Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
•ROOF CURB
•ALTERNATE UNIT SUPPORT
Step 2 — Remove Shipping Rails . . . . . . . . . . . . . . . . 3 Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3
•POSITIONING
•ROOF MOUNT
•INSTALLATION ONTO CURB
Step 4 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 8 Step 5 — Make Unit Duct Connections . . . . . . . . . . . 8 Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . . 9 Step 7 — Make Electrical Connections . . . . . . . . . . . 9
•FIELD POWER SUPPLY
•FIELD CONTROL WIRING
Step 8 — Install
Step 9 — Position Optional Power Exhaust
or Barometric Relief Damper Hood. . . . . . . . . . . . 22 Step 10 —
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform the basic maintenance functions of replacing filters. All other operations should be performed by trained service personnel. When working on
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
IMPORTANT: Units have high ambient operating lim- its. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.
INSTALLATION
Step 1 — Provide Unit Support
ROOF CURB — Assemble or install accessory roof curb in accordance with instructions shipped with this accessory. See Fig. 1. Install insulation, cant strips, roofing, and counter flash- ing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb must be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is
±1/16 in. per linear ft in any direction. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When a curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equal- ly spaced
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.