Carrier 40RU manual Check Voltage Imbalance, Comp A1 Comp B1

Page 40

40RU

CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS:

AB

 

 

V

AC

 

V

BC

 

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

 

 

 

 

 

V

 

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

 

 

 

 

V

 

 

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START-UP

CHECK INDOOR FAN MOTOR SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RUS ONLY)

INTDOOR UNIT LEAVING WATER TEMP (40RUS ONLY)

COMPRESSOR AMPS (L1/L2/L3)

____/____/____

____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT 1/8 to 1/3 FULL? (Y/N)

NOTES:

Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date:01/11

Catalog No: 40RU---07SI

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Replaces: 40RU--- 05SI

40

Image 40
Contents Installation, Start---Up Service Instructions PRE-INSTALLATION 40RUA Physical Data, English Cooling Units 40RUA Physical Data, SI Cooling Units 40RUQ Physical Data, English Heat Pump Units Unit 40RUQ40RUA Physical Data, SI Heat Pump Units Operating charge kgFins/m 591 138Unit 40RUS 40RUS Physical Data, English Chilled Water UnitsChilled Water Coil Operating Weight kg Base Unit 40RUS Physical Data, SI Chilled Water UnitsFace Area sq m Upper Face Area sq m Lower Rows...Fins/m Max Working Pressure kPag at 125 CUnit Unit Weight 40RUA*2540RUQ*25 40RUS*25Dimensions Sizes 28 40RUA*28 1050 40RUA*30 1062 40RUS*28 1035 40RUS*30 1042U a a 2 5 a 1 a 6 0 a 0 a Preferred Suspension Technique Refrigerant and Chilled Water Piping Access Holes Face-Split Coil Suction and Liquid Line Piping Typical Factory-Installed Nozzle and Distributor Data Fitting RequirementsUnit Coil Type TXV Distributor STD Feeder Tubes PER DistributorFitting Requirement 40RUA*28Typical 40RUS Chilled Water Piping Condensate Drains Fire Hazard Electrical Data, Standard Motors Electrical Data, Alternate MotorsUnit Voltage Maximum 40RUHolding VA 25, 28Typical Fan Discharge Connections for Multiple Fan Units Label, TXV Adjustment 40RUA and 40RUQ onlyLubricant Data Manufacturer LubricantFan Rotation Fan Pulley Alignment Align as followsRemove Filter Retainer Clip Fan Motor Data, Standard Motor English Fan Motor Data, Alternate Motor EnglishFan Motor Data, Standard Motor SI Fan Motor Data, Alternate Motor SIStandard Drive Data, 60 Hz English Medium-Static Drive Data, 60 Hz EnglishMotor Drive FAN DriveHigh-Static Drive Data, 60 Hz English Standard Drive Data, 60 Hz SIMedium-Static Drive Data, 60 Hz SI High-Static Drive Data, 60 Hz SIUnit External Static Pressure kPa 000 542 577 1042 646 716 785 849 907 2830 10.77 11.94 13.08 1087 14.15 15.12 FACTORY-SUPPLIED Pressure Drop English Unit Airflow Pressure Drop 40RU Catalog No 40RU---07SI START-UP Checklist 40RUA, 40RUQCheck Voltage Imbalance Comp A1 Comp B1