Carrier 50HG014-028 Electrical Data Units Without Optional Convenience Outlet, FLA MCA Mocp

Page 10

Table 2A — Electrical Data (Units Without Optional Convenience Outlet)

UNIT

NOMINAL

VOLTAGE

 

 

COMPRESSOR

 

 

 

OFM

 

ELECTRIC

 

 

IFM

 

 

POWER

POWER

 

DISCONNECT

SIZE

VOLTAGE

RANGE

No. 1

 

No. 2

No. 3

 

 

 

 

HEAT

 

 

 

 

EXHAUST

SUPPLY

 

SIZE

50HG

(3 Ph, 60 Hz)

Min

Max

RLA

LRA

 

RLA

LRA

RLA

LRA

Qty

Hp

 

FLA

kW

FLA

Hp

FLA

Qty

 

Hp

FLA

MCA

MOCP*

FLA

 

 

 

 

(ea)

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

10.6/

9.6

 

60/ 59

70/ 70

70/ 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

5.9

72/

71

90/

80

80/

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

16.7/15.2

 

66/ 64

80/ 80

80/ 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

5.9

78/

76

90/

90

90/

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

10.6/

9.6

 

60/ 60

70/ 70

70/ 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/16

33/

38

2

 

1.0

5.9

72/

74

90/

80

80/

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

16.7/15.2

 

66/ 67

80/ 80

80/ 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

19.2

146.0

 

19.2

146.0

4.0

1/4

 

1.5

 

 

 

2

 

1.0

5.9

78/

81

90/

90

90/

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

10.6 /9.6

 

78/ 87

80/ 90

80/ 90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19/25

52/

60

2

 

1.0

5.9

93/102

100/110

90/100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

16.7/15.2

 

86/ 94

90/100

80/ 90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

5.9

101/109

110/110

100/110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

10.6/

9.6

 

143/132

150/150

150/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38/50

104/120

2

 

1.0

5.9

158/147

175/150

150/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

16.7/15.2

 

151/139

175/150

150/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

5.9

166/154

175/175

175/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

4.8

 

 

29

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

35

 

40

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

7.6

 

 

32

 

40

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

38

 

45

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

4.8

 

 

29

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

18

 

 

2

 

1.0

3.1

36

 

40

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

7.6

 

 

32

 

40

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

014

460

414

506

9.5

73.0

 

9.5

73.0

4.0

1/4

 

0.7

 

 

 

 

2

 

1.0

3.1

40

 

45

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

4.8

 

 

44

 

45

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

30

 

 

2

 

1.0

3.1

51

 

60

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

7.6

 

 

47

 

50

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

55

 

60

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

4.8

 

 

66

 

80

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

60

 

 

2

 

1.0

3.1

74

 

80

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

7.6

 

 

70

 

80

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

77

 

80

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

3.9

 

 

24

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

30

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

6.1

 

 

26

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

32

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

3.9

 

 

24

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

15

 

 

2

 

1.0

3.1

31

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

6.1

 

 

26

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

633

7.6

58.4

 

7.6

58.4

4.0

1/4

 

0.7

 

 

 

 

2

 

1.0

3.1

34

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

3.9

 

 

35

 

35

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

24

 

 

2

 

1.0

3.1

43

 

45

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

6.1

 

 

38

 

40

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

45

 

50

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

3.9

 

 

62

 

70

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

46

 

 

2

 

1.0

3.1

70

 

80

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

6.1

 

 

65

 

70

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

1.0

3.1

73

 

80

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND AND NOTES FOR TABLES 2A AND 2B

 

 

LEGEND

FLA

Full Load Amps

MCA

Minimum Circuit Amps

HACR — Heating, Air Conditioning and

MOCP — Maximum Overcurrent Protection

 

Refrigeration

NEC

National Electrical Code

IFM

Indoor (Evaporator) Fan Motor

OFM

Outdoor (Condenser) Fan Motor

LRA

Locked Rotor Amps

RLA

Rated Load Amps

*Fuse or HACR circuit breaker.

†208/230 v 75-kW Electric Heat units must use dual-point wiring. The main table lists the branch circuit values for the refrigeration part of the system. The following two tables list the branch circuit values for the electric heat and values for a feeder circuit for both branch circuits.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance. 7

%Voltage Imbalance = 100 x 457

=1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.The 75-kW 208/240-v electric heat can be factory installed but it must be wired sepa- rately in the field.

4.The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v units, respectively.

5.The FLA load amps provided in the table for electric heaters are based on 208/240, 480 and 600 v.

6. MCA calculation for 50HG014-028 units with electric heaters over 50 kW is = 1.25 x (IFM + Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA).

10

Image 10
Contents Installation Instructions Roof Curb Details Shipping Rail Removal Rigging Details Base Unit Dimensions Physical Data Voltage024 028 Make Unit Duct Connections Make Electrical Connections Electrical Data Units Without Optional Convenience Outlet FLA MCA MocpFeeder Circuit for 208/230-V Unit with 75-kW Electric Heat 020 024 028 Electrical Data Units With Optional Convenience Outlet 460 414 506 70.0 100 110 108 125 103 111 575 518 633 55.0 020 024 028 Field Power Wiring Connections Heat Anticipator SettingsOutdoor Air Hood Details Power Exhaust or Barometric Relief Damper Mounting Details Bracket and Hood Positioning Copyright 2003 Carrier Corporation