Carrier 48HJ004---007 ECONOMI$ER IV Standard Sensors, Outdoor Air Temperature OAT Sensor

Page 23

NOTE: These instructions are for installing the optional EconoMi$er IV and EconoMi$er2 only. Refer to the accessory EconoMi$er IV or EconoMi$er2 installation instructions when field installing an EconoMi$er IV or EconoMi$er2 accessory.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. (See Fig. 31.)

2.The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 26. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. (See Fig. 32.)

IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.

3.The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. (See Fig. 33.)

4.Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. (See Fig. 34.)

5.Remove the shipping tape holding the economizer barometric relief damper in place.

6.Insert the hood divider between the hood sides. (See Fig. 34 and 35.) Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.

7.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. (See Fig. 35.)

8.Caulk the ends of the joint between the unit top panel and the hood top. (See Fig. 33.)

9.Replace the filter access panel.

10.Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 36. EconoMi$er2 wiring is shown in Fig. 37.

Barometric flow capacity is shown in Fig. 38. Outdoor air leakage is shown in Fig. 39. Return air pressure drop is shown in Fig. 40.

FILTER ACCESS PANEL

COMPRESSOR

ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

C06023

Fig. 31 ---Typical Access Panel Locations

 

 

 

x

 

 

 

o

 

o

B

 

HOOD BOX

H

od

 

 

 

 

 

BRACKET

 

 

 

 

Fig. 32 ---Hood Box Removal

C06024

 

48HE,HJ

 

 

SIDE

 

 

 

 

PANEL

 

 

 

 

 

TOP

 

 

 

SIDE

 

 

CAULK

PANEL

 

 

 

 

 

HERE

 

 

INDOOR

 

INDOOR

 

COIL

 

COIL

 

ACCESS

 

ACCESS

 

PANEL

 

PANEL

 

 

 

C06025

 

Fig. 33 ---Indoor Coil Access Panel Relocation

 

 

 

TOP

 

 

 

PANEL

 

 

 

INDOOR COIL

 

 

 

ACCESS PANEL

LEFT

 

 

 

HOOD

B

SCREW

 

SIDE

 

 

 

19 1/16”

 

 

 

 

 

33 3/8”

 

HOOD DIVIDER

 

 

 

 

C06026

 

Fig. 34 ---Outdoor-Air Hood Construction

ECONOMI$ER IV STANDARD SENSORS

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. (See Fig. 29.) The operating range of temperature measurement is 40_ to 100_F.

