Carrier 50HG014-028 installation instructions Make Electrical Connections

Page 9

NOTE: Dimensions A, A, B, and Bare obtained from field-supplied ceiling diffuser.

Shaded areas indicate block-off pans.

Fig. 9 — Concentric Duct Details

Step 6 — Trap Condensate Drain — See Fig. 10 for drain location. One 3/4-in. half coupling is provided outside unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. See Fig. 11.

Step 7 — Make Electrical Connections

FIELD POWER SUPPLY — Unit is factory wired for volt- age shown on unit nameplate.

When installing units, provide disconnect per NEC (Nation- al Electrical Code) of adequate size (MOCP [Maximum Overcurrent protection] of unit is on the informative plate). See Tables 2A and 2B. All field wiring must comply with NEC and local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 12 for power wiring connections to the unit power terminal block and equipment grounds.

Route power and ground lines through control box end pan- el or unit basepan (see Fig. 4) to connections as shown on unit wiring diagram and Fig. 12.

The correct power phasing is critical to the operation of the scroll compressors. An incorrect phasing will result in an alarm being generated and compressor operation lockout. Should this occur, power phase correction must be made to the incoming power.

The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (American National Standards Institute/National Fire Protection Association).

Field wiring must conform to temperature limitations for type ‘‘T’’ wire. All field wiring must comply with NEC and local requirements.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

FIELD CONTROL WIRING — Unit can be controlled with either a Carrier-approved accessory thermostat or a Carrier- approved space temperature sensor. Install thermostat accord- ing to the installation instructions included with accessory. Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature.

Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 13 or 14.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.

Fig. 10 — Condensate Drain Details

NOTE: Dimensions in [] are in millimeters.

Fig. 11 — Condensate Drain Piping Details

9

Image 9
Contents Installation Instructions Roof Curb Details Shipping Rail Removal Rigging Details Base Unit Dimensions Voltage Physical Data024 028 Make Unit Duct Connections Make Electrical Connections FLA MCA Mocp Electrical Data Units Without Optional Convenience OutletFeeder Circuit for 208/230-V Unit with 75-kW Electric Heat 020 024 028 Electrical Data Units With Optional Convenience Outlet 460 414 506 70.0 100 110 108 125 103 111 575 518 633 55.0 020 024 028 Heat Anticipator Settings Field Power Wiring ConnectionsOutdoor Air Hood Details Power Exhaust or Barometric Relief Damper Mounting Details Bracket and Hood Positioning Copyright 2003 Carrier Corporation