Carrier 48HE003---006, 48HJ004---007 FIRE, Explosion Hazard, Roof Curb, Alternate Unit Support

Page 2

!

WARNING

FIRE, EXPLOSION HAZARD

Failure to follow this warning could death and/or

property damage.

 

Disconnect gas piping from unit when leak testing at

pressure greater than 1/2 psig. Pressures greater than 1/2

psig will cause gas valve damage resulting in hazardous

condition. If gas valve is subjected to pressure greater than

1/2 psig, it must be replaced before use. When pressure

testing field-supplied gas piping at pressures of 1/2 psig or

less, a unit connected to such piping must be isolated by

manually closing the gas valve(s).

 

 

 

INSTALLATION

48HE,HJ

Unit is shipped in the vertical discharge configuration. To convert

 

 

to horizontal discharge application, remove duct opening covers.

 

Using the same screws, install covers on duct openings in

 

basepan of unit with insulation-side down. Seals around

 

 

openings must be tight. (See Fig. 1.)

C06108

Fig. 1 ---Horizontal Conversion Panels

Step 1 Provide Unit Support

ROOF CURB

Assemble and install accessory roof curb in accordance with instructions shipped with curb. (See Fig. 2.) Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can result in air leaks and poor unit performance.

Curb should be level. Unit leveling tolerances are shown in Fig.

3.This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

SLAB MOUNT (Horizontal Units Only)

Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of

condenser-coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT

When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

Step 2 Field Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg with economizer or 0.45 in. wg without economizer.

These units are designed for a minimum continuous return-air temperature in heating of 50_F (dry bulb), or an intermittent operation down to 45_F (dry bulb), such as when used with a night setback thermostat.

To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45_F. Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.

Step 3 Install External Trap for

Condensate Drain

The unit’s 3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. The center drain plug looks like a star connection, however it can be removed with a 1/2-in. socket drive extension. (See Fig. 4.) The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.). (See Fig. 5.)

Step 4 Rig and Place Unit

Inspect unit for transportation damage, and file any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and 2 and Fig. 6 for additional information. Operating weight is shown in Table 1 and 2 and Fig. 6.

2

Image 2
Contents Installation Instructions Electrical Shock HazardAlternate Unit Support FIRE, Explosion HazardRoof Curb 48HE,HJ Positioning Install Flue HoodProperty Damage Hazard 48HJ Unit Operating Dimensions Weight48HE 48HJ004-007 Base Unit Dimensions 48HE003-006 Base Unit Dimensions Heat anticipator settings Field power supplyField control wiring Physical Data 48HJ Nominal CapacityHJE HJD Physical Data 48HE HEE HED Power Wiring Connections Electrical Data 48HE 48HE003---006Electrical Data 48HJ 38.2 242 208/230---3---60 187 254 12.4 Manual outdoor damper AssemblyHUMIDI-MIZERADAPTIVE Dehumidification System Convenience outletTypical Humidi-MiZer t Adaptive Dehumidification System Install the Indoor Air Quality CO2 Sensor Install the Supply Air Temperature SAT SensorOutdoor Air Temperature Sensor OAT Enthalpy Sensors and ControlPremierLinkSensor Usage PremierLink ControllerPremierLinktController Installed Return Air Enthalphy Sensor EconoMi$er IV Component LocationsOutdoor Air Temperature OAT Sensor ECONOMI$ER IV Standard SensorsECONOMI$ER IV Control Modes EconoMi$er IV Wiring RUNIndoor Air Quality IAQ Sensor Input Exhaust Set Point AdjustmentDifferential Enthalphy Control Damper Movement Minimum Position ControlThermostats Enthalpy Changeover Set Points Demand Controlled Ventilation DCVBelt drive motors Adjust Evaporator-Fan SpeedDehumidification of Fresh Air with DCV Control CO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor 48HJ Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory static pressure Evaporator-Fan Motor Data High-Static MotorsUnit ARI Octave Bands Rating 48HJ Outdoor Sound Power Total Unit48HE Outdoor Sound Power Total Unit Airflow1200 Rpm Bhp1100 1300Rpm Bhp Watts 1600 Rpm Bhp WattsWatts Rpm Bhp 1200 1700Rpm Bhp Watts 1500 1642 2333 17042700 Watts Rpm Bhp 18002600 2800Bhp 600 Bhp Watts Rpm2700 2800 2900 3000 Watts Rpm Bhp 900 Bhp Watts 900Watts Rpm 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 1250 1500 1750 2000 2250 2500 2750 3000 Unit Preparation Internal WiringRefrigerant Service Ports Gas PipingHeating CoolingMain Burners Operating Sequence Cooling units without economizer Safety ReliefVentilation Continuous Fan Heating units without economizerDX Cooling Temperature Control Example Routine 3 OATNormal Design Operation Subcooling ModeUnits with HUMIDI-MIZERADAPTIVE Dehumidification System Condenser coil CleaningEvaporator Coil One-Row CoilsFilters Condenser-Fan AdjustmentHigh Pressure Switch Lubrication CompressorHUMIDI-MIZERSYSTEM Charging Cooling Charging Chart Standard 48HJ006 To USE Cooling Charging CHART, Standard Unit Flue Gas Passageways Combustion-Air BlowerRemoval and Replacement of GAS Train See Limit SwitchLED Error Code Description Burner IgnitionReplacement Parts LOW HeatOFM Dcv demand controlled ventilation and power exhaust Unit TroubleshootingEconomi$er IV Troubleshooting Economi$er IV troubleshooting completionComponent Damage Hazard LED Error Code Service AnalysisSymptom Cause Remedy LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsSTART-UP Checklist

48HJ004---007, 48HE003---006 specifications

Carrier has long been a trusted name in the HVAC industry, and its models 48HJ004---007 and 48HE003---006 continue that legacy, offering efficient, reliable climate control solutions. These models are designed for different applications, ensuring optimal performance in a variety of environments.

The 48HJ series features advanced rooftop units that are ideal for commercial settings. They come equipped with high-efficiency scroll compressors that provide superior cooling and heating capabilities. This series is noted for its compact design, allowing for easy installation on rooftops or other constrained spaces. The units offer variable capacity operation, which enables them to efficiently meet varying heating and cooling demands without unnecessary energy consumption.

One of the standout features of the 48HJ series is its use of advanced microprocessor controls. This technology allows for precise temperature management and system diagnostics, enhancing the ease of operation while ensuring maximum comfort. Additionally, the series supports advanced connectivity options, enabling integration with building management systems. This allows for remote monitoring and control, making it easier for facility managers to keep track of performance and energy usage.

On the other hand, the 48HE series specializes in high-efficiency heating and cooling performance. These units are designed for larger commercial spaces and come with robust features for enhanced durability and efficiency. Like the 48HJ series, the 48HE models utilize scroll compressors and are equipped with a high-efficiency fan setup for improved airflow and reduced noise levels.

The 48HE also includes an innovative heat pump option, which allows the system to reverse the cooling process to provide heating, making it versatile across different seasonal demands. Both series are designed with eco-friendly refrigerants that comply with the latest environmental regulations, ensuring a minimized ecological footprint.

In terms of energy efficiency, both the 48HJ and 48HE series hold impressive SEER and EER ratings, contributing to reduced operational costs over time. The units are also built with durable, corrosion-resistant materials, ensuring longevity and low maintenance needs.

In conclusion, Carrier 48HJ004---007 and 48HE003---006 models are designed with cutting-edge technology, energy efficiency, and flexibility in mind. Their robust features make them ideal choices for commercial applications, providing reliable comfort and operational excellence. Whether for cooling or heating, these systems stand out in performance and sustainability, earning Carrier's reputation as a leader in the HVAC market.