Carrier 50HG014-028 Field Power Wiring Connections, Heat Anticipator Settings

Page 20

LEGEND

EQUIP — Equipment

GND — Ground

NEC — National Electrical Code

TB — Terminal Board

NOTE: The maximum wire size for TB1 is 2/0.

Fig. 12 — Field Power Wiring Connections

 

 

 

THERMOSTAT ASSEMBLY

 

 

 

 

REMOVABLE JUMPER

 

 

 

 

 

 

 

Y1

Y2

 

 

 

 

L

 

RH RC

W1

W2

G

C

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB4

R

Y1

Y2

W1

W2

G

C

X

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

Fig. 13 — Field Control Thermostat Wiring

 

T-55 SPT

 

 

 

T-56 SPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

T2

 

 

 

TH

 

COM

 

SN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB3

 

 

 

 

 

 

 

 

7

 

8

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPT — Space Temperature Sensor

Fig. 14 — Field Control Space

Temperature Sensor Wiring

Set heat anticipator settings as shown inTable 3.

Table 3 — Heat Anticipator Settings

 

 

STAGE 1

 

STAGES 1 AND 2

UNIT SIZE

ELECTRIC

(W1) ON

 

(W1 and W2) ON

50HG

HEAT (kW)

Voltage

 

Voltage

 

 

 

208/240

480

600

208/240

480

600

 

15

0.2

0.2

0.2

0.2

0.2

0.2

014

25

0.2

0.2

0.2

0.4

0.4

0.4

 

50

0.4

0.2

0.2

0.8

0.4

0.4

 

25

0.2

0.2

0.2

0.4

0.4

0.4

016-028

50

0.4

0.2

0.2

0.8

0.4

0.4

 

75

0.4

0.2

0.2

0.8

0.4

0.4

Settings may be changed slightly to provide a greater degree of comfort for a particular installation.

Step 8 — Install Outdoor Air Hood — Perform the following procedure to install the outdoor-air hood:

1.Remove blank panel from return end of unit (hood sec- tion). Save the screws. See Fig. 15 for shipping location of components.

2.Hood sides are fastened to sides of outdoor air opening. Remove the hood sides and save the screws (3 each side).

3.Remove the bracket holding the bottom half of the hood in the shipping position. Remove the hood bottom half and filters (or manual dampers on units so equipped) from outdoor section.

NOTE: On units without economizers, the components are attached to the unit basepan. To access the compo- nents, remove the panel below the outdoor air intake section.

4.Remove inner filter track from shipping position in out- door section. Position inner filter track so the track is fac- ing outward from the unit. Install the filter track with 4 screws provided.

5.Apply seal strip (provided) to back flange of both hood sides where hood side connects to the unit back panel. See Fig. 16.

6.Apply seal strip (provided) to top flange of both hood sides where hood sides connect to the hood top panels. See Fig. 16.

7.Install hood sides to the back panels using the screws from Step 2. The sloped flanges point outward. The drip edges of the side panels should face outward as well. The filter guides should face inward to hold the filters in place. See Fig. 16.

8.Apply seal strip along the entire length of the bottom flange of the hood top. See Fig. 16.

9.Install the bottom part of the hood top using 4 screws pro- vided. See Fig. 16.

10.Remove the packaging from filters (3) and install into the filter tracks. Slide the filters to the sides then place the last filter into the center of the filter track.

NOTE: For units with manual dampers, replace the end filters with the manual dampers. Install the filter in the center between the manual dampers.

11.Install the filter retainer track along the bottom edge of the outdoor air hood using 4 screws provided. See Fig. 16.

12.Install top section of the outdoor air hood using 9 screws provided. See Fig. 16. See Fig. 17 for a picture of the assembled outdoor air hood.

NOTE: For filter removal, remove the four screws holding the filter retainer. The filters can then be removed, cleaned, or replaced. Install the filters by reversing the procedure.

MANUAL DAMPER ASSEMBLY — For units equipped with manual dampers, the assembly process is similar to the out- door air hood for units with economizers. There are two slide dampers shipped with the unit to allow for manual setting of the outside air volume. When assembling the hood, place one of the manual slide dampers in each of the end positions and the re- maining filter in the center position. The manual dampers can then be moved to the appropriate position and then locked into place using the screws mounted in the adjustment slots. See Fig. 18.

 

HOOD

HOOD TOP

HOOD TOP

SIDE

(BOTTOM HALF)

 

 

(TOP HALF)

 

 

HOOD

 

 

SIDE

 

 

RETURN AIR

 

 

SECTION

 

 

Fig. 15 — Outdoor-Air Hood Compartment

Shipping Location

20

Image 20
Contents Installation Instructions Roof Curb Details Shipping Rail Removal Rigging Details Base Unit Dimensions Physical Data Voltage024 028 Make Unit Duct Connections Make Electrical Connections Electrical Data Units Without Optional Convenience Outlet FLA MCA MocpFeeder Circuit for 208/230-V Unit with 75-kW Electric Heat 020 024 028 Electrical Data Units With Optional Convenience Outlet 460 414 506 70.0 100 110 108 125 103 111 575 518 633 55.0 020 024 028 Field Power Wiring Connections Heat Anticipator SettingsOutdoor Air Hood Details Power Exhaust or Barometric Relief Damper Mounting Details Bracket and Hood Positioning Copyright 2003 Carrier Corporation