Xanbus Automatic Generator Start Installation

Type 14

Type 14 works with two-wire generators that use an integrated engine control module to perform the necessary relay cycles to start and stop the generator. This is similar to Type 8 but without the B+ signal requirement. The AGS closes relay 1 to start the generator and illuminates the Generator On light to indicate the relay is closed. To stop the generator, relay 1 is opened and the Generator On light turned off.

IMPORTANT: Since Type 14 does not monitor the generator run status, illumination of the Generator On light on the AGS does not necessarily indicate the generator is actually running. If this generator type is used, ensure the generator’s integrated controller has the ability to monitor, control and report generator status and faults. With Type 14, no faults are raised if the generator fails to start or stop or is externally started or stopped.

Once the generator is stopped, there is a 10-minute delay before the generator can be re-started using the AGS. This is to allow the generator’s integrated engine controller to completely and safely shut down the generator. This delay can be adjusted by changing the Gen Spin down setting.

AGS Harness Wires

 

Generator Wires

Relay 1

14

5A fuse

RUN

16

 

RELAY 1 RETURN

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 22 Type 14 Connection Diagram (two-wire)

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

RunStop

Relay 3 mode

Not used

Gen Run signal hold time

0 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

0 s

Crank retry time

0 s

Gen Cool Down

30 s

Gen Spin Down

600 s

Shutdown bypass time

0 s

Start tries

1

28

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Page 38
Image 38
Xantrex Technology 809-0915 manual Type 14 Connection Diagram two-wire