6)

6.125 (155.6)

10.38 (263.7)

 

40RUS*28, 30

5, 6, 7, 8

21/2 (63.5)

21/2 (63.5)

21/2 (63.5)

21/2 (63.5)

6.0 (152.5)

9.625 (244.5)

13.38 (339.9)

17.0 (431.8)

{ Must be enlarged from 11/8 in. (28.6mm) to 13/4 in. (44.5mm) NOTE: Access hole knockouts 1--- 4 are factory--- supplied.

Fig. 8 - Refrigerant and Chilled Water Piping Access Holes

13

Image 13
Contents Installation, Start---Up Service Instructions PRE-INSTALLATION 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units Unit 40RUQ 40RUQ Physical Data, English Heat Pump UnitsOperating charge kg 40RUA Physical Data, SI Heat Pump UnitsFins/m 591 138Unit 40RUS 40RUS Physical Data, English Chilled Water UnitsChilled Water Coil 40RUS Physical Data, SI Chilled Water Units Operating Weight kg Base UnitFace Area sq m Upper Face Area sq m Lower Rows...Fins/m Max Working Pressure kPag at 125 C40RUA*25 Unit Unit Weight40RUQ*25 40RUS*2540RUA*28 1050 40RUA*30 1062 40RUS*28 1035 40RUS*30 1042 Dimensions Sizes 28U a a 2 5 a 1 a 6 0 a 0 a Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Fitting Requirements Factory-Installed Nozzle and Distributor DataUnit Coil Type TXV Distributor STD Feeder Tubes PER Distributor40RUA*28 Fitting RequirementTypical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Alternate Motors Electrical Data, Standard Motors40RU Unit Voltage MaximumHolding VA 25, 28Typical Fan Discharge Connections for Multiple Fan Units 40RUA and 40RUQ only Label, TXV AdjustmentManufacturer Lubricant Lubricant DataFan Pulley Alignment Align as follows Fan RotationRemove Filter Retainer Clip Fan Motor Data, Alternate Motor English Fan Motor Data, Standard Motor EnglishFan Motor Data, Alternate Motor SI Fan Motor Data, Standard Motor SIMedium-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz EnglishMotor Drive FAN DriveStandard Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz EnglishHigh-Static Drive Data, 60 Hz SI Medium-Static Drive Data, 60 Hz SIUnit External Static Pressure kPa 000 542 577 1042 646 716 785 849 907 2830 10.77 11.94 13.08 1087 14.15 15.12 Unit Airflow Pressure Drop FACTORY-SUPPLIED Pressure Drop English40RU Catalog No 40RU---07SI 40RUA, 40RUQ START-UP ChecklistComp A1 Comp B1 Check Voltage Imbalance

40RU specifications

The Carrier 40RU is a highly regarded solution in the realm of commercial cooling systems, specifically designed for applications requiring reliable, long-lasting climate control. This unit stands out due to its engineering excellence, innovative features, and efficient operation.

One of the primary attributes of the Carrier 40RU is its robust construction. Engineered to withstand varying environmental conditions, this unit is built with high-quality materials that promote durability and longevity. The design incorporates corrosion-resistant finishes, which enhances its resilience, especially in outdoor installations.

The Carrier 40RU is equipped with advanced cooling technologies, including variable speed compressors and innovative coil designs. These technologies contribute to its exceptional energy efficiency, allowing the unit to optimize performance while minimizing energy consumption. The variable speed compressors adjust their output based on the current cooling demand, which not only saves energy but also reduces wear and tear on the equipment.

Additionally, the system features a sophisticated control platform that allows for ease of operation and monitoring. This control system offers numerous settings and modes, enabling users to customize their cooling experience based on specific needs. Integration with smart building systems is also possible, providing even greater flexibility and energy management capabilities.

The 40RU model includes a comprehensive filtration system that enhances indoor air quality by effectively capturing dust, allergens, and other particulates. This feature is essential for commercial spaces where maintaining a clean and healthy environment is paramount.

In terms of performance metrics, the Carrier 40RU offers impressive cooling capacities suitable for various applications, from small offices to large commercial buildings. Its noise levels are also minimized through the application of advanced acoustic insulation, ensuring a comfortable environment for occupants.

Moreover, the Carrier 40RU is designed with ease of maintenance in mind. Regular service points are readily accessible, allowing technicians to perform routine checks and repairs efficiently. This design consideration is crucial for minimizing downtime and ensuring the system operates optimally.

In summary, the Carrier 40RU combines rugged construction, energy-efficient technologies, advanced controls, and superior filtration to deliver an outstanding cooling solution for commercial applications. Its versatility, coupled with robust performance characteristics, makes it a preferred choice among HVAC professionals and building managers alike. Whether for new installations or upgrades, the 40RU ensures reliability and comfort in any environment.