23

Image 23
Contents Electrical Shock Hazard Installation InstructionsAlternate Unit Support FIRE, Explosion HazardRoof Curb 48HE,HJ Positioning Install Flue HoodProperty Damage Hazard 48HJ Unit Operating Dimensions Weight48HE 48HJ004-007 Base Unit Dimensions 48HE003-006 Base Unit Dimensions Heat anticipator settings Field power supplyField control wiring Nominal Capacity Physical Data 48HJHJE HJD Physical Data 48HE HEE HED Power Wiring Connections 48HE003---006 Electrical Data 48HEElectrical Data 48HJ 38.2 242 208/230---3---60 187 254 12.4 Convenience outlet AssemblyHUMIDI-MIZERADAPTIVE Dehumidification System Manual outdoor damperTypical Humidi-MiZer t Adaptive Dehumidification System Enthalpy Sensors and Control Install the Supply Air Temperature SAT SensorOutdoor Air Temperature Sensor OAT Install the Indoor Air Quality CO2 SensorPremierLink Controller PremierLinkSensor UsagePremierLinktController Installed EconoMi$er IV Component Locations Return Air Enthalphy SensorECONOMI$ER IV Standard Sensors Outdoor Air Temperature OAT SensorECONOMI$ER IV Control Modes RUN EconoMi$er IV WiringIndoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats Demand Controlled Ventilation DCV Enthalpy Changeover Set PointsBelt drive motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control Belt Drive Motor Mounting CO2Sensor Standard SettingsEvaporator-Fan Motor Data High-Static Motors 48HJ Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory static pressure Evaporator-Fan Motor Data Standard MotorAirflow 48HJ Outdoor Sound Power Total Unit48HE Outdoor Sound Power Total Unit Unit ARI Octave Bands Rating1300 Rpm Bhp1100 1200Rpm Bhp Watts 1700 Rpm Bhp WattsWatts Rpm Bhp 1200 16001642 2333 1704 Rpm Bhp Watts 15002800 Watts Rpm Bhp 18002600 2700Bhp 600 Bhp Watts Rpm2700 2800 2900 3000 Watts Rpm Bhp 900 Bhp Watts 900Watts Rpm Bhp Watts 1700 1800 1900 20001900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 1250 1500 1750 2000 2250 2500 2750 3000 Gas Piping Internal WiringRefrigerant Service Ports Unit PreparationHeating CoolingMain Burners Heating units without economizer Safety ReliefVentilation Continuous Fan Operating Sequence Cooling units without economizerRoutine 3 OAT DX Cooling Temperature Control ExampleNormal Design Operation Subcooling ModeUnits with HUMIDI-MIZERADAPTIVE Dehumidification System One-Row Coils CleaningEvaporator Coil Condenser coilLubrication Compressor Condenser-Fan AdjustmentHigh Pressure Switch FiltersHUMIDI-MIZERSYSTEM Charging Cooling Charging Chart Standard 48HJ006 To USE Cooling Charging CHART, Standard Unit Combustion-Air Blower Flue Gas PassagewaysBurner Ignition Limit SwitchLED Error Code Description Removal and Replacement of GAS Train SeeLOW Heat Replacement PartsOFM Economi$er IV troubleshooting completion Unit TroubleshootingEconomi$er IV Troubleshooting Dcv demand controlled ventilation and power exhaustLED OFF LED Error Code Service AnalysisSymptom Cause Remedy Component Damage HazardProblem Cause Remedy Heating Service AnalysisCooling Service Analysis Inputs Outputs EconoMi$er IV Input/Output LogicSTART-UP Checklist

48HJ004---007, 48HE003---006 specifications

Carrier has long been a trusted name in the HVAC industry, and its models 48HJ004---007 and 48HE003---006 continue that legacy, offering efficient, reliable climate control solutions. These models are designed for different applications, ensuring optimal performance in a variety of environments.

The 48HJ series features advanced rooftop units that are ideal for commercial settings. They come equipped with high-efficiency scroll compressors that provide superior cooling and heating capabilities. This series is noted for its compact design, allowing for easy installation on rooftops or other constrained spaces. The units offer variable capacity operation, which enables them to efficiently meet varying heating and cooling demands without unnecessary energy consumption.

One of the standout features of the 48HJ series is its use of advanced microprocessor controls. This technology allows for precise temperature management and system diagnostics, enhancing the ease of operation while ensuring maximum comfort. Additionally, the series supports advanced connectivity options, enabling integration with building management systems. This allows for remote monitoring and control, making it easier for facility managers to keep track of performance and energy usage.

On the other hand, the 48HE series specializes in high-efficiency heating and cooling performance. These units are designed for larger commercial spaces and come with robust features for enhanced durability and efficiency. Like the 48HJ series, the 48HE models utilize scroll compressors and are equipped with a high-efficiency fan setup for improved airflow and reduced noise levels.

The 48HE also includes an innovative heat pump option, which allows the system to reverse the cooling process to provide heating, making it versatile across different seasonal demands. Both series are designed with eco-friendly refrigerants that comply with the latest environmental regulations, ensuring a minimized ecological footprint.

In terms of energy efficiency, both the 48HJ and 48HE series hold impressive SEER and EER ratings, contributing to reduced operational costs over time. The units are also built with durable, corrosion-resistant materials, ensuring longevity and low maintenance needs.

In conclusion, Carrier 48HJ004---007 and 48HE003---006 models are designed with cutting-edge technology, energy efficiency, and flexibility in mind. Their robust features make them ideal choices for commercial applications, providing reliable comfort and operational excellence. Whether for cooling or heating, these systems stand out in performance and sustainability, earning Carrier's reputation as a leader in the HVAC market.