Xanbus Automatic Generator Start Installation
Type 14
Type 14 works with
IMPORTANT: Since Type 14 does not monitor the generator run status, illumination of the Generator On light on the AGS does not necessarily indicate the generator is actually running. If this generator type is used, ensure the generator’s integrated controller has the ability to monitor, control and report generator status and faults. With Type 14, no faults are raised if the generator fails to start or stop or is externally started or stopped.
Once the generator is stopped, there is a
AGS Harness Wires |
| Generator Wires | |
Relay 1 | 14 | 5A fuse | RUN |
16 |
| RELAY 1 RETURN | |
|
|
For additional information, see “Circuit Limitations” on page 11.
Figure 22 Type 14 Connection Diagram (two-wire)
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | RunStop |
Relay 3 mode | Not used |
Gen Run signal hold time | 0 s |
Preheat time | 0 s |
Preheat to crank delay | 0 s |
Crank time | 0 s |
Crank retry time | 0 s |
Gen Cool Down | 30 s |
Gen Spin Down | 600 s |
Shutdown bypass time | 0 s |
Start tries | 1 |
28 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |