Carrier 48HJ004---007 Units with HUMIDI-MIZERADAPTIVE Dehumidification System, Subcooling Mode

Page 49

SSPT reading is available

S OAT ± SPT

SEconomizer Position is NOT forced

If any of the above conditions are not met, the economizer submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated every 30 seconds.

If an optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.

If field-installed accessory CO2 sensors are connected to the PremierLinkcontrol, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed.

HEATING - UNIT WITH ECONOMI$ER2, PREMIER- LINK CONTROL AND A ROOM SENSOR

Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain Supply-Air Temperature (SAT) if the following qualifying conditions are met:

SIndoor fan has been on for at least 30 seconds. S COOL mode is not active.

SOCCUPIED, TEMP. COMPENSATED START or HEAT mode is active.

SSAT reading is available.

SFire shutdown mode is not active.

If all of the above conditions are met, the number of heat stages is calculated; otherwise the required number of heat stages will be set to 0.

If the PremierLink controller determines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied.

Staging should be as follows: If Heating PID STAGES=2

SHEAT STAGES=1 (50% capacity) will energize HS1 S HEAT STAGES=2 (100% capacity) will energize HS2

If Heating PID STAGES=3 and AUXOUT = HS3

SHEAT STAGES=1 (33% capacity) will energize HS1 S HEAT STAGES=2 (66% capacity) will energize HS2 S HEAT STAGES=3 (100% capacity) will energize HS3

In order to prevent short cycling, the unit is locked into the Heating mode for at least 10 minutes when HS1 is deenergized. When HS1 is energized the induced-draft motor is then energized and the burner ignition sequence begins. On units equipped for two stages of heat, when additional heat is needed, HS2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the space condition is satisfied and HS1 is deenergized the IFM stops after a 45-second time-off delay unless in the occupied mode. The fan will run continuously in the occupied mode as required by national energy and fresh air standards.

UNITS WITH HUMIDI-MIZERADAPTIVE

DEHUMIDIFICATION SYSTEM

Normal Design Operation

When the rooftop operates under the normal sequence of operation, the compressors will cycle to maintain indoor conditions. (See Fig. 53.)

The Humidi-MiZer adaptive dehumidification system includes a factory-installed Motormasterlow ambient control to keep the

head and suction pressure high, allowing normal design cooling mode operation down to 0° F.

Subcooling Mode

When subcooling mode is initiated, this will energize (close) the liquid line solenoid valve (LLSV) forcing the hot liquid refrigerant to enter into the subcooling coil. (See Fig. 54.)

As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil. The liquid is further subcooled to a temperature approaching the evaporator leaving-air temperature. The liquid then enters a thermostatic expansion valve (TXV) where the liquid drops to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid, so the liquid then enters the Acutroldevice at the evaporator coil.

The liquid enters the evaporator coil at a temperature lower than

 

in standard cooling operation. This lower temperature increases

 

48HE,HJ

the latent capacity of the rooftop unit. The refrigerant passes

 

through the evaporator and is turned into a vapor. The air passing

 

over the evaporator coil will become colder than during normal

 

operation. However, as this same air passes over the subcooling

 

coil, it will be slightly warmed, partially reheating the air.

 

Subcooling mode operates only when the outside air

 

temperature is warmer than 40_F. A factory-installed temperature

 

switch located in the condenser section will lock out subcooling

 

mode when the outside temperature is cooler than 40_F.

 

The scroll compressors are equipped with crankcase heaters to

 

provide protection for the compressors due to the additional

 

refrigerant charge required by the subcooling/reheat coil.

 

When in subcooling mode, there is a slight decrease in system

 

total gross capacity (5% less), a lower gross sensible capacity

 

(20% less), and a greatly increased latent capacity (up to 40%

 

more).

 

C06135

Fig. 53 ---Humidi-MiZer Normal

Design Cooling Operation

49

Image 49
Contents Electrical Shock Hazard Installation InstructionsRoof Curb FIRE, Explosion HazardAlternate Unit Support 48HE,HJ Property Damage Hazard Install Flue HoodPositioning 48HE Unit Operating Dimensions Weight48HJ 48HJ004-007 Base Unit Dimensions 48HE003-006 Base Unit Dimensions Field control wiring Field power supplyHeat anticipator settings Nominal Capacity Physical Data 48HJHJE HJD Physical Data 48HE HEE HED Power Wiring Connections 48HE003---006 Electrical Data 48HEElectrical Data 48HJ 38.2 242 208/230---3---60 187 254 12.4 HUMIDI-MIZERADAPTIVE Dehumidification System AssemblyManual outdoor damper Convenience outletTypical Humidi-MiZer t Adaptive Dehumidification System Outdoor Air Temperature Sensor OAT Install the Supply Air Temperature SAT SensorInstall the Indoor Air Quality CO2 Sensor Enthalpy Sensors and ControlPremierLink Controller PremierLinkSensor UsagePremierLinktController Installed EconoMi$er IV Component Locations Return Air Enthalphy SensorECONOMI$ER IV Standard Sensors Outdoor Air Temperature OAT SensorECONOMI$ER IV Control Modes RUN EconoMi$er IV WiringDifferential Enthalphy Control Exhaust Set Point AdjustmentIndoor Air Quality IAQ Sensor Input Thermostats Minimum Position ControlDamper Movement Demand Controlled Ventilation DCV Enthalpy Changeover Set PointsDehumidification of Fresh Air with DCV Control Adjust Evaporator-Fan SpeedBelt drive motors Belt Drive Motor Mounting CO2Sensor Standard SettingsAccessory static pressure 48HJ Fan Rpm at Motor Pulley Setting With High-Static MotorEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors48HE Outdoor Sound Power Total Unit 48HJ Outdoor Sound Power Total UnitUnit ARI Octave Bands Rating Airflow1100 Rpm Bhp1200 1300Rpm Bhp Watts Watts Rpm Bhp 1200 Rpm Bhp Watts1600 17001642 2333 1704 Rpm Bhp Watts 15002600 Watts Rpm Bhp 18002700 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 Bhp Watts 1700 1800 1900 20001900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 1250 1500 1750 2000 2250 2500 2750 3000 Refrigerant Service Ports Internal WiringUnit Preparation Gas PipingMain Burners CoolingHeating Ventilation Continuous Fan Safety ReliefOperating Sequence Cooling units without economizer Heating units without economizerRoutine 3 OAT DX Cooling Temperature Control ExampleUnits with HUMIDI-MIZERADAPTIVE Dehumidification System Subcooling ModeNormal Design Operation Evaporator Coil CleaningCondenser coil One-Row CoilsHigh Pressure Switch Condenser-Fan AdjustmentFilters Lubrication CompressorHUMIDI-MIZERSYSTEM Charging Cooling Charging Chart Standard 48HJ006 To USE Cooling Charging CHART, Standard Unit Combustion-Air Blower Flue Gas PassagewaysLED Error Code Description Limit SwitchRemoval and Replacement of GAS Train See Burner IgnitionLOW Heat Replacement PartsOFM Economi$er IV Troubleshooting Unit TroubleshootingDcv demand controlled ventilation and power exhaust Economi$er IV troubleshooting completionSymptom Cause Remedy LED Error Code Service AnalysisComponent Damage Hazard LED OFFProblem Cause Remedy Heating Service AnalysisCooling Service Analysis Inputs Outputs EconoMi$er IV Input/Output LogicSTART-UP Checklist

48HJ004---007, 48HE003---006 specifications

Carrier has long been a trusted name in the HVAC industry, and its models 48HJ004---007 and 48HE003---006 continue that legacy, offering efficient, reliable climate control solutions. These models are designed for different applications, ensuring optimal performance in a variety of environments.

The 48HJ series features advanced rooftop units that are ideal for commercial settings. They come equipped with high-efficiency scroll compressors that provide superior cooling and heating capabilities. This series is noted for its compact design, allowing for easy installation on rooftops or other constrained spaces. The units offer variable capacity operation, which enables them to efficiently meet varying heating and cooling demands without unnecessary energy consumption.

One of the standout features of the 48HJ series is its use of advanced microprocessor controls. This technology allows for precise temperature management and system diagnostics, enhancing the ease of operation while ensuring maximum comfort. Additionally, the series supports advanced connectivity options, enabling integration with building management systems. This allows for remote monitoring and control, making it easier for facility managers to keep track of performance and energy usage.

On the other hand, the 48HE series specializes in high-efficiency heating and cooling performance. These units are designed for larger commercial spaces and come with robust features for enhanced durability and efficiency. Like the 48HJ series, the 48HE models utilize scroll compressors and are equipped with a high-efficiency fan setup for improved airflow and reduced noise levels.

The 48HE also includes an innovative heat pump option, which allows the system to reverse the cooling process to provide heating, making it versatile across different seasonal demands. Both series are designed with eco-friendly refrigerants that comply with the latest environmental regulations, ensuring a minimized ecological footprint.

In terms of energy efficiency, both the 48HJ and 48HE series hold impressive SEER and EER ratings, contributing to reduced operational costs over time. The units are also built with durable, corrosion-resistant materials, ensuring longevity and low maintenance needs.

In conclusion, Carrier 48HJ004---007 and 48HE003---006 models are designed with cutting-edge technology, energy efficiency, and flexibility in mind. Their robust features make them ideal choices for commercial applications, providing reliable comfort and operational excellence. Whether for cooling or heating, these systems stand out in performance and sustainability, earning Carrier's reputation as a leader in the HVAC market.