INSTALLATION
48/50A Units — The CO2 sensor is to be installed in the predrilled holes located above the auxiliary control box (see Fig. 2).
1.Shut off unit power supply.
2.Open the hinged auxiliary control box access door and secure.
3.Remove the sensor and cover from the sensor mounting plate.
4.Secure mounting plate to bracket (48/50A) with no. 8 screws (see Fig. 3).
5.Wire the electrical harness to the sensor as shown in Fig. 3 and 4.
6.Remove the blankout plate from the partition, just above the auxiliary control box.
7.Attach the sensor to the mounting plate.
8.Mount the bracket to the partition using 2 sheet metal screws (see view F in Fig. 2).
9.Connect the electrical harness (PL18).
10.Restore power to unit.
CO2
SENSOR
48/50P and 48/50Z Units — The CO2 sensor is to be installed in the predrilled holes located in the power exhaust section. See Fig.
1.Shut off unit power supply.
2.Open the power exhaust section doors/panels to gain access.
3.Remove the sensor and cover from the sensor mounting plate.
4.Secure mounting plate to the bracket with no. 8 screws.
5.The electrical wire harness for the CO2 sensor is factory installed. Locate the four wires in the power exhaust section. Wire the electrical harness to the sensor as shown in Fig. 4.
6.Attach the sensor to the mounting plate.
Mount the bracket to the appropriate location:
size
BRACKET
PARTITION | (48/50A) |
| |
| ELECTRICAL |
| HARNESS |
VIEW F
AUXILIARY
CONTROL BOX
Fig. 2 — 48/50A CO2 Sensor Mounting Location
